IPDU-A Series User Manual
IPDU-A Series User Manual
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the IPDU-A Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Datwyler IPDU-A Series

  • Page 1 IPDU-A Series User Manual IPDU-A Series User Manual...
  • Page 2: Table Of Contents

    IPDU-A Series User Manual Contents . Introduction ........................3 Ⅰ . Main functions ......................3 Ⅱ . Monitoring m ethod ...................... 3 Ⅲ . Applications ......................... 3 Ⅳ . Product sketch ......................4 Ⅴ . Mounting method ......................4 Ⅶ...
  • Page 3: Introduction

    Apply to single phase 100VAC~240VAC up to 63Amps, three phase 200VAC~400VAC up to 32Amps and 100VDC~350VDC power source. The outlet type and quantity can be customized at request. IPDU-A Series is widely applied to the data centers of industries like network communication, telecom, electric power, finance, insurance, aerospace, transportation, information processing, education, medical,...
  • Page 4: Product Sketch

    . Instruction on the RS485 port and RJ45 terminal pin Ⅵ Color Instructions 1.Orange & White 2.Orange 3.Green & White RS485-A 4.Blue RS485-A 5.Blue & White RS485-B 6.Green RS485-B Brown & White 8. Brown . Mounting method Ⅶ IPDU-A Series products can be vertically mounted inside the racks.
  • Page 5: Hardware Introduction

    IPDU-A Series User Manual . Hardware introduction Ⅷ 1. Front panel introduction: Panel Function Description composition Run indicator States: flash frequency is 1 second kWh indicator States: flash frequency depends on the load Alarm indicator Sates: light on if there is an alarm happening...
  • Page 6 IPDU-A Series User Manual 6th screen: the threshold of the temperature (40 ) and humidity (90%) (Figure 6) ℃ Temp Press MENU Press MENU Press MENU 192.168. 00.0 Baud ℃ 1.165 00.0 9600 Addr 0 00% 000000.0KWh Figure 1) (Figure 2)...
  • Page 7: Hardware Settings

    IPDU-A Series User Manual 6th screen: the device IP, address code (from 0 to 4) (Figure 6) 7th screen: L1 threshold of the current (32A) and voltage ( 276VAC) (Figure 7) 8th screen: L2 threshold of the current (32A) and voltage (276VAC) (Figure 8)
  • Page 8: Daisy-Chain Connection

    4. Daisy-chain connection Serial Daisy-chain mode: (Figure 1) 4.1. Setting one IPDU-A Series as Master unit, and the rest as Slave unit. The maximum daisy-chain is 4pcs. Apply to IPDU-A Series 6, refer to figure 1 Ethernet Daisy-chain mode: (Figure 2)...
  • Page 9: Software Introduction

    1. Web browser access User can access, monitor and control the IPDU-A Series by web browser like Internet Explorer, google chrome and etc) by input the correct IP address in the address bar. The pop-up login window is illustrated as...
  • Page 10 IPDU-A Series User Manual A. Device state: Click the Device State(AC or DC), user can check the current, voltage, power and energy consumption of the IPDU-A SERIES as figure 2 Input: From the drop-down list to view the power date of L1,L2 or L3(...
  • Page 11 IPDU-A Series User Manual Device Settings as figure 4 Device Settings Device Name: fill the device name customer wants to define in the blank, then save it. Web server port Work model: Revise master and slave mode, to set slave1,2..(Virtual Value:1-4) Energy Setting:...
  • Page 12 IPDU-A Series User Manual ser can revise the user name and password,the save it (the Max. length of user name and password is 16 digits.) Networking Setting as figure 6 Figure 6 Networking Setting: System IP: 192.168.1.163 (factory default IP Address) Subnet Mask: 255.255.255.0...
  • Page 13 IPDU-A Series User Manual Figure 7 G. E-mail Alarm Settings as figure 8: Set the SMTP including SMTP account, password, SMTP server and port, then save. Click “Testing” and fill in the testing email address. If the test email is received, the setting is effective. See below interface.
  • Page 14: Snmp Access

    Select Activity: user can restart the software or restore to factory default settings. After click “Save”, when IPDU-A series buzzing, the software restart is successful. See below: Note: Press and hold the MENU button when power on to restore to factory settings.
  • Page 15 IPDU-A Series User Manual mHum 1.3.6.1.4.1.30966.10.3.2.11 The humidity value of Master sOneVoltage A 1.3.6.1.4.1.30966.10.3.2.12 Voltage of L1 for slave 1 sOneVoltage B 1.3.6.1.4.1.30966.10.3.2.13 Voltage of L2 for slave 1 sOneVoltage C 1.3.6.1.4.1.30966.10.3.2.14 Voltage of L3 for slave 1 sOneCurrent A 1.3.6.1.4.1.30966.10.3.2.15...
  • Page 16: Telnet Access

    IPDU-A Series User Manual sThreeTem 1.3.6.1.4.1.30966.10.3.2.43 The temperature value of Slave 3 sThreeHum 1.3.6.1.4.1.30966.10.3.2.44 The temperature value of Slave 3 sFourVoltage A 1.3.6.1.4.1.30966.10.3.2.45 Voltage of L1 for slave 4 sFourVoltage B 1.3.6.1.4.1.30966.10.3.2.46 Voltage of L2 for slave 4 sFourVoltage C 1.3.6.1.4.1.30966.10.3.2.47...
  • Page 17: Technical Specification

    IPDU-A Series User Manual Ⅹ Technical Specification Item Parameters Rating voltage 110/220V 50/60HZ Single phase The max current 16A、 32A、63A Rating voltage 380V 50/60HZ Three phase The max current 3×16A、3×32A Rating voltage 240V /336V Direct current The max current 40A / 60A 16A:3×2.5mm...
  • Page 18 IPDU-A Series User Manual Vertical Accuracy:±1﹪ Resolution:0.1kWh Respond time:400ms Display method: LCD; Display direction: Vertical Material ABS+PC Physical Spec Color Black Build-in IPDU-A SERIES 155mm modular Dimension Hot-Swap IPDU-A 180mm SERIES modular Installation Vertical Total load current Input Voltage Monitor Total energy consumption(kWh)...