Standard And Optional Number Of Water Passes; Min Water Volume And Evaporator & Condenser Water Flow Rates; Variable Flow Evaporator - Carrier 19PV550 Installation, Operation And Maintenance Instructions

Hide thumbs Also See for 19PV550:
Table of Contents

Advertisement

6 - APPLICATION DATA

6.5 - Standard and optional number of water passes

19PV
Evaporator
Standard
Evaporator with option 100C
Condenser
Standard
Condenser with option 102C
6.6 - Min water volume and evaporator & condenser water flow rates
These below values are given for standard units. For Evaporator and condenser with option 100C/102C, please refer to the unit
selection program.
19PV
Minimum installation volume (l)
Air conditioning application
Industrial process application
Evaporator water flow rate, (m
Minimum
(1)
Maximum
(3)
Condenser water flow rate, (m
Minimum
(2)
Maximum
(3)
(1) Minimum evaporator flow rate based on a water velocity of 0,5 m/s.
(2) Minimum condenser flow rate based on a water velocity of 0,3 m/s.
(3) Maximum flow rate based on a pressure drop of 120 kPa (units with two evaporator passes and two condenser passes).
This volume is necessary for stable operation.
It is often necessary to add a buffer water tank to the circuit in order
to achieve the required volume. The tank must itself be internally
baffled in order to ensure proper mixing of the liquid (water or
brine). Refer to the examples below.
Connection to a buffer tank
Bad
Bad
18
550
720
2
1
2
1
550
720
1770
2310
3530
4620
/h)
3
34
34
179
235
/h)
3
21
21
245
299
Good
Good
800
900
2
2
2
1
1
1
2
2
2
1
1
1
800
900
2570
2890
5140
5780
34
34
257
281
36
36
346
486

6.7 - Variable flow evaporator

Variable evaporator flow can be used. The controlled flow rate
must be higher than the minimum flow given in the table of
permissible flow rates and must not vary by more than 10% per
minute.
If the flow rate changes more rapidly, the system should contain
a minimum of 6.5 litres of water per kW instead of 3.25 l/kW.
1010
1180
1300
2
2
2
1
1
1
2
2
2
1
1
1
1010
1180
1300
3240
3790
4170
6480
7570
8330
61
61
61
289
286
295
36
36
36
457
454
428
1450
1600
2
2
1
1
2
2
1
1
1450
1600
4640
5130
9290
10250
61
61
295
329
36
36
594
526

Advertisement

Table of Contents
loading

This manual is also suitable for:

19pv72019pv800

Table of Contents