Download Print this page

Febco 767FR Series Installation Instructions

Anti-siphon pressure vacuum breaker featuring replaceable seats sizes: 1/2"- 2" 15-50mm

Advertisement

Quick Links

I N S T A L L A T I O N I N S T R U C T I O N S
Function: To protect the potable water supply from backflow from a non-
potable source due to a drop in supply.
Protection: Pressure i.e. backsiphonage
Installation Instructions
Requirements:
1. Install 12" (300mm) above highest point of downstream piping.
2. Install bonnet side up and allow for accessibility for testing/service.
3. Install where discharge or spillage is not objectionable.
4. Do not undersize supply or oversize the valve in relation to demand.
5. Do not install where backpressure can occur.
6. Protect from extended freezing.
7. ASSE Standard 1020 requires that the atmospheric vent valve remains
open until the valve bodypressure exceeds 1 lb. Until this pressure is
reached, some amount of spillage will occur at the atmospheric vent. In
order to minimize this leakage on start-up, close the downstream shut-
off valve and open inlet shutoff valve quickly
Recommended Service:
1. Test periodically as required by local jurisdictional authorities.
2. Open test cocks to drain in cold climates if only operated seasonally.
3. Replace rubber goods every 5 years.
Pressure-Temperature:
Working Temp:
33°F -140°F (0.5°C-60°C)
Max. Pressure
150psi (10.3 bar)
Min. Pressure
15psi (103kPa)
Series 767FR/LF767FR
Anti-Siphon Pressure Vacuum Breaker
featuring Replaceable Seats
IMPORTANT: INQUIRE WITH GOVERNING AUTHORITIES
FOR LOCAL INSTALLATION REQUIREMENTS
Limited Warranty: FEBCO warrants each product to be free from defects in material and
workmanship under normal usage for a period of one year from the date of original ship-
ment. In the event of such defects within the warranty period, the Company will, at its
option, replace or recondition the product without charge.
THE WARRANTY SET FORTH HEREIN IS GIVEN EXPRESSLY AND IS THE ONLY
WARRANTY GIVEN BY THE COMPANY WITH RESPECT TO THE PRODUCT.
COMPANY MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED. THE COMPANY
HEREBY SPECIFICALLY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED,
INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE.
The remedy described in the first paragraph of this warranty shall constitute the sole and
exclusive remedy for breach of warranty, and the Company shall not be responsible for any
incidental, special or consequential damages, including without limitation, lost profits or the
cost of repairing or replacing other property which is damaged if this product does not work
properly, other costs resulting from labor charges, delays, vandalism, negligence, fouling
caused by foreign material, damage from adverse water conditions, chemical, or any other
circumstances over which the Company has no control. This warranty shall be invalidated
by any abuse, misuse, misapplication, improper installation or improper maintenance or
alteration of the product.
Some States do not allow limitations on how long an implied warranty lasts, and some
States do not allow the exclusion or limitation of incidental or consequential damages.
Therefore the above limitations may not apply to you. This Limited Warranty gives
you specific legal rights, and you may have other rights that vary from State to State.
You should consult applicable state laws to determine your rights. SO FAR AS IS
CONSISTENT WITH APPLICABLE STATE LAW, ANY IMPLIED WARRANTIES THAT MAY
NOT BE DISCLAIMED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED IN DURATION TO ONE
YEAR FROM THE DATE OF ORIGINAL SHIPMENT.
Sizes:
1
"- 2" (15-50mm)
2
767FR/LF767FR
1
/
",
3
/
"
2
4
(15, 20mm)
RP/IS-F-767FR
767FR/LF767FR
1"-2"
(25-50mm)
THE

Advertisement

loading

Summary of Contents for Febco 767FR Series

  • Page 1 3. Install where discharge or spillage is not objectionable. 4. Do not undersize supply or oversize the valve in relation to demand. Limited Warranty: FEBCO warrants each product to be free from defects in material and 5. Do not install where backpressure can occur.
  • Page 2 7. Remove the check disc holder and guide assembly. Kits consists of: Seat, Seat O-ring and Bonnet O-ring. 8. Disassemble the check disc holder assembly. FEBCO reserves the right to change or modify product design, construc- tion, specifications, or materials without prior notice and without incurring Reassembly any obligation to make such changes and modifications on FEBCO prod- Reassemble in the reverse order utilizing the new parts from the repair kit.

This manual is also suitable for:

Lf767fr series