Connection To Wsc 5Xx; Fault Indication - Window Master WSK 501 Installation Instruction

Break glass units for wsc 310 / 320 / 5xx
Table of Contents

Advertisement

Available languages

Available languages

1.2 Connection to WSC 5xx

Smoke detectors and keypads are connected on the break glass unit type
WSK 501/502.
Per 20A section up to 30 break glass units can be connected.
On max 10 of these 30 break glass units smoke detectors type WSA 300 can
be connected - and max 10 smoke detectors per break glass unit.
This gives a total of 100 smoke detectors per 20A section.
Example with WSC 5xx:
3 smoke zones and connected components; 3 break glass units WSK 501/502, 3 smoke detectors WSA 300, 2 resistances
WSA 501 and 4 keypads.
For further information, e.g. configuration please see the installation instruction of WSC 3xx.

1.3 Fault indication

If the smoke panel loses the mains connection (230V), the green LED in the break glass unit (WSK 501 / 502 / 503 / 504)
will flash. The green LED will flash until the system goes into alarm.
With the standard settings it can take up to 10min before the loss of connection is registered.
After reset all the diodes flashes simultaneously. Once the WSK has received its configuration, the diodes are controlled by
the smoke panel. If the WSK loses communication with the smoke panel the yellow and green diode will flashes alternately
(90 sec. after it has not heard from the smoke panel).
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Wsk 502Wsk 503Wsk 504

Table of Contents