1.0 General Description
The D9560CM is a high performance passive infrared intrusion
detector. It is equipped with advanced PIR detection and
supervision circuits and is designed to provide an alarm
condition upon detection of an intruder passing through its area
of coverage.
Employing balanced dual-opposed sensing elements, the
D9560CM passive infrared (PIR) detector makes use of the fact
that all objects give off (transmit) infrared energy, and that the
warmer the object is, the greater the amount of infrared given
off. The D9560CM uses PIR receiver technology designed to
detect the CHANGE in infrared energy caused when a target of
a different temperature from a stable background passes
through its field of coverage.
The coverage pattern consists of sensor zones arranged to form
a circular coverage pattern.
Using Motion Analyzer II circuitry, the detector must first see a
change in infrared energy in one finger followed by a change of
energy in the remaining finger. Therefore, disturbances that
occur in only one finger do not constitute motion and are
ignored. This "catch sensitivity" may be changed in the field by
the installer to provide the degree of sensitivity required by the
installation.
Self-test and supervision circuits provide reliable, uniform
operation in a wide variety of installation environments. The
result is a highly advanced detector offering superior perfor-
mance with freedom from false alarms.
2.0 Specifications
• Input Power: 6.0 to 15.0 VDC; 18 mA nominal @ 12 VDC.
38 mA maximum.
• Standby Power: There is no internal standby battery. Unit is
intended to be connected to DC power sources capable of
supplying standby power in the event primary power fails.
Eighteen mA-H required for each hour of standby time
needed. Four hours (72 mA-H) minimum are required for U. L.
Certificated installations.
• Coverage: 360° by 60 ft. (18.3 m) diameter coverage when
mounted on 8 to 18 ft. (2.4 to 5.5 m) high ceilings. Pattern
consists of 64 zones grouped into 16 barriers, with one
additional zone looking straight down from the unit (sabo-
tage). Each barrier is 30 ft. (9.2 m) long and 4.4 ft. (1.3 m)
wide at 30 ft. (9.2 m). Choice of two optical modules depend-
ing on ceiling height.
Note: For U. L. Listed Requirements, the coverage is 360 ° by
54 ft. (16.5 m) when mounted from 10 to 13 ft. (3.1 to 4.0
m) using the AR8-13 Array and when mounted from 15 to
18 ft. (4.6 to 5.5 m) using the AR13-18 Array.
• Sensitivity: Field selectable for Standard, Intermediate, or
High.
• Alarm Relay: Silent operating Form "C" reed relay. Contacts
rated 3 Watts, 125 mA, 28 VDC maximum for DC resistive
loads, and protected by a 4.7 ohm, 1/2 Watt resistor in the
common "C" leg of the relay. Do not use with capacitive or
inductive loads (such as relays or magnetic locks).
P/N 31367C

Installation Instructions

Passive Infrared Intrusion Detector
• Tamper: Normally Closed (with cover in place) tamper
switch. Contacts rated at 3 Watts, 28 VDC, 125 mA maxi-
mum. .
• Trouble Output: A solid state open collector conducts to
terminal 1 (-) when the detector is in a trouble condition.
Maximum current load is 25 mA.
• Temperature: The storage and operating range is -20° to
+120°F (-29° to +49°C). For U. L. Listed Requirements, the
range is +32 ° to +120 ° F (0 ° to +49 ° C).
• Sonalert™ Connector: Using a Sonalert™ type sounder
(low voltage) will provide an audible tone when the unit is in
alarm. Use of the sounder is intended only as an aid for walk
testing during installation.
• Options: TC6000 Test Cord.
• U. S. Patent Numbers: #4,764,755 and #5,083,106.
D9560CM Installation Instructions
Page 1
D9560CM Ceiling Mount
Sonalert™ is a trademark of Mallory.
TERMINAL
REAR WIRE
STRIP
ENTRANCE
WIRE
TIE-DOWNS (2)
MOUNTING
INTERFACE
SLOTS (4)
PINS
Mounting Base
SOUNDER
TEST LEAD
CUTOUT
NOISE
AR8-13
VOLTAGE
CONFIGURATION
MODULE TABS (2)
SWITCHES
Top View of Enclosure
with Cover Removed
ALARM/TEST LED
INDICATOR (3)
OPTICAL
MODULE
COVER
TAMPER
© 1996 Radionics

Advertisement

loading

Summary of Contents for Radionics D9560CM

  • Page 1: Installation Instructions

    Employing balanced dual-opposed sensing elements, the • Temperature: The storage and operating range is -20° to D9560CM passive infrared (PIR) detector makes use of the fact +120°F (-29° to +49°C). For U. L. Listed Requirements, the range is +32 ° to +120 ° F (0 ° to +49 ° C).
  • Page 2 4.7 ohm, 1/2 Watt resistor in the common “C” Note: The D9560CM base will not completely cover a 4" square leg of the relay. Use terminals 4 & 5 for Normally Closed box. Where aesthetics are important, a 4" octagonal box circuits.
  • Page 3 • High Gain: Recommended for large coverage applications up unit and outside the coverage pattern, then monitor the to 60 ft. (18.3 m) in diameter. The D9560CM is shipped in this background noise for at least three minutes. setting. If the gain jumper is missing, the unit will default to Readings should not deviate from the reference level more High Gain.
  • Page 4 Drawings are not to scale and are intended as pattern identifiers only. © 1996 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved. ™ The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, U.S.A. Radionics ™ Radionics, Inc., 1800 Abbott Street Salinas, CA, 93901, U.S.A.