Download Print this page

Robertshaw 570B Series User Manual

Two-wire vibration sensor

Advertisement

Quick Links

Industrial Products Division
Robertshaw Industrial Products Division
1602 Mustang Drive
Maryville, Tennessee 37801 Telephone:
(865) 981-3100
Fax: (865) 981-3168
FEATURES:
Corrosion resistant
ESD protection
Reverse wiring protection
Overload protection
Hermetic
No trim pots
2.80"
2.12"
1.12"
Typical Circuit
Pin A
+
Pin B
Model 570
R
LOAD
Signal Measuring Circuit
Due to continued research and development, the Manufacturer reserves the right to amend these specifications without notice.
SPECIFICATIONS
DYNAMIC
ELECTRICAL
ENVIRONMENTAL
PHYSICAL
2 pin
connector
1 1/16" hex
NOTES:
1/4-28
mounting hole
+
DC Power
ACCESSORIES SUPPLIED:
Supply
Output (±5% of Full Scale) .............................................
Vibration Range .............................................................
Frequency Response:
–3 dB .....................................................................
Repeatability ..................................................................
Resonant Frequency, mounted, nominal .......................
Transverse Sensitivity, max. ..........................................
Power Requirements (Two wire loop power):
voltage source ........................................................
1
Loop Resistance
at 24 VDC, maximum ........................
Turn on Time ..................................................................
Grounding ......................................................................
Temperature Range .......................................................
Vibration Limit ................................................................
Shock Limit ....................................................................
Electromagnetic Sensitivity, equiv. g .............................
Sealing ...........................................................................
Weight ............................................................................
Sensing Element Design ................................................
Case Material .................................................................
Mounting ........................................................................
Output Connector ...........................................................
Pin A ............................................... plus (+) White
Pin B ............................................. minus (–) Black
2
Cabling
.........................................................................
Torque Limit ...................................................................
Warranty ........................................................................
1
Maximum loop resistance can be calculated by:
R
(max) = -------------------------
L
Loop resistance is the sum of wiring
resistance and the load resistor.
2
Cable resistance equals 40 ohms, total per 1000 ft.
Model
Mode
570B-A
acceleration
570B-B
acceleration
570B-C
acceleration
570B-D
velocity
570B-E
velocity
570B-F
velocity
Model 570B Series
Two-wire Vibration Sensor
Power Source
Vpower – 10 V
20 mA
1/4-28 mounting stud.
Range
Frequency
Response
0 - 5 g peak
2 Hz - 2 kHz
0 - 10 g peak
2 Hz - 2 kHz
0 - 20 g peak
2 Hz - 2 kHz
0 - 0.5 IPS peak
2 Hz - 2 kHz
0 - 1 IPS peak
2 Hz - 2 kHz
0 - 2 IPS peak
2 Hz - 2 kHz
TABLE
4-20 mA DC
see table below
see table below
±2%
see table below
5%
10 VDC - 30 VDC
700Ω
<30 seconds
Case isolated, internally
shielded
–40 to 85°C
250 g peak
2,500 g peak
10 µg/gauss
hermetic, NEMA 4X, IP68
162 grams
PZT ceramic / shear
316L stainless steel
1/4 - 28 tapped hole
2-pin, MIL-C-5015 style
Two conductor shielded
(See Table 1 on back)
30 in lbs. max
1 year
Typical
R
max
L
Voltage
20
500
24
700
26
800
Resonant
Frequency
28 kHz
28 kHz
28 kHz
28 kHz
28 kHz
28 kHz
98549 Rev.G.1 1/04

Advertisement

loading

Summary of Contents for Robertshaw 570B Series

  • Page 1 Model 570B Series Two-wire Vibration Sensor Industrial Products Division SPECIFICATIONS DYNAMIC Robertshaw Industrial Products Division Output (±5% of Full Scale) ..........4-20 mA DC 1602 Mustang Drive Vibration Range ............. see table below Maryville, Tennessee 37801 Telephone: Frequency Response: (865) 981-3100 –3 dB ..............
  • Page 2 Cable generators, and transformers. Finally, avoid routing the cable Clamp through areas prone to ESD. Even though Robertshaw sensors are protected against ESD failure, temporary Machine Surface distortion signals may appear at the output.

This manual is also suitable for:

570b-a570b-b570b-c570b-d570b-e570b-f