Download Print this page

Tantalus RT-2200 Instruction Manual page 4

Advertisement

R T - 2 2 0 0
P R O D U C T
Functional
Data rate: 1600/3200 bps
Mechanical interfaces:
• Form S connector for installing into meter socket
• Form S socket for accepting meters equipped with TC-XXXX modules
Data interface: optical
Radio
Type: frequency agile, very narrow-band GFSK
Frequency range: 220-222 MHz
Channels: 200 with 5 kHz spacing
RF power output: +37 dBm (5 watts)
Out of band Spurious: < -65 dBc
Frequency stability: < +/- 1.5 ppm
Standard antenna: internal mounted
Standards
CFR Title 47 Part 15b (unintentional radiators)
CFR Title 47 Part 90, Sub-Part I & T (private land mobile radio services)
CSA C22.2 No. 0-M91 (product safety)
NEMA 4X (environmental)
Power
Power supply: 240 VAC from AC line mains
Power consumption
• Standby: 2 watts
• Transmit: 12 watts (pulsed)
• Outage reporting (optional)
Physical
Size: 13.5" (H) 7.6" (W) 2.8" (D)
Weight: 6 lbs
Storage temperature range: -40° to +85°C
Operating temperature range: -30° to +60°C
Operating humidity range: 5 to 95% non-condensing relative humidity