PGC, Inc.
INPUT COMMANDS:
(Note: Sign byte is optional on inputs. Set point input commands may only be used in steady state modes)
Command
=OO<CR>
=RC<CR>
=TT<CR>
=DY<CR>
=SD<CR>
=SS<CR>
=PG<CR>
=AS<SP>xx.xx<CR>
=AH<SP>xx.xx<CR>
=AR<SP>xx.xx<CR>
=AD<SP>xxx<CR>
=XS<SP>xx.xx<CR>
=XH<SP>xx.xx<CR>
=XR<SP>xx.xx<CR>
=XD<SP>xxx<CR>
The following command is available in Two Temperature mode only.
=WS<SP>xx.xx<CR>
=WR<SP>xx.xx<CR>
=WH<SP>xx.xx<CR>
=WD<SP>xx.xx<CR>
The following commands are available in a Cascade mode only.
=WL<SP>xx.x<CR>
=WU<SP>xx.x<CR>
=RS<SP>xx.xx<CR>
=RH<SP>xx.xx<CR>
=RR<SP>x.xxx<CR>
=RD<SP>xxx<CR>
The following commands are available in Slow Damper mode only.
=DH<SP>xx.xx<CR>
=DR<SP>x.xxx<CR>
The following commands are available in programmable modes only.
=GO<CR>
=ST<CR>
=LUP<SP>xx<SP>yy<SP>zz<CR>
=PR<SP>xx<SP>aa.a<SP>ww.w<SP>hh:mm:ss<CR>
=IN<CR>
November 2005
Appendix B; SmartPad version 0.503
Function
Toggles current run state (On/Off command)
Instructs Smart Pad to reboot in Rh Cascade control mode
Instructs Smart Pad to reboot in Two Temperature control mode
Instructs Smart Pad to reboot in Dryer control mode
Instructs Smart Pad to reboot in Slow Damper control mode
Instructs Smart Pad to reboot in Steady State set point entry mode
Instructs Smart Pad to reboot in Programmable set point entry mode
Inputs xx.xx as the new Air Set point
Inputs xx.xx as the new Air Half proportional band
Inputs xx.xx as the new Air Reset rate
Inputs xxx as the new Air Derivative constant
Inputs xx.xx as the new auXiliary Set point
Inputs xx.xx as the new auXiliary Half proportional band
Inputs xx.xx as the new auXiliary Reset rate
Inputs xxx as the new auXiliary Derivative constant
Inputs xx.xx as the new Water Set point
Inputs xx.xx as the new Water Reset rate
Inputs xx.xx as the new Water Half proportional band
Inputs xx.xx as the new Water Derivative constant
Inputs xx.x as the new Water Lower limit
Inputs xx.x as the new Water Upper limit
Inputs xx.xx as the new Rh Set point
Inputs xx.xx as the new Rh Half proportional band
Inputs x.xxx as the new Rh Reset rate
Inputs xxx as the new Rh Derivative constant
Inputs xx.xx as the new Damper Half proportional band
Inputs x.xxx as the new Rh Reset rate
Instructs the program to run/resume
Instructs the program to halt
Inputs xx,yy,zz as the new loop (LUP) parameters [start seg; loop from seg;
loop to seg] This command will also reinitialize the loop at the new loop parameters.
Inputs the PRogram data, air (aa.a) and water
(ww.w) set points and time (hh:mm:ss), for the segment indicated (xx).
Instructs the program to reINitialize the loop at the existing loop parameters.
Steady State & Programmable
B-31