Download Print this page

Adel System FLEX Series Instruction Manual page 2

Advertisement

FLEX
power supply
TECHNICAL DATA
Model
Wattage
INPUT DATA
Nominal Input Voltage / Tensione d'ingresso nominale
Input Voltage Range / Campo di funzionamento
2
Inrush Current (Vn and In Load) I
t / Corrente di Inserzione
Frequency /Frequenza di Ingresso
Input Current / Assorbimento
Internal Fuse / Fusibile Interno (non sostituibile)
External Fuse (recommended)/ Fusibile Esterno raccomandato
OUTPUT DATA
Output Voltage Factory Setting ±3%/ Tensione di Uscita – (Vn)
Adjustment range / Campo di regolazione (Vadj)
Start up with capacitive load / Start up con carichi capacitivi
Turn-On delay after applying mains voltage /
Accensione con tensione di rete
Continuous Current at 24 V < 40°C (In) / Corrente Continua
Continuous Current at 24 V < 50°C (In) / Corrente Continua
Continuous Current at 24 V < 60°C (In) / Corrente Continua
Power Boost Current / Corrente di Boost (at 24Vdc 60°C ≥ 3min.)
Current Max Oveload approx. 4Vdc (permanent) /
Corrente di sovraccarico (permanente)
Short circuit current (Icc) / Corrente di corto circuito
Hold-up Time ( min. Vac) 24Vdc / Tempo di arresto
Residual Ripple / Ripple Residuo
Efficiency (50% of In) / Rendimento tipico
Dissipation power load max (W) / Potenza dissipata
CLIMATIC DATA
Ambient Temperature operation / Temperatura Ambiente di Lavoro
De rating Tª > (In) / De rating Tª > (In)
Ambient Temperature Storage / Temperatura max. Magazzino
Humidity at 25 °C / Umidità
GENERAL DATA
Isolation Voltage (IN / OUT) / Tensione di Isolamento (IN / OUT)
Isolation Voltage(IN / PE) / Tensione di Isolamento(IN / TERRA)
Isolation Voltage(OUT / PE) / Tensione di Isolamento(OUT/TERRA)
Protection Class (EN/IEC 60529) / Protezione Classe
Reliability (MTBF IEC 61709) / Affidabilità
Pollution Degree Environment / Grado d'inquinamento ambientale
Connection Terminal Blocks Screw Type / Dimensione morsetti
Protection class (with PE connected) /
Grado di protezione (con cavo di terra collegato)
Dimension (w-h-d)/Dimensioni (l-h-p) mm
Weight / Peso
All specification are subject to change without notice
1 Phase
FLEX6024A
FLEX9024A
FLEX17024A
40–70W
95–120W
120–180W
115 – 230Vac
115 – 230Vac
115 – 230Vac
Input selectable
Input selectable
90 – 135Vac
90 – 135Vac
90 – 264Vac
180 – 264Vac
180 – 264Vac
≤ 19 A ≤ 5msec
≤ 36 A ≤ 5msec
≤ 36 A ≤ 5msec
47 – 63 Hz
47 – 63 Hz
47 – 63 Hz
1.0 – 0.7A
1.8 – 0.9A
2.8 – 1.3A
4A
4A
4A
6A
10A
10A
24Vdc
24Vdc
24Vdc
22 – 27Vdc
22 – 27Vdc
22 – 27Vdc
≤ 50.000µF
≤ 50.000µF
≤ 50.000µF
1.5 sec. (max)
1 sec. (max)
1 sec. (max)
2.0A(115) – 3.0A(230)
5.0A
7.5A
1.5A(115) – 2.5A(230)
4.5A
6.0A
4.0A
5.0A
3.5A
5.0A
7.5A
Imax =
Imax =
Imax =
In 50°C x (1,8 – 2,2)
In 60°C x (1,8 – 2,2)
In 60°C x (1,8 – 2,2)
7.0A
12A
16A
Typ. 20 msec
Typ. 20 msec
Typ. 20 msec
≤ 80 mVpp
≤ 80 mVpp
≤ 80 mVpp
≥ 85%
≥ 89%
≥ 89%
6
11
17
-25 – +70°C
-25 – +70°C
-25 – +70°C
> 50° 2.5% °C
> 60° 2.5% °C
> 60° 2.5% °C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
95% to 25°C
95% to 25°C
95% to 25°C
3000Vac
3000Vac
3000Vac
1605Vac
1605Vac
1605Vac
500Vac
500Vac
500Vac
IP 20
IP 20
IP 20
> 500 000 h
> 500 000 h
> 500 000 h
2
2
2
2,5mm
2,5mm
2,5mm
I
I
I
50x120x50 mm
55x110x105 mm
55x110x105 mm
0.30 Kg approx
0.56 Kg approx
0.56 Kg approx
(Input 115 – 230Vac)
FLEX28024A
FLEX50024A
240–330W
480–600W
2 x Vac
115 – 230Vac
115 – 230Vac
Input selectable
Input selectable
90 – 135Vac
90 – 135Vac
180 – 264Vac
180 – 264Vac
≤ 42 A ≤ 5msec
≤ 80 A ≤ 5msec
47 – 63 Hz
47 – 63 Hz
3.3 – 2.2A
8.5 – 4.2 A
6.3A
10A
16A
16A
24Vdc
24Vdc
22 – 27Vdc
22 – 27Vdc
≤ 50.000µF
≤ 50.000µF
1 sec. (max)
1 sec. (max)
14A
25A
12A
22A
10A
20A
14A
25A
Imax =
Imax =
In 60°C x (1,8 – 2,2)
In 60°C x (1,8 – 2,2)
30A
60A
Typ. 20 msec
Typ. 20 msec
≤ 80 mVpp
≤ 80 mVpp
≥ 89%
≥ 90%
28
54
-25 – +70°C
-25 ÷ +70°C
> 60° 2.5% °C
> 60° 2.5% °C
-40 ÷ +85°C
-40 ÷ +85°C
95% to 25°C
95% to 25°C
3000Vac
3000Vac
1605Vac
1605Vac
500Vac
500Vac
IP 20
IP 20
> 500 000 h
> 500 000 h
2
2
2,5mm
4 mm
I
I
72x115x135 mm
85x120x140mm
0.85 Kg approx
1.2 Kg approx
2 and 3Phase
(Input 230 – 400 – 500Vac)
FLEX9024B
FLEX17024B
FLEX28024B
95–120W
120–180W
240–330W
2 x Vac
230 – 400 – 500Vac
230 – 400 – 500Vac
230 – 400 – 500Vac
Input selectable
Input selectable
Input selectable
187 – 264Vac
187 – 264Vac
187 – 264Vac
330 – 550Vac
330 – 550Vac
330 – 550Vac
≤ 28 A ≤ 5msec
≤ 28 A ≤5 msec
≤ 34 A ≤5 msec
47 – 63 Hz
47 – 63 Hz
47 – 63 Hz
1.0 – 0.5 – 0.4A
1.5 – 0.8 – 0.7 A
2.2 – 1.4 – 1.0A
4A
4A
4A
10A
10A
16 A
24Vdc
24Vdc
24Vdc
22 – 27Vdc
22 – 27Vdc
22 – 27Vdc
≤ 50.000µF
≤ 50.000µF
≤ 50.000µF
1 sec. (max)
1 sec. (max)
1 sec. (max)
5.0A
7.5A
14A
4.5A
6.0A
12A
4.0A
5.0A
10A
5.0A
7.5A
14A
Imax =
Imax =
Imax =
In 60°C x (1,8 – 2,2)
In 60°C x (1,8 – 2,2)
In 60°C x (1,8 – 2,2)
12A
16A
30A
Typ. 20 msec
Typ. 20 msec
Typ. 20 msec
≤ 80 mVpp
≤ 80 mVpp
≤ 80 mVpp
≥ 89%
≥ 89%
≥ 89%
11
17
28
-25 ÷ +70°C
-25 ÷ +70°C
-25 ÷ +70°C
> 60° 2.5% °C
> 60° 2.5% °C
> 60° 2.5% °C
-40 ÷ +85°C
-40 ÷ +85°C
-40 ÷ +85°C
95% to 25°C
95% to 25°C
95% to 25°C
3000Vac
3000Vac
3000Vac
1605Vac
1605Vac
1605Vac
500Vac
500Vac
500Vac
IP 20
IP 20
IP 20
> 500 000 h
> 500 000 h
> 500 000 h
2
2
2
2,5mm
2,5mm
2,5mm
I
I
I
55x110x105 mm
55x110x105 mm
72x115x135 mm
0.56 Kg approx
0.56 Kg approx
0.85 Kg approx
Data List FLEX UNI_R14_pag 2.xls
www.adelsystem.com
FLEX50024B
480–600W
3 x Vac
400 – 500Vac
330 – 550Vac
≤ 35 A ≤ 5 msec
47 – 63 Hz
1,7A max
6.3A
16A
24Vdc
22 – 27Vdc
≤ 50.000µF
1 sec. (max)
25A
22A
20A
25A
Imax =
In 60°C x (1,8 – 2,2)
60A
Typ. 20 msec
≤ 80 mVpp
≥ 91%
54
-25 ÷ +70°C
> 60° 2.5% °C
-40 ÷ +85°C
95% to 25°C
3000Vac
1605Vac
500Vac
IP 20
> 500 000 h
2
4 mm
I
85x120x140mm
1.2 Kg approx