Type IAV Undervoltage and Overvo/tage Relays
GEH-12668
100
Function
Tripping Duty
Carry Continuoudy
4
120
140
Per cent of minimum operating voltage
2.
Time-voltage <urves for Types
Fig.
Amperes,
A-c or D-e
I
2-amp Tap
0.2- a rnp Tap
(0.13
Ohm)
(7 Ohms)
Target and
Target and
Seal-in Coil
Seal-in Coil
30
5
4
0.8
160
:ao
200
IAVSIA
IAV52A
and
relays
The tap setting used on the seal-in element is
determined by the current drawn by the trip coil.
The 0.2-ampere tap is for use with trip coils that
operate on currents ranging from 0.2 up to 2.0 am­
peres at the minimum control voltage. If this tap is
used with trip coils requiring more than two amperes,
there is a possibility that the seven ohms resistance
will reduce the current to so low a value that the
breaker will not be tripped.
The 2.0-ampere tap should be used with trip
(
"--·
2 20