KT-Elektronik ModBus-MBus-Gateway Installation And Operating Manual

Firmware version 1.0x,

Advertisement

Quick Links

ModBus-MBus-Gateway
Installation and operating
manual
Firmware version 1.0x,
May 2011

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ModBus-MBus-Gateway and is the answer not in the manual?

Questions and answers

Summary of Contents for KT-Elektronik ModBus-MBus-Gateway

  • Page 1 ModBus-MBus-Gateway Installation and operating manual Firmware version 1.0x, May 2011...
  • Page 2: Table Of Contents

    Installation and operating manual KT-Elektronik Warranty We permanently enhance our products, therefore we reserve the right to make changes to our products at any time and without prior notice. We take no responsibility for the accuracy or completeness of this manual. No liability can be accepted for the use of our products for a buyer specific purpose.
  • Page 3: Installation

    "TROVIS LEITTECHNIK" by SAMSON visualize and monitor the meter data for billing, for example. Operation of the ModBus-MBus-Gateway: data from up to 6 meters configured are read cyclically via MBus from meters and stored in an internal memory of the ModBus-MBus-Gateway. A control system can read the last temporarily stored meter data via Modbus from the ModBus-MBus-Gateway.
  • Page 4: Control System Communication

    Addressing by slave device TROVIS 5573, SOL3-1, SOL3-7 and WPR3 The ModBus-MBus-Gateway automatically takes the address from the slave device. In the worst case, the acquisition of the station address of the slave device takes a few minutes to complete because all station addresses in the supported addressing modes and all supported baud rates are successively tested for recognition of a slave device.
  • Page 5: Display And Operation

    The device has no controls. The device settings are exclusively via a Modbus connection changed. In stand-alone operation, in which no slave device is connected, the setting of the ModBus-MBus-Gateway has to make by control system BMS. If one slave device is connected, the setting of the MBus meter configuration can be adjust by using the operation of slave device.
  • Page 6: Updating The Firmware

    KT-Elektronik Updating the firmware To perform an firmware upgrade of the ModBus-MBus-Gateway, use the software BootManager. At the time of the firmware update it is not allowed to connect one slave device. A firmware upgrade for a connected slave device can be carried out using the software BootManager. In this case the ModBus-MBus-Gateway provides a transparent connection between BootManager and slave device.
  • Page 7: Technical Specification

    KT-Elektronik ModBus-MBus-Gateway Technical specification Interfaces 1 x control system interface BMS: RS485 2 wire network, potential free, 9600 baud, 19200 baud (automatically) 8 bit, no parity, 1 stop bit MODBUS RTU 1 x slave interface: RS-485 2 wire network, slave device potential,...
  • Page 8 KT-Elektronik GmbH Berlinickestrasse 11 12165 Berlin - Germany Telephone: (030) 79 08 05-0 Telefax: (030) 79 08 05-20 EB_11997_ModBus- E-mail: info@kt-elektronik.de MBus- Internet: http://www.kt-elektronik.de Gateway_EN001...