Page 2
300 Brickstone Square Andover, Massachusetts 01810 All Rights Reserved. Published by the Engineering Department at Andover Controls Corporation. IMPORTANT NOTICE This product is subject to change without notice. This document does not constitute any warranty, express or implied. Andover Controls Corporation reserves the right to alter capabilities, performance, and presentation of this product at any time.
Page 3
Preface The Andover Controls ACX 700 Installation Guide presents instructions for installing the ACX 700 access controller on an Infinet network. It first presents site preparation information and then step-by- step installation instructions. ACX 700 Installation Guide www.PDF-Zoo.com...
Contents Setting Up the ACX 700 Controller and Infinet Site/System Setup Requirements ............2 Controller Dimensions and Weight ..........3 Power Requirements ................3 Cable Limitations................4 Lightning Protection ................4 Building Ground Requirements ............5 Inspecting the Ground..............6 Environmental Requirements ............6 Enclosure Requirements ..............6 Special Wire for Card Reader Inputs..........6 Special Wire for Keypad Inputs ............7...
Page 6
Wiring Outputs ...................40 Wiring Door Outputs ..............40 Connecting Modules to the Expansion Port ........42 Wiring Power Supply for Modules..........45 Powering Up the ACX 700..............47 Reset Button...................48 Connecting the Battery ..............48 Connecting the Andover Controls Service Tool......49 Appendix A—Underwriters Laboratories Requirements Appendix B—Setting the Card Type Jumpers...
Page 7
Provided, in inches (mm) ..............11 2. Dimensions and Location of Mounting Holes in Backplate, in inches (mm)..................12 3. Dimensions of ACX 700 on Backplate with EMX 190s, in inches (mm)...................13 4. Cover Plate of the ACX 700 ..............14 5. Metal Plate and Screw for Power Supply Wire ........16 6.
Page 8
25. Wiring Diagram for DOOR and AUX Form C Outputs if Normally Closed ................42 26. Wiring External and AC Power to Controller and Modules.....46 B-1. Location of Card Type Jumpers.............B-2 B-2. Jumpers for ABA Cards..............B-3 B-3. Jumpers for Wiegand Cards............B-4 viii ACX 700 Installation Guide www.PDF-Zoo.com...
Page 9
Tables 1. Maximum Length Wire for Card Readers ..........7 2. Connecting Jumpers for AC Input Voltages ........16 Andover Controls Corporation www.PDF-Zoo.com...
Setting Up the ACX 700 Controller and Infinet The ACX 700 is a building access controller that can control access to two doors. You can use it to control access through up to four doors by attaching two EMX 190 modules to the ACX 700.
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la class A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada. ACX 700 Installation Guide www.PDF-Zoo.com...
Hardware Installation Controller Dimensions and Weight Each ACX 700 is 19 × 15 × 4.56 in. (483 × 381 × 116) and weighs 17 lbs. (7.73 kg). Power Requirements Caution The ACX 700 should receive power from its own independent, unswitched circuit.
(such as for a card reader) enters or exits a building. Use the following arrestor: Two pair combination gas tube/silicon avalanche ar- restor, Andover Controls # 01-2100-299. 1. You can also use any cables you may already have in place for ACNET or LBUS.
Controls units respond to changes in potential more rapidly than poorly grounded electrical systems, a poorly grounded building tries to reach ground through the Andover Controls system. The surge of current can destroy electronic components on the controller board. Surges of much lower potential than lightning also impact the reliability of Andover Controls equipment.
2. Be sure your Andover Controls cabinet is connected to the ground with a copper conductor that terminates at the distribution panel. Environmental Requirements The ACX 700 operates in rooms with temperatures ranging from 32 to 120°F (0° to 49°C) and with humidity between 10 and 95%, non- condensing.
(1.0 mm 2 ) (0.35 mm 2 ) Sensor Engineering * 500 ft (152 m) 200 ft (60 m) Proximity (12V at ACX 700) 250 ft (76 m) 100 ft (30 m) Proximity (12V at Reader) 500 ft (152 m)
Wiegand or ABA. You may also have additional card readers by attaching one or two EMX 190 modules to the ACX 700. The card reader may have an LED, but does not have to. (UL listed systems must use model 30387 Sensor Engineering card readers.)
• Location of the controller. • Serial number. • Model name and number. • Communications port the Infinet connects to on the ACX 700 controller. Then collect the tags. You will need to know where your controllers are located when you later assign a name to each controller and each input and output.
• Up to two EMX 190 Modules (optional) Mounting Caution You must keep the ACX 700 in the UL listed enclosure provided or insert it in a UL listed enclosure. 1. Before you begin, if you have the enclosed unit, open the front door of the ACX 700 cabinet.
– INFINET SHLD +24VDC CLASS 11 160 m A AUTO/OFF/ON SERVICE EXPANSION OVERRIDE PORT PORT Caution Never drill holes in the ACX 700 cover or boards. A metal shaving could easily short circuit the electronics. ACX 700 Installation Guide www.PDF-Zoo.com...
OVERRIDE PORT PORT Figure 3 shows the dimensions of the ACX 700 with an EMX 190. When you attach modules, they must be enclosed in the same UL listed enclosure as the controller. For additional modules, you require a larger cabinet.
Hardware Installation Figure 3. Dimensions of ACX 700 on Backplate with EMX 190s, in inches (mm) 12.54 (318) R .117 (3) 11.72 (298) USE COPPER INPUT CONDUCTORS ONLY .45 (11) AC INPUT VOLTAGE SEL 115V 230V FROM FROM FROM E4 E3 E4...
Hardware Installation Figure 4. Cover Plate of the ACX 700 USE COPPER INPUT CONDUCTORS ONLY AC INPUT VOLTAGE SELECTION 115V 230V FROM FROM FROM ACX700 3A,250V SLOW BLOW +12VDC -INPUT – POWER 3.6V RET1 1.8AHr LITHIUM RET2 RET3 RET4 KEYPAD 1...
Hardware Installation Figure 4 shows the location of various parts inside the ACX 700, labeled on the cover plate. Note the parts of the controller labeled here. You may want to refer to this figure to locate parts during the installation process.
From From — — To change the voltage from 115 V to 24 V, proceed as follows: 1. Disconnect the jumper end from E5 and move it to E7 so it jumpers E6 to E7. ACX 700 Installation Guide www.PDF-Zoo.com...
AC power. Note Be sure to size the power supply to provide 1.6 A for each ACX 700 controller. If the supply also provides power to motion sensors, card readers, or other auxiliary devices, be sure to size the power supply accordingly.
Wiring the Infinet to the ACX 700. If you purchased the ACX 700 without the cabinet (open class), includ- ed with it is an LED that you can wire to the printed circuit board and mount on the front of the UL listed enclosure.
EXTERNAL LED on the cover plate. 2. Find the LED included with the controller. It should have two wires on the back end. Figure 7 shows the LED with the three nuts and one washer on it. ACX 700 Installation Guide www.PDF-Zoo.com...
-in. (1.5 mm) nut until it is tight against the -in. ----- - ----- - (4.7 mm) frontmost nut and secures it. 8. Tighten the hexagonal nut from the rear until it is tight against the inside of the enclosure. ACX 700 Installation Guide www.PDF-Zoo.com...
Class A FCC limits and to ensure reliable communications. Figure 9 illustrates how to wire the Infinet cable to the removable terminal block connector in the lower left corner of the ACX 700. Figure 9. Infinet Cable Wiring Infinet Connection –...
3. Select the port to wire the cable to—on a 9000, either the RS-485 port just above the three RS-232 ports (COMM2) or the RS-485 port just below the three RS-232 ports (COMM1). Once you use either of ACX 700 Installation Guide www.PDF-Zoo.com...
Page 33
–IN and jumper it to the screw labeled –OUT. 8. Tighten both screws to hold the wire there. 9. Slip the shield in under the middle screw labeled SHLD and tighten the screw to hold it there. ACX 700 Installation Guide www.PDF-Zoo.com...
We recommend you run input wiring in a conduit separate from AC power or output wiring and avoid long wiring runs. The “supervisory” inputs are on the upper left side of the ACX 700, just below the 12VDC UPS power connector. Input wires should enter from the left side.
Page 35
• Keep cabinet free of foreign materials (extra power supplies, relays, and so on). • Be careful when stripping wire not to drop small pieces of wire inside the cabinet. If you violate any of these rules, the controller could malfunction. ACX 700 Installation Guide www.PDF-Zoo.com...
NC Series and Parallel Door Closed SW Closed Door Open SW Open SW Shorted Zero K Wire Cut Infinite This configuration is the best choice; the parallel and series resistors provide a redundant security feature. ACX 700 Installation Guide www.PDF-Zoo.com...
We recommend NO Parallel and NO Series and Parallel types for access control installations. The next sections explain how to wire these types of inputs for door switches and motion detectors. ACX 700 Installation Guide www.PDF-Zoo.com...
This switch can detect either the switch position, or tampering if the switch has an open fault. If the switch is shorted, it appears closed. Figure 13. Wiring Ordinary Switch to DoorSwitch Input Ω 10 K ACX 700 Installation Guide www.PDF-Zoo.com...
(normally open). The switch remains open while the door is in a normal state (closed or not tampered with). If the switch detects the door is open or has been tampered with, it appears closed. ACX 700 Installation Guide www.PDF-Zoo.com...
500 ft of #18 gauge wire (152 m of 1.0 mm 2 ) or 200 ft of #22 gauge wire (60 m of 0.35 mm 2 ). Be sure that when you wire the motion detector, it is correctly set up, as illustrated in the next figure. ACX 700 Installation Guide www.PDF-Zoo.com...
Figure 16. Functioning of Passive Infrared (PIR) Motion Detector Switch Wired to Supervisory Input Normally Open PIR Motion Detector Access Controller No Motion Detected Ω 10 K Normally Open PIR Motion Detector Access Controller Ω 10 K Motion Detected!!! ACX 700 Installation Guide www.PDF-Zoo.com...
Refer to the earlier sections in this manual. In the case of Proximity card readers, you may connect the required ± VDC power supply at the ACX 700 or at the card reader. ACX 700 Installation Guide www.PDF-Zoo.com...
Wiring Wiegand Card Reader (Sensor Engineering) Wire the Sensor Engineering Wiegand card reader to the READER 1 and READER 2 inputs on the lower left side of the ACX 700 as follows: 1. Look at the wire connection on your Wiegand card reader. Notice that you have five connection points: •...
8. Tie back the shield at the card reader end and any wires you do not use. 9. Set the switch on the ACX 700 cover plate (to the right of the wiring) to WIEGAND.
2. Wire the first end of five wires to the appropriate connection point. Figure 20 shows where to connect the various wires on the card reader and the ACX 700. Figure 20. Connections Between Card Reader and Controller ACX 700 Controller...
GND wire, and the end of the shield. Slip all of them under the GND screw on the module; tighten the screw down on them. 10. Set the switch on the ACX 700 cover plate (to the right of the wiring) to WIEGAND. ACX 700 Installation Guide...
2. Wire the first end of each wire to the appropriate connection point on the card reader. Figure 22 shows where to connect the various wires on the card reader and the ACX 700. Figure 22. Connections Between Card Reader and Controller Card Reader...
ACX 700 8. Tie back the shield as well as any wires you do not use. 9. Set the switch on the ACX 700 cover plate (to the right of the wiring) to ABA. If you would like to connect a different card reader, contact your An- dover Controls representative.
The remaining two wires for the Essex Keypad are connected as follows: 1. Connect the wire labeled 5VDC POWER (red) to the appropriate +5V Reader terminal. 2. Connect the wire labeled LED (white) to the appropriate LED Read- er terminal. ACX 700 Installation Guide www.PDF-Zoo.com...
Hardware Installation Wiring Outputs The outputs are on the lower right side of the ACX 700, labeled DOOR1, DOOR2, and AUX. All output wires should enter from the right. Wiring Door Outputs Wire the door and auxiliary outputs as follows: You wire the door outputs like any other Form C output, as follows: 1.
(APHV) for UL listed systems) This configuration shows a normally deenergized lock (when secured) in a fail secure mode. Always be sure to use “panic” hardware that al- lows emergency exit from the secured area. ACX 700 Installation Guide www.PDF-Zoo.com...
The expansion port at the bottom center of the controller board allows you to connect modules to expand the capabilities of the controller. For details on installing the EMX 190, see the EMX 190 Installation Guide provided with the unit. ACX 700 Installation Guide www.PDF-Zoo.com...
Page 53
Hardware Installation Caution If you are wiring an ACX 700 rather than an ACX 710, disregard the Modules Configuration Guide included with the unit and follow the guidelines that follow. You can install multiple expansion modules, along with the EMX 190s, on the ACX 700, as long as you comply with the following: •...
Page 54
ACX 700 controller. Expansion Inputs Allowed Before you add any input modules to the ACX 700, the first 4 inputs you define are the supervisory inputs on the EMX 190s. Of the input mod- ules you can attach, you can always have a maximum of two EMX 160s and one EMX 170s for 17 more expansion inputs;...
Modules Configuration Guide for details regarding how much external power each module you attach requires. You must wire the power supply to ensure that the modules receive power at the same time that the controller does. ACX 700 Installation Guide www.PDF-Zoo.com...
Figure 26 shows how to wire the power supply. You must wire it to the AC power source as shown. Figure 26. Wiring External and AC Power to Controller and Modules 120 VAC Modules 24 VDC – 120 VAC External Power Supply ACX 700 Installation Guide www.PDF-Zoo.com...
Hardware Installation Powering Up the ACX 700 Warning Before powering up the controller, be sure the board is jumpered for the correct input voltage. Before you proceed, be sure the following are correct: 1. Be sure you have jumpered the proper input voltage.
EXTERNAL +24V light goes out, it means no power is being supplied to the expansion port. You may have to replace the fuse. See the Andover Controls Infinet Controller Troubleshooting Guide. Reset Button The RESET button is the red square button to the left of the vertical cen- ter of the board.
The SERVICE PORT on the left side of the bottom of the controller is to connect the Andover Controls Service Tool to an ACX 700. The ser- vice tool accesses all ACX 700s and other Infinet controllers on the same network.
Appendix A Underwriters Laboratories Requirements This appendix explains all requirements for installing the ACX 700 in a UL listed system. ACX 700 Installation Guide www.PDF-Zoo.com...
Page 62
UL requirements listed in this manual is a violation of the listing mark of Underwriters Laboratories. EMX 190 modules are UL listed for use with the ACX 700 in access con- trol systems. These modules are designed for use with the open class ACX 700 for access control.
Appendix B Setting the Card Type Jumpers This appendix shows how to switch required jumpers if you change card types from ABA to Wiegand or from Wiegand to ABA. ACX 700 Installation Guide www.PDF-Zoo.com...
Locating the Card Type Jumpers Located inside the ACX 700 cabinet to the right of the Card Type Switches are two sets of 0 Ω resistor jumpers. These jumpers are cor- rectly set for ABA or Wiegand card types when shipped. If you choose to change the card type from ABA to Wiegand or from Wiegand to ABA you must reset the jumpers.
Set the READER 2 jumpers for ABA cards as follows: 1. Find the jumpers labeled J5, J6, J7, and J8 to the right of the Card Type Switch for READER2 on the ACX 700. 2. Using pliers, remove the jumper from J6.
Set the READER 1 for Wiegand cards as follows: 1. Find the jumpers labeled J1, J2, J3, and J4 to the right of the Card Type Switch for READER 1 on the ACX 700. 2. Leave J1 jumpered. 3. Do not jumper J2.
Page 69
15 cabinet 3 AC voltage dimensions to knockouts 10 door outputs setting 16 length of wire to 40 Andover Controls Service Tool wiring 40 using 49 door switch inputs auxiliary outputs wiring 28 wiring 40 door switches length of wire to 28...
Page 70
inputs normally open card reader supervisory inputs 27 wiring 33, 35, 37 door switch wiring 28 outputs keypad wiring auxiliary 40 wiring 39 wiring door 40 motion sensor wiring rules 25 wiring 30 standard two wire wiring 32 wiring rules 25 parts inside the controller 15 port...
Page 71
normally closed 26 wiring normally open 27 AC power connection 15 recommended types 27 card reader ABA 37 Wiegand 33, 35 connecting Infinet cable 21 temperatures correct wire gauge for ground 6 for operating 6 counter inputs 32 two-wire inputs door outputs 40 wiring 32 door switch inputs 28...