OPERATING INSTRUCTIONS
STATIONARY VENTED LEAD ACID BATTERIES
Assembly and CE-marking by.........................
.........................................................................
Commissioning by............................................
WARNINGS
Observe operating instructions and position them within sight of the battery! Work only on
batteries under instruction of skilled personnel!
When working on batteries wear safety glasses and protective clothing! Comply with accident
prevention rules as well as with DIN VDE 0510, VDE 0105 part 1!
No smoking! Do not expose the battery to an open flame, a glowing fire or sparks as explosion
and fire hazards exist.
Acid splashes in the eyes or on the skin must be washed out or off with plenty of water. Then
see a doctor immediately. Clothing exposed to acid should be washed out with water without
delay.
Explosion and fire hazard due to explosive gases escaping from the battery. Caution! Metal
parts of the battery are always live, therefore do not place items or tools on the battery! Avoid
short circuits!
The electrolyte (diluted sulphuric acid) is extremely corrosive.
Block batteries or cells are heavy! Ensure secure installation! Only use suitable transport
equipment!
Dangerous voltages !
Used batteries with this symbol are reusable goods and must be returned to
the recycling process. Used batteries which are not returned to the recycling
process must be disposed of as special waste in accordance with all the
regulations.
OPzS, OPzL and OGi
Number of cells/blocks:
date...................
.................................................
date.................... Type:.........................................
BAE

Advertisement

loading

Summary of Contents for BAE OPzS

  • Page 1 OPERATING INSTRUCTIONS STATIONARY VENTED LEAD ACID BATTERIES OPzS, OPzL and OGi Assembly and CE-marking by......Number of cells/blocks: ................. date..............Commissioning by..........date....Type:......... WARNINGS Observe operating instructions and position them within sight of the battery! Work only on...
  • Page 2 The charge voltage at 20°C must be occur. When charging is finished switch off the charger set for OPzS and OGi at (2,23V x number of or switch over to operating voltage, as per point 2.3. cells)+- 1% and for OPzL (2,25V x number of 2.0 Operation...
  • Page 3 Higher temperatures reduce density electrolyte, lower temperatures increase it. On exceeding the maximum temperature of 55°C, charging must either be stopped or proceed with The temperature correction factor is -0,0007 kg/l reduced current or be switched to float charge to allow the temperature to drop.