Do you have a question about the Capital Controls 1041B Series and is the answer not in the manual?
Questions and answers
Subscribe to Our Youtube Channel
Summary of Contents for De Nora Capital Controls 1041B Series
Page 1
Instruction Manual - Series 1041B CAPITAL CONTROLS ® - 1 - 310.6002.0...
Page 2
If you do not understand these instructions, please call De Nora Water Technologies (DNWT), Inc. for clarification before commencing any work at +1 215 997 4000 and ask for a Field Service Manager. De Nora Water Technologies, Inc.
INTRODUCTION General These instructions apply to the Series 1041 and 1041B Automatic Switchover control units. Instruction manuals for other system components and supplemental data are referenced where applicable. The Series 1041 Automatic Switchover model number describes the basic design as follows: MODEL Design/Inspection 01 - Standard...
Automatic switchover is initiated by low pressure (high vacuum) of the on-line source and resulting switch closure. The mechanical limit switch in each motorized ball valve actuator is adjusted to transfer when the valve reaches the closed position. When the controller senses a limit switch closure, it opens the motorized ball valve on the stand-by source.
ALARM CONTACTS SIDE A / SIDE B Manual Auto Close Open Close Open Reset GAS TO DISPENSING SYSTEM OPEN / CLOSED REMOTE STATUS CONTACT VALVE A, VALVE B VALVE A VALVE B SIDE A SIDE B NOTE: Gas supply may be cylinders, ton container or a combination of both. All containers in use must be at the same temperature.
ALARM CONTACTS SIDE A / SIDE B Manual Auto Close Open Close Open Reset OPEN / CLOSED REMOTE STATUS CONTACT VALVE A, VALVE B LIQUID TO VAPORIZER VALVE A VALVE B SIDE A SIDE B NOTE: Liquid supply shall be ton containers. All containers in use must be at the same temperature and elevation. Liquid Service Components: Automatic switchover controller (120 Vac or 240 Vac) Liquid expansion chamber with rupture disc, pressure indicator and pressure switch (chlorine or sulfur dioxide)
INSTALLATION Automatic Switchover Mounting 2.1.1 The Automatic Switchover electronics unit may be wall mounted indoors or in a protected outdoor location using the corrosion-resistant wall mounting feet provided. Choose a location free from vibration. Care should be taken when installing conduit to ensure rainwater, condensation or other contaminants do not enter the enclosure.
START-UP General The manual valves on each of the liquid or gas sources should not be opened until both motorized ball valves are electrically closed and calibrated and all leak tests have been successfully completed. 3.1.1 To electrically close both motorized ball valves proceed as follows: a.
Leak Testing 3.2.1 Air/Nitrogen Pressure Leak Testing The piping system upstream and downstream of the motorized ball valves must be checked pressurizing the piping with 150 psi dry air or nitrogen and applying soapy water to the outside of all pipe joints and fittings.
OPERATION General The Series 1041 & 1041A Automatic Switchover Systems are totally automatic systems with manual override. In the automatic mode, the system dispenses liquid or gas from the on-line source. When the on-line source is depleted, the system will automatically switchover and dispense from the stand-by source. Manual mode switching is done by manually opening and closing the motorized ball valves.
Page 12
g. After Side A’s chemical has been replenished, EMPTY and STAND-BY lights flash indicating Side A source has been replaced. Side Empty Open Closed Stand-by • • Side A source has been replenished. h. The operator depresses RESET push-button completing side A source replenishment and placing side A source in stand-by status for subsequent automatic switchover to Side A source when Side B on-line source becomes depleted.
4.2.2 Manual Override Mode To place the automatic switchover into manual override with Side A source on-line set Side A switch to OPEN, then set the mode switch to MANUAL. Side Empty Open Closed Stand-by • • • Valve A open and Valve B closed. Side B in stand-by. b.
Valve A failure, limit switch open, system halted. Side Empty Open Closed Stand-by Valve B failure, limit switch open, system halted. Side Empty Open Closed Stand-by Re-powering requiring manual reset, check power, fuse. If condition persists, contact De Nora Water Technologies Service Department. 310.6002.0 - 14 -...
SERVICE To perform routine maintenance on system components, De Nora Water Technologies recommends closing the manual line valves at the two independent chemical sources while continuing system operation to evacuate the piping system of chemical. Such routine maintenance might include cleaning filters and vaporizers, and pressure reducing valve repair.
5.5.2 5.5.3 Press OK. Arrow to PROGRAM. 5.5.4 Press OK. 5.5.5 Arrow to RUN. 5.5.6 Press OK. 5.5.7 5.5.8 Fault should clear, RUN light should illuminate. If condition persists, contact De Nora Water Technologies Service Department. 310.6002.0 - 16 -...
TROUBLESHOOTING CHART TROUBLE PROBABLE CAUSE CORRECTIVE ACTION 1. All Control indicators are not a. Power supply failure at a. Check and reset circuit illuminated. source. breaker. b. Blown fuse. b. Replace fuse. 2. One or more control a. Indicator failure. a.
Need help?
Do you have a question about the Capital Controls 1041B Series and is the answer not in the manual?
Questions and answers