Slim Type
HSR-3SL
3-Phase Solid State Relay
INSTRUCTION MANUAL
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
Safety information
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
DANGER indicates an imminently hazardous situation which, if
DANGER
not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation which, if
WARNING
not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, if
CAUTION
not avoided, may result in minor or moderate injury
DANGER
Do not touch or contact the input/output terminals because they may cause electric shock.
WARNING
• Before you use, read safety precautions carefully, and use this product properly.
• Do not touch or contact the input/output terminals because they may cause electric shock.
• If you are concerned about serious accident due to the malfunction of products,
please install the external safety equipment
• To prevent defection or malfunction of this product, supply proper power voltage in
accordance with the rating.
• To prevent electric shock or devise malfunction of this product, do not supply the
power until the wiring is completed.
• Reassemble this product while the power is off. Otherwise, it may cause malfunction
or electric shock.
• If the user use the product with methods other than specified by the manufacturer,
there may be bodily injuries or property damages.
• Due to the danger of electric shock, use this product installed onto a panel while an
electric current is applied.
CAUTION
• Before using the product you have purchased, check to make sure that it is exactly
what you ordered.
• Do not use this product at any place with corrosive
(especially noxious gas or ammonia) or flammable gas.
• Do not use this product at any place with liquid, oil, medical substances, dust, salt or
iron contents.
• Do not use this product at any place with excessive induction trouble, static electricity
or magnetic noise.
• Do not use this product at any place with possible thermal accumulation due to direct
sunlight or heat radiation.
• When the product gets wet, the inspection is essential because there is danger of an
electric leakage or fire.
• Do not connect anything to the unused terminals.
• For DC types, connect wires at the correct position after checking polarity of terminal.
• The rated heat sink must be used otherwise, the product may be destroyed.
• When product is disposed, treat as a industrial waste.
• Since a heat sink corner is sharp, it would lead to a serious injury.
when electricity flows, desktop or heat sink temperature would be high so that it
could lead people to suffer burns.
•This model has epoxy molding for the purpose of safety, reliability and extends of the life.
•When it is out of order, please separate SSR from head sink and only change SSR.
• When applying an electric current, SSR is heated more and more. So, it has more durable
at low heat sink temperature and ambient temperature.
Suffix code
Model
Code
HSR-3SL
   
Input Operating Voltage D
15
Rated load current
25
40
2
Rated load voltage
4
Z
Operation method
(Switching Mode)
R
Information
Slim Type 3-Phase Solid State Relay
4 - 32 V DC
15 A
25 A
40 A
90 - 264 V AC (Low voltage)
90 - 480 V AC (High voltage)
Zero Cross Switching (Standard product)
Random Switching
HANYOUNGNUX CO.,LTD
28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea
HEAD OFFICE
TEL : (82-32)876-4697
FAX : (82-32)876-4696
http://www.hynux.com
PT. HANYOUNG ELECTRONIC INDONESIA
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
INDONESIA
LIPPO CIKARANG CICAU, CIKARANG PUSAT, BEKASI INDONESIA 17550
FACTORY
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
Specification
Low
Model
High
Low
Rated Load
Voltage
High
Low
Peak Voltage
(Non-repetition)
High
Rated load current
Load
Frequency
Low
Surge current
(8.3 ms No repeti t i o n)
High
Leakage current
Output ON voltage dropping
Rated Voltage
Operating Voltage Range
Impedance
Input
Operation Voltage
Reset Voltage
Input Current
Response Time
Insulating Resistance
Dielectric strength
Vibration resistance
Shock resistance
Storage Temperature
Ambient Temperature
Ambient Humidity
Weight
※ Weight included the weight of box
● HSR-3SL 외형 및 패널 가공치수 (단위:mm)
● HSR-3SL 외형 및 패널 가공치수 (단위:mm)
Dimension
- 15A,25A
- 15A,25A
▒ 15 A, 25 A
79.0
20.5
10.0
20.5
10.0
▒ 40 A
- 40A -
- 40A -
95.0
20.5
10.0
20.5
10.0
HSR-3SLD152Z
HSR-3SLD252Z
HSR-3SLD154Z
HSR-3SLD254Z
90 - 264 V AC
90 - 480 V AC
600 V
800 V
15 A
25 A
50/60 ㎐ (Dual usage)
170 A
260 A
170 A
250 A
20 ㎃ max
1.6 V (R.M.S) max
5 - 24 V DC
4 - 32 V DC
Less than 4 ㏀
More than 3 V DC
Less than 1.5 V DC
Constant-current system : 10 ㎃ (±3)
1/2 Cycle + 1 ms max. ("R"type below 1 ms)
500 V DC, 100 ㏁ (Between the input / output and case)
3,000 V AC (For 1 min at 60 ㎐)
10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
1,000 ㎨, X,Y,Z each axis 3 times
-30 ~ 90 ℃
0 ~ 25 ℃ (But without frostiness)
45 ~ 85 % R.H.
Approx. 1,000 g
79.0
4.5
13.8
4.5
13.8
95.0
4.5
13.8
4.5
13.8
MC0601KE140227
HSR-3SLD402Z
HSR-3SLD404Z
1,200 V
40 A
420 A
370 A
Approx. 1,300 g
[Unit : mm]
120
120
146
146

Advertisement

loading

Summary of Contents for HANYOUNG NUX HSR-3SL series

  • Page 1 MC0601KE140227 Slim Type HSR-3SL HANYOUNGNUX CO.,LTD 3-Phase Solid State Relay 28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea HEAD OFFICE TEL : (82-32)876-4697 FAX : (82-32)876-4696 INSTRUCTION MANUAL http://www.hynux.com Thank you for purchasing HANYOUNG product. PT. HANYOUNG ELECTRONIC INDONESIA Please check whether the product is the exactly same as you ordered. JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK INDONESIA Before using the product, please read this instruction manual carefully.
  • Page 2 Equivalent Circuit How to install •Please install SSR in the vertical direction. •Otherwise, production performance may be reduced to less than 50 %. •When installing DIN rail, please install it stably since the product is heavy. Horizontality direction vertical direction Connection Load voltage FUSE...

This manual is also suitable for:

Hsr-3sld152zHsr-3sld252zHsr-3sld154zHsr-3sld402zHsr-3sld254zHsr-3sld404z