DUCT HUMIDITY SERIES
Installation & Operation Instructions
GENERAL INFORMATION
The A/RH Duct Series Sensor is a Relative Humidity
transmitter that can be powered with either an AC or
DC supply voltage. The RH Duct transmitter is eld
selectable with a 4-20 mA, 0-5 VDC, or 0-10 VDC output
signal that is equivalent to 0 to 100% RH. This sensor is
designed for use with electronic controllers in commer-
cial heating and cooling building management
systems. All units are shipped from the factory set up
for a 4-20 mA output. The transmitter can also include
an optional temperature sensor for monitoring the
space temperature.
For optimal readings, follow these tips:
The sensor should be mounted in the middle of the duct
where air circulation is well mixed (no strati cation), and
not blocked by obstructions. Strati cation and
obstructions can cause sensing errors. An example is
downstream from a heating or cooling coil.
Duct probe should be placed (3) to (4) duct
segments down from any bend or obstructions and
away from 90° bends.
Mount the sensor on the top or sides of duct work;
mounting on the bottom risks damage due to moisture.
MOUNTING INSTRUCTIONS
The Euro enclosure (-EH) requires a 0.875" (22.23 mm)
hole in the duct, and the Nema 4X enclosure (-4X)
requires a 1.25" (31.75 mm) hole - see FIGURE 1. After
drilling, insert the probe through the hole until the
foam pad is tight to the duct. Drill pilot holes for the
mounting screws. Use the enclosure as a guide, or use
the dimensions listed on the right to measure out.
Now fasten and insert mounting screws through the
mounting holes and tighten until the unit is held rmly
to the duct. Refer to Wiring Instructions (p. 2-4) to
make necessary connections.
Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
FIGURE 1: ENCLOSURE DIMENSIONS
EURO (-EH)
4.30"
(109.22 mm)
2.12"
(53.72 mm)
NEMA (-4X)
2.55"
(64.77 mm)
2.21"
(56.07 mm)
Page 1
Phone: 1-888-967-5224
Website: workaci.com
3.80"
(96.56 mm)
1.90"
(48.28 mm)
7.94"
(201.60 mm)
ø
: 0.75"
(19.05 mm)
1.96"
(49.78 mm)
0.98"
(24.89 mm)
6.96"
(176.66 mm)
ø
: 1.08"
(27.50 mm)
Version 6.0
I0000546

Advertisement

loading

Summary of Contents for aci DUCT HUMIDITY SERIES

  • Page 1 DUCT HUMIDITY SERIES Phone: 1-888-967-5224 Installation & Operation Instructions Website: workaci.com FIGURE 1: ENCLOSURE DIMENSIONS GENERAL INFORMATION The A/RH Duct Series Sensor is a Relative Humidity EURO (-EH) 3.80" transmitter that can be powered with either an AC or (96.56 mm) 4.30"...
  • Page 2: Wiring Instructions

    RELATIVE HUMIDITY WIRING INSTRUCTIONS Open the cover of the enclosure. ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all transmitters. Twisted pair may be used for 2-wire current output transmitters or 3-wire for voltage output. Refer to FIGURE 5 (p. 3) for wiring diagrams.
  • Page 3 FIGURE 4: PRINTED CIRCUIT BOARD FIGURE 5: OUTPUT SIGNALS 2 WIRE CURRENT OUTPUT SIGNAL SQUARE PCB (-4X ENCLOSURE) OPTIONAL TEMP. SENSOR (-) CONNECT TO THE 2 or 3 22 AWG FLYING LEADS PUSH TAB IN AND PULL UP ON THE SENSOR OPTIONAL TEMP.
  • Page 4: Output Signals

    WIRING INSTRUCTIONS (Continued) REVERSE ACTING OUTPUT (Continued) TEMPERATURE WIRING INSTRUCTIONS (Continued) To change the transmitter to reverse acting or back to Note: When using a shielded cable, be sure to connect direct acting, set switch 4 to ON to put the unit in setup only (1) end of the shield to ground at the controller.
  • Page 5: Test Instructions

    7.50 / 0.10 = 75% RH WARRANTY The ACI Duct Series RH sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
  • Page 6: Product Specifications

    PRODUCT SPECIFICATIONS SENSOR SPECIFIC RH Supply Voltage: 4-20 mA: 250 Load: 15 - 40 VDC / 18 - 28 VAC | 500 Load: 18 - 40 VDC / 18 - 28 VAC 0-5 VDC: 12 - 40 VDC / 18 - 28 VAC | 0-10 VDC: 18 - 40 VDC / 18 - 28 VAC (Reverse Polarity Protected) Voltage Output: 8 mA max (0.32 VA) | Current Output: 24 mA max (0.83 VA) RH Supply Current (VA):...
  • Page 7: Troubleshooting

    If the sensor is brand new, leave the sensor powered for at least 30 minutes to stabilize. • If you suspect that the transmitter is not reading within the speci ed tolerance, please contact ACI for further assistance. TEMPERATURE (Optional) PROBLEM SOLUTION(S) •...