Download Print this page
Fire-Lite Alarms SD355CO Installation And Maintenance Instructions
Fire-Lite Alarms SD355CO Installation And Maintenance Instructions

Fire-Lite Alarms SD355CO Installation And Maintenance Instructions

Multi-criteria co and smoke sensor

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
SD355CO Multi-Criteria CO and Smoke Sensor
SPECIFICATIONS
Operating Voltage Range:
Standby Current:
Max. Alarm Current (LED on:)
Operating Humidity Range:
Operating Temperature Range:
Height:
Diameter:
Weight:
*For additional compatible bases, refer to the Base/Sensor Cross Reference
Chart at systemsensor.com.
BEFORE INSTALLING
This sensor must be installed in compliance with the control panel system
installation manual. For local audible indication of a fire and/or carbon
monoxide alarm, it is recommended to install the SD355CO detector into a
B200S series sounder base. If a local audible device is not used, care should
be taken to develop a proper response plan. The installation must meet
the requirements of the Authority Having Jurisdiction (AHJ). Sensors offer
maximum performance when installed in compliance with the National Fire
Protection Association (NFPA); see NFPA 72 and NFPA 720. For a complete
list of compatible bases, refer to the Base/Sensor Cross Reference Chart at
systemsensor.com.
GENERAL DESCRIPTION
Model SD355CO is a plug-in type smoke sensor that is a photoelectronic sens-
ing chamber combined with carbon monoxide (CO), thermal and infra-red (IR)
sensors as well as a carbon monoxide detector both with addressable-analog
communications. The sensors transmit an analog representation of smoke
and/or carbon monoxide density over a communication line to a control panel.
Rotary-decade switches are provided for setting the sensor's address.
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA400Z /RA100Z).
The SD355CO requires compatible addressable communications to function
properly. Connect these sensors to listed-compatible control panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low
air flow applications with smooth ceilings, space sensors 30 feet apart. For
specific information regarding sensor spacing, placement, and special appli-
cations, refer to NFPA 72 or the System Smoke Detector Application Guide,
available from Fire-Lite.
TAMPER-RESISTANCE
Models SD355CO includes a tamper-resistant capability that prevents removal
from the bracket without the use of a tool. Refer to the base manual for details
on making use of this capability.
WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1.
Wire the sensor base (supplied separately) per the wiring diagram, see
Figure 1.
2.
Set the desired address on the sensor address switches, see Figure 2.
3.
Install the sensor into the sensor base. Push the sensor into the base
while turning it clockwise to secure it in place.
FL-400-006
15 to 32 VDC
300µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)
7 mA @ 24 VDC
15% to 90% Relative Humidity, Non-condensing
0°C to 38°C (32°F to 100°F)
2.7˝ (69 mm) installed in B200S Base*
6.875˝ (175 mm) installed in B200S Base*
4.6 oz. (130 g)
4.
After all sensors have been installed, apply power to the control unit and
activate the communication line.
5.
Test the sensor(s) as described in the TESTING section of this manual.
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke or
carbon monoxide. Remove sensors prior to heavy remodeling or construction.
FIGURE 1. WIRING DIAGRAM:
(–) COMM.
(+) COMM.
4
5
1
2
6
3
(+) POWER
(–) POWER
FIGURE 2. ROTARY DECADE ADDRESS SWITCHES:
7
8
6
9
5
10
4
3
13
2
14
1 0
15
TENS
SMOKE SENSOR TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer max-
imum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A.
Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, testing the
sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.
1
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
CAUTION
OPTIONAL REMOTE ANNUNCIATOR
4
1
5
1
2
2
6
3
7
8
6
9
5
11
4
12
3
2
1 0
ONES
4
5
6
3
C0474-02
C0162-00
I56-4129-000

Advertisement

loading

Summary of Contents for Fire-Lite Alarms SD355CO

  • Page 1 (–) COMM. GENERAL DESCRIPTION (+) COMM. Model SD355CO is a plug-in type smoke sensor that is a photoelectronic sens- ing chamber combined with carbon monoxide (CO), thermal and infra-red (IR) sensors as well as a carbon monoxide detector both with addressable-analog communications.
  • Page 2 TOP RING TEST MAGNET C0951-00 Smoke Entry: For SD355CO, smoke entry testing should be performed immediately fol- lowing the magnet test. Magnet test initiates an approximately 10 minute C0952-01 COVER REMOVAL period when the detector’s signal processing software routines are not TABS active.
  • Page 3 10-50 400 ±10ppm 4-15 Also young children and pets may be the first to be affected. SENSOR Per UL standard 2075, the SD355CO has been tested to the sensitivity limits defined in UL standard 2034. COVER REMOVAL TABS ALARM THRESHOLDS ARE AS FOLLOWS:...
  • Page 4 Please refer to insert for the Limitations of Fire Alarm Systems FCC STATEMENT This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.