Trenton TTL Series Installation Instructions Manual
Ttl two-way low profile evaporators, high, medium and low temperature applications -10 degrees f (-23.3 degrees c) or above box temperature, air, electric or hot gas
defrost (reverse cycle)
TTL Two-Way Low Profile Evaporators PRODUCT DATA & INSTALLATION High, Medium and Low Bulletin T30-TTL-PDI-16 Temperature Applications 1087831 Part # -10°F (-23.3 °C) or Above PRODUCT SUPPORT scan: Box Temperature web: t-rp.com/ttl email: evaps@t-rp.com call: 1-844-893-3222 x520 Air, Electric or Hot Gas Defrost (Reverse Cycle) INCLUDES RATINGS FOR CONTENTS...
NOMENCLATURE 1 1 5 - S1 Model Name Design Version T = Trenton Product Name Unit Electrical Designaton. TL = Two Way Low Profile Evaporator S1 = 115/1/60 S2 = 208-230/1/60 S6 = 200-220/1/50 X 100 = Nominal Capacity (10°F TD, 60Hz), Btu/H Defrost Type.
60Hz ELECTRICAL DATA 115/1/60 AIR DEFROST FAN MOTOR(S) - FAN MOTOR(S)- FAN MOTOR(S)- MODEL SHADED POLE (STANDARD) (OPTIONAL) (OPTIONAL) TOTAL TOTAL TOTAL FANS MOTOR M.C.A. M.O.P WATTS MOTOR M.C.A. M.O.P WATTS MOTOR M.C.A. M.O.P WATTS 010MA-S1A 0.65 0.81 015MA-S1A 0.65 0.81 020MA-S1A 0.65...
Page 5
60Hz ELECTRICAL DATA 208-230/1/60 AIR DEFROST FAN MOTOR(S) - FAN MOTOR(S)- FAN MOTOR(S)- MODEL SHADED POLE (STANDARD) (OPTIONAL) (OPTIONAL) TOTAL TOTAL TOTAL FANS MOTOR M.C.A. M.O.P WATTS MOTOR M.C.A. M.O.P WATTS MOTOR M.C.A. M.O.P WATTS 010MA-S2A 0.24 0.30 015MA-S2A 0.24 0.30 020MA-S2A 0.24...
60Hz WIRING DIAGRAM AIR DEFROST - ALL VOLTAGES WITH DEFROST TIME CLOCK WITHOUT DEFROST TIME CLOCK REFER TO EVAPORATOR REFER TO EVAPORATOR NAMEPLATE FOR ELECTRICAL NAMEPLATE FOR ELECTRICAL REQUIREMENTS REQUIREMENTS L1 L2(N) L2(N) DEFROST CLOCK PARAGON # 8145 OR EQUIVALENT FUSE OR FUSE OR CIRCUIT...
60Hz WIRING DIAGRAM ELECTRIC DEFROST - 115V FOR ALL MODELS WITHOUT DEFROST HEATER CONTACTOR FOR ALL MODELS USING DEFROST HEATER CONTACTOR USING MAXIMUM 15A HEATER OVERCURRENT PROTECTION REFER TO EVAPORATOR NAMEPLATE FOR ELECTRICAL REFER TO EVAPORATOR DEFROST CLOCK REQUIREMENTS PARAGON # 8145 NAMEPLATE FOR ELECTRICAL DEFROST CLOCK OR EQUIVALENT...
60Hz DIMENSIONAL DATA - 1 FAN Inches (mm) PIPING CONNECTION SIDE VIEW CONNECTION END VIEW 7/8 (22 mm) dia. knockouts 2 connection end 9/16 (14 mm) dia. knockouts 2 each side 7/8 (22 mm) dia. knockouts 2 each side AIR IN 1/2 (12 mm) dia.
Page 10
60Hz DIMENSIONAL DATA - 2 & 3 FAN Inches (mm) PIPING CONNECTION END VIEW NOTES: 1). Electric defrost views shown. Air defrost models have identical dimensioning. 2). Electrical connection end is opposite the piping end on multiple fan models. AIR IN 23-3/4 (603) 9/16 (14 mm) dia...
Page 11
60Hz NOZZLE SELECTIONS (FACTORY INSTALLED) For all applications and refrigerants Model TTL Nozzle Model TTL Nozzle 009LE 010MA/ME 013LE 015MA/ME 017LE L-1/4 020MA/ME 025MA/ME 021LE L-1/3 032MA/ME L-1/4 028LE L-1/2 038MA/ME L-1/3 033LE L-1/2 060MA/ME L-1/2 052LE 077MA/ME L-3/4 066LE 115MA/ME 099LE L-1 1/2...
60Hz INSTALLATION INSTRUCTIONS INSPECTION LOCATION Careful inspection of all parts when received for loss The evaporator is designed to be mounted to the or damage in transit is very important - ceiling of the box or cabinet. Refrigeration piping and Remember, you, the consignee, must make any electrical connections are routed to the rear sides claim necessary against the transportation company.
60Hz INSTALLATION INSTRUCTIONS (CONT’D) DRAIN LINE When fan delay thermostats are installed the fans The drain line should be run from the drain may not start up until the coil temperature connection, sloping at least 4” vertical drop for reaches approximately 26°F. On initial start up it may every foot of horizontal distance .
“AS BUILT” SERVICE PARTS LIST Service Parts List Label To Be Attached HERE NATIONAL REFRIGERATION & AIR CONDITIONING CANADA CORP. 159 Roy Blvd. Brantford Ontario Canada N3R 7K1 PHONE: (519) 751-0444 800-463-9517 FAX (519) 753-1140 www.t-rp.com Due to the manufacturer’s policy of continuous product improvement, we reserve the right to make changes without notice. 23/06/17...