Adjustment examples..........................5 10 Error search ............................6 11 Technical data ............................6 12 Housing Type K ............................8 1 Display and controls Adjust Full- scale Adjust Zero LED green - in Operation MU100U 10730-0701-00 Page 2 / 8 www.ziehl.de...
The universal transmitter MU100U can be connected to any supply voltage between 24 V and 240 V, DC or AC voltage can be connected. Input and output signals are galvanically isolated. Signals DC 0/4-20 mA or 0-0 V can be connected to the inputs.
A circuit-breaker or switch must be situated within easy reach of the unit and fused. Installation excess current protection should be ≤ 10 A. MU100U 10730-0701-00 Page 4 / 8 www.ziehl.de...
2) Input Output 0…20 mA or 0…10 V Zero point: at the input (terminals 1 and 2) set current constant to 4.800 mA. Adjust the current or voltage output with the potentiometer “Zero”. MU100U 10730-0701-00 Page 5 / 8 www.ziehl.de...
0,025% *K Nominal rise time t= 0,9 50 ms Test conditions EN 61010-1 / EN 50178 Rated impulse voltage 4000 V Overvoltage category Pollution degree Rated insulation voltage Ui 300 V On-period 100 % MU100U 10730-0701-00 Page 6 / 8 www.ziehl.de...
Page 7
Protection class housing / terminals IP40 / IP 20 Snap mounting on 35 mm standard rail EN60715 or Mounting M4 screws (additional bar not included) Mounting position Various Weight app. 200 g Subject to technical changes MU100U 10730-0701-00 Page 7 / 8 www.ziehl.de...