wirsbo ProMIX 101 Series Installation And Operating Instructions For The Installer

Radiant heating reset control

Advertisement

A3091000/A3091250
ProMIX™ 101 Radiant
Installation and Operating Instructions

General Description

The ProMIX™ 101 Radiant Reset
Control provides closed loop control of
water in a secondary (radiant) loop of a
heating system, based on outdoor air
temperature and design temperature
settings. It also provides protection
against boiler condensation by monitor-
ing and anticipating the boiler return
water temperature. This control is
designed specifically for radiant heat-
ing but is compatible with other types of
hydronic heat distribution systems
where the use of a weather responsive
control is desired.

Features

Provides outdoor reset control using a 3-way proportional valve in familiar plumbing configu-
rations.
Eliminates the need to analyze and select complex reset ratios – just set the design tempera-
tures.
No guessing about current conditions – the outdoor and radiant loop temperatures are
displayed continuously, along with the secondary loop setpoint.
Efficient use of boiler and circulator operation – only turned on to meet heating demands
Helpful test mode for system setup and diagnostics.
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ProMIX 101 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for wirsbo ProMIX 101 Series

  • Page 1 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Installation and Operating Instructions General Description The ProMIX™ 101 Radiant Reset Control provides closed loop control of water in a secondary (radiant) loop of a heating system, based on outdoor air temperature and design temperature settings.
  • Page 2 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Basic Operation On installation, five design parameters must be The SL sensor provides feedback for the set: control loop. To provide the proper temperature • Outdoor Air Low - the anticipated coldest in the radiant loop, the control positions the outdoor design temperature.
  • Page 3 T86H and the Honeywell T87F) are not (1°F) to provide close room temperature control. compatible with the Wirsbo ProMIX™ 101. The ProMIX™ control can be wired in conjunction with the Wirsbo Zone Control Module, or a single thermostat (DT10).
  • Page 4 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Installation 1. Mount the control on a wall near the modulating valve. 2. The outdoor air sensor should be mounted in a shady location, preferably on the north side of the building under the eaves or a window sill.
  • Page 5 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Power-up/Setup Display Sequence This mode is entered on power-up or any time the Display or Reset Button is pressed while run- ning. On power-up or reset, the settings scroll through automatically. To scroll manually, press the Display button once.
  • Page 6 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Run Mode Display Sequence This mode is entered automatically after the power-up/setup sequence. It continuously loops until a button is pressed or power is lost. Important: Any changes or adjustments made to the temperature or jumper settings are ignored until the test/reset or display button is pressed.
  • Page 7 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Typical Piping Arrangement using the Wirsbo ProMIX™ 101 Controller...
  • Page 8 ProMIX™ 101 Radiant Heating Reset Control Typical wiring using the ProMIX™ 101 Controller and a Wirsbo DT10 Thermostat Typical wiring using the ProMIX™ 101 Controller, Wirsbo Zone Control Module and a Single Pump Relay to provide Domestic Hot Water Priority...
  • Page 9 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Typical wiring using the ProMIX™ 101 Controller with Wirsbo Zone Control Module...
  • Page 10 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Typical wiring using the ProMIX™ Controller, Wirsbo Zone Control Module and Multiple Pump Relay.
  • Page 11 A3091000/A3091250 ProMIX™ 101 Radiant Heating Reset Control Fine Tuning 1. If heating is inadequate at relatively warm below OAL, the SL temperature should be outdoor temperatures (below OAH), at its maximum. SLH should not be increase the minimum loop temperature increased above the maximum tempera- (SLL) by 5°-10°F.
  • Page 12 -51° to 104°C (supplied) Environmental: 1. Operating Temperature 40° to 104°F (4° to 40°C 2. Shipping/Storage Temp. -20° to 140°F (-29° to 60°C) 3. Moisture 95% RH non-condensing 4. Mounting Location Solid wall, away from heat source and direct sun www.wirsbo.com...