Download Print this page

VERIS INDUSTRIES, INC. AA10 Series Installation Manual

Temperature transmitter, resistive to 4-20ma

Advertisement

Quick Links

Installation Guide
Accessories
RoHS
Compliant
NOTICE
• This product is a Class 2 device.
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classi ed locations.
• Read and understand the instructions before installing this product.
• Turn o all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed by Veris Industries for any consequences arising out of the
use of this material.
Z206880-0A
Page 1 of 2
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Product Overview
The AA10 Series temperature-to-current transmitter is designed for use with 100R platinum, 1k platinum, 10k Type
2, and 10k Type 3 external resistive output devices. When the resistive output from the external device is connected
to the AA10 input terminal, the resistive value is converted to a 4-20 mA signal compatible with most building
control systems.
Product Identification
Sensor Type
AA10
B = 100R platinum, RTD
C = 1k platinum, RTD
D = 10k T2, Thermistor
H = 10k T3, Thermistor
W = 10k T2 high accuracy, Thermistor
Y = 10k T3 high accuracy, Thermistor
Specifications
Transmitter Accuracy
Transmitter Operating Temperature
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
AA10 Series
Temperature Transmitter,
Resistive to 4-20mA
4-20mA Temperature Sensor Range*
Bottom Range Temp
= (choose a valid
temp value)
* Temperature range must be whole numbers where the bottom value is less
than the top value in the range of -25°C to 105°C (-13°F and 221°F).
Current Loop
Class 2; 2-wire, loop powered 4-20mA; 9-30VDC
±1% of span or ±0.1ºC, whichever is greater
(does not include accuracy of resistive element in external
temperature device)
-15° to 50°C (5° to 122°F)
Range
Connectors
2 pluggable terminal block connectors
Encapsulation
Epoxy encapsulated
Temp Scale
Top Range Temp
C = Celsius
= (choose a valid
F = Farenheit
temp value)
TM
1214

Advertisement

loading

Summary of Contents for VERIS INDUSTRIES, INC. AA10 Series

  • Page 1 Resistive to 4-20mA Product Overview The AA10 Series temperature-to-current transmitter is designed for use with 100R platinum, 1k platinum, 10k Type 2, and 10k Type 3 external resistive output devices. When the resistive output from the external device is connected...
  • Page 2 Installation Guide Accessories AA10 Series Dimensions 0.75” (20 mm) Ø 0.3” (8 mm) Ø 0.2” 1.5” (5 mm) (39 mm) 0.5” 0.8” 1.5” (13 mm) (21 mm) (39 mm) 1.5” (39 mm) Installation 1. To mount the AA10 to a surface, use a #6 or #8 pan head sheet metal screw (not included). Remove the terminal block connector before mounting, as the connector may partially block access to the mounting hole.