EVAX EVX-ZM Installation Manual

Zone splitter intended for use with the evax 25/50/100

Advertisement

Quick Links

Installation Manual: EVAX EVX-ZM Zone Splitter

NOTICE TO THE INSTALLER

This manual provides an overview and the installation instructions for the EVAX EVX-ZM Zone Splitter. All terminals are power limited
and should be wired in accordance with the requirements of NFPA 70 (NEC), NFPA 101 (Life Safety Code) and NFPA 72 (National Fire
Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further
information, refer to the control panel installation instructions.
The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.

Description

The EVX-ZM Zone Splitter Module is intended for use with the EVAX 25/50/100. Its purpose is to enable the output of the EVAX
25/50/100 to be split into multiple circuits for audio power distribution. The modules accept input from the EVAX 25/50/100 speaker
output and utilize output relays to distribute the power to separate circuits. The modules may be cascaded to increase the number of
circuits. The modules provide supervision of the individual circuits for either open or short conditions. Indicator LEDs display active or
fault condition for the individual circuits. Fault condition is reported to the EVAX 25/50/100 via the I2C communication port. The EVX-ZM
may also be used with legacy EVAX 25/50/100 models, but supervision must now employ TB2 Terminals 10-11 as a supervisory input.
Consult factory for connection details.
If Manual control of the circuits is required an EVX-SL8 must be employed. Zones may then be selected manually by switches or
through pull-down inputs. In the event of an alarm condition, module defaults to an All-Call. All-Call feature may only be overridden if
accompanying panel has zone control features

Installation and Operation

Install equipment in a clean, dry environment, avoid installation where equipment could be subjected to vibration. Remove electronic
assemblies from the enclosure prior to any drilling or punching of the enclosure. Where possible, make all cable entries from the rear or
sides. Before making any modifications to the enclosure, be certain that they will not interfere with assemblies or batteries.
In normal standby the EVX-ZM will supervise each speaker zone wire loop. The EVX-ZM will provide 4 Class B (Style Y) or 2 Class A
(Style Z) speaker circuits. This is field selectable via SW1. Upon an open or short condition the Amber LED for that zone will light. This
Fault will report through the EVAX 25/50/100 to the supervising FACP.
If manual Zone selection is employed, select the corresponding EVX-SL8 switch. It's Red LED will light, and the EVX-ZM output relay
activation will be enabled. On activation of the PTT signal from the EVAX 25/50/100, the output relay will connect the zone to the EVAX
25/50/100 speaker output.
In an Alarm condition the EVX-ZM defaults to an All-Call. On activation of the EVAX 25/50/100 V+ Alarm output, all zones are
automatically selected, enabling evac tone and message to play. Modules will have field selectable option for alarm zone activation only
if the FACP has the ability to provide separate pull-down inputs.
Speaker output may be 25 or 70 Vrms. This is field selectable by SW1-2. Output circuits are limited to 50W per zone at 70 Vrms and
40W at 25 Vrms. Total speaker load combined is not to exceed output rating of the EVAX 25/50/100 driving the Zone Module. Upon a
short condition, the shorted zone will open excluding that zone from output and enable the other zones to continue operating. Speaker
circuits must be terminated with a 10K EOLR device. The end of line value is not adjustable or programmable. Speaker circuits will
indicate a Fault if the circuit impedance falls to 5K or increases to 15K Ohms.
Evax by Potter
Branford, CT
Phone: (800) 325-3936
www.evax.com
PAGE 1 OF 3
5403675 Rev A 1/18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVX-ZM and is the answer not in the manual?

Questions and answers

Summary of Contents for EVAX EVX-ZM

  • Page 1: Installation And Operation

    Before making any modifications to the enclosure, be certain that they will not interfere with assemblies or batteries. In normal standby the EVX-ZM will supervise each speaker zone wire loop. The EVX-ZM will provide 4 Class B (Style Y) or 2 Class A (Style Z) speaker circuits.
  • Page 2: Specifications

    INSTALLATION MANUAL: EVAX EVX-ZM ZONE SPLITTER EVX-ZM Connections SW1:Power Selection SW1-1 Select class “A” or “B” Speaker circuit TB1: On for Class “A” Off Class “B” Ter. 1 - 8 Speaker Output 25/70 Vrms Speaker Output SW1-2 Select 25v or 70v speaker voltage 70V - 50W Max speaker load per zone.
  • Page 3: Multiple Units

    INSTALLATION MANUAL: EVAX EVX-ZM ZONE SPLITTER EVX-ZM Zone Splitter Typical Wiring Diagram ZONE 1 Class "B" (Style Y) Wiring ZONE 2 (supervised) (SUPERVISED) ZONE 3 ZONE 4 #18 AWG min. EOLR POWER SPKR (SUPERVISED) SPEAKER CONNECTION CAUTION: EOLR Break wire run to maintain supervision.