Download Print this page

Fire-Lite Alarms BG-12LR Operating Instructions page 2

Agent release pull station

Advertisement

Wiring Instructions
1) If semi-flush mounted to a single-gang box, proceed to
step #2. Mount the backbox and pull all necessary wiring
through it before wiring the agent release station.
2) Remove the correct amount of wire insulation. The agent
release pull station backplate is molded with a strip gauge
to measure the amount of insulation to be removed.
4) Connect the wiring from the agent release control panel's
Manual Release Circuit, or any previous agent release
initiating device to terminals 1 and 2 on the station's terminal
strip. Connect the next agent release initiating device or
End-of-Line Resistor (ELR) to terminals 1 and 2.
5) Maintain consistent polarity with all connections throughout
the manual release circuit.
WARNING! Do not loop wiring under any terminals. Break
wire run to maintain IDC supervision.
Abort Plate Wiring (BG-12LRA only)
Connect the wiring from the agent release control panel's Abort Circuit to the wire leads D&E of the normally open abort switch.
Connect 24 VDC (+) to a form-c relay, this relay shall be called the Release Relay. Connect the relay's normally closed contact to the
System Normal LED wire lead A. Connect the relays normally open contact to the System Activated LED wire lead B. Connect the 24
VDC (-) to the LED assembly ground wire C.
1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1
Normally Open
1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1
Abort Switch
1 2 3 4 5 6 7 8 9 0 1
1 2 3 4 5 6 7 8 9 0 1
CAUTION
Install the agent release pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire
and Electrical codes and the requirements of the Authority Having Jurisdiction (AHJ). Conduct regular testing of the devices using
appropriate NFPA standards. Fire•Lite is not responsible for devices that have not been properly installed, tested or maintained.
When used for CO
releasing applications, observe proper precautions as stated in NFPA 12. Do not enter the protected space unless
2
physical lockout and other safety procedures are fully completed. Do not use software disable functions in the panel as lockout.
www.PDF-Zoo.com
From agent release
control panel’s
manual release
circuit or previous
agent release
initiating device
*Mount End of line resistor on last unit.
Document 51370    Revision A    ECN 00-190    06/16/2000
To next agent
release initiating
device or ELR if last
device on circuit