This procedure must be carried out by a certified electrician. 1. Connect the PAN-14 sensor to the CT : 2. Connect the two CT’s outputs to the PAN-14 sensor using a 1.0-4.0mm (12-17 AWG) wires as follows: a. Connect the PAN-14 sensor’s terminal marked as ‘1’ to the CT’s terminal marked as ‘S1’...
Page 7
5. Finalize the PAN-14 sensor and the CT’s position on the panel: Maintain a reasonable distance between the CT and the sensor. Place the PAN-14 sensor on the side that is closer to the bridge • (to avoid RF blocking, make sure the CT is positioned between the sensor and the bridge).
Do not leave the CT mounted/installed on a hot wire without being short circuited. It is possible to have both the PAN-14 sensor and the short circuiting wire connected to the CT at the same time. Registering the installed sensor See ‘Panoramic Power deployment guide’.