Package Contents
•
ACE02 Electronic Swinghandle
with Proximity Reader (qty1)
•
®
M3x25 POZIDRIV
•
®
M3x14 POZIDRIV
•
Rotation Limiter (qty 1)
•
Rotation Limiter (qty1)
•
Pawl Screw (qty 1)
•
Lock Plug Screw (qty 1) (optional)
•
Top Mounting Bracket (qty 1)
•
Bottom Mounting Bracket (qty 1)
•
Operating Instructions (qty 1)
ACE02 Electronic Swinghandle with Proximity Reader
1.
Handle
2.
Prox Reader
3.
Tri-Color Status LED
4.
Lock Plug (optional)
Features
•
Installed 125kHz proximity reader module with Wiegand data
output
•
Remote lock and unlock capability
•
Single or multi-point lock actuation
•
Momentary or continuous lock actuation
•
Tri-color LED (blue/magenta/red) to indicate lock and handle
status
•
DIN lock manual override
•
Accommodates both left and right doors
•
For indoor use only
WARNING: The ACE02 is shipped without a lockplug. This product
must be paired with an approved lock to function properly. Use with an
unapproved lockplug voids the product warranty.
visit
www.panduit.com
for latest version of this document
ACE02 Electronic Swinghandle with PROX Card
Reader Operating Instructions
Mounting Screws (qty 4)
Mounting Screw (qty 1)
Specifications
Actuator Module
Supply Voltage (V
): 12VDC to 24VDC (NOTE: Status LED will blink
SUPPLY
red if the supply voltage is out of range.)
Standby Current:
50mA maximum at 12VDC
Operating Current:
200mA maximum at 12VDC (with no external
mechanical load applied to handle
Stall Current:
1A maximum (at 12VDC, limited to 2 seconds)
Operating Transit Time:
1 second maximum (NOTE: Power must be
present during transit times. If power is
removed while the lock slide is in transit, it will
complete its cycle when power is
restored.)
Electronic Unlock Time:
3 seconds minimum
Open Collector Outputs:
Rated for V
Proximity Reader Module
Supply Voltage (V
):
12VDC to 24VDC
CC
Operating Current:
20mA maximum (no external devices
attached)
Transmit Frequency:
125kHz FSK
DATA Signal Voltage:
5VDC
DATA Pulse Interval Time: 40µs
DATA Signal Delay:
2ms
Mounting and Installation
Please refer to product drawing for mounting and installation details.
NOTE: Use a #1 POZIDRIV
screws. See product drawing for additional details.
Wiring Diagrams
The ACE02 contains two separate functional modules: the actuator
module and proximity reader module. The actuator module controls and
monitors the locking function of the swinghandle. The proximity module
reads the contents of a compatible proximity card and converts it to
Wiegand format.
These two modules operate independently of each other and require
connection to an access control unit (not provided), as illustrated below,
for the entire product to be fully functional.
, maximum load
SUPPLY
®
driver when installing the mounting
Page 1 of 4