USE AND MAINTENANCE MANUAL TRANSLATION OF THE ORIGINAL INSTRUCTIONS – ENGLISH Codice EAS 15-806 Code Code 933329003 Codigo Kodezahl Código Код Edizione Edition Édition • Quadro automatico • Notstromautomatik Edición 07.2011 • Automatic transfer unit • Quadro automático Ausgabe • Cadre d’intervention automatique • Автоматическое устройство для...
Page 2
· Competent support in the solution of problems; ofthe International Certification Network IQNet, · Information and training in the correct applicatio- awarded the official approval to MOSA after an- nand use of the products to assure the security examination of its operations at the head office ofthe operator and protect the environment;...
Page 3
EAS 15 - 806 REV.1-07/11 INDEX Pag. M 1.01 Copyright M 1.4 CE mark M 1.4.1 Declaration of conformity 1 - General 1.1 – Introduction 1.2 – General warning 1.3 – Symbols in the manual 1.4 – Important tips 1.5 – Cautions 1.6 –...
Page 5
MARCHIO CE CE ZEICHEN CE MARK MARCA CE MARQUE CE REV.0-07/11 Su ciascun esemplare di quadro è apposta la marcatura CE che attesta la conformità alle direttive applicabili ed il soddisfacimento dei requisiti essenziali di sicurezza del prodotto. L’elenco delle direttive applicabili è riportato nella dichiarazione di conformità.
Déclaration de Conformité – Declaration of Conformity – Konformitätserklärung Conformiteitsverklaring – Declaración de Conformidad MOSA dichiara sotto la propria responsabilità che il prodotto : QUADRO DI INTERVENTO AUTOMATICO MOSA déclare, sous sa propre responsabilité, que le produit : MOSA declares, under its own responsibility, that the procuct : MOSA erklärt, daß...
EAS 15 - 806 REV.1-07/11 1 – GENERAL WARNING AND MANUAL USE The Instruction for Use are integral part of the machine and must accompany it for all its useful life until its demolition. For every operation one must always apply to what is prescribed in the Instructions. Follow scrupulously all indication reported in the Instructions Prevent from making use of the machine operators not knowing the prescription based on the Instructions Keep complete and legible Instructions in a place accessible to operators.
EAS 15 - 806 REV.1-07/11 - Before doing any cleaning or maintenance, de-energise and switch off the machine it is connected to. - De-energise and disconnect the equipment in the event of breakdown or malfunction. If any repairs is needed contact an Authorized Retailer only and ask that only original spare parts are used.
Page 9
EAS 15 - 806 REV.1-07/11 1.7 - Cautions levels Below we give the symbols used in the manual to draw the reader’s attention to the different levels of danger in the “Use and Maintenance” of the electric panel. DANGER!! Information or procedures that, unless carried out meticulously, cause death or serious injury. CAUTION!! Information or procedures that, unless carried out meticulously, could cause death or serious injury.
EAS 15 - 806 REV.1-07/11 2 – POWER ON OF THE EAS ELECTRICAL PANEL, USE AND DESCRIPTION 2.1- General information of electrical panel This product permit to control all the functions about a generator • Engine command and protection module for diesel or gasoline generators •...
EAS 15 - 806 REV.1-07/11 2.3- Installation Drilling template (use the two screw anchor provided) Free space of Ø= 6mm aeration reason = 245mm min. 20cm all around the switchboard Internal Battery charger with fuse FCB = F500mA 2.4- Power electrical connections Three-phase systems connections Cables sections Single-phase systems connections...
EAS 15 - 806 REV.1-07/11 2.6- Power ON – clock programming To program the time, follow the procedure descripted below: - Press RESET button (if the electronic card is not in that mode). - Press TEST button for 5 seconds until the display shows “Set”; after that the display shows the first code of the user menu, parameter “U.01 – Automatic test interval time”.
EAS 15 - 806 REV.1-07/11 Setup Description Range Default U.01 Automatic test interval time 1 – 30days 7 days U.02 Test duration 1 – 30 min 10 min U.03 Test start time 00:00 – 23:59 10:00 2.8- Automatic test – Enabled and disabled When the automatic test parameters are set, you have to enable this test;...
EAS 15 - 806 REV.1-07/11 2.10- Display measures Table of the parameters show on display: Push MEAS to scroll the V MAINS: Mains voltage measures V GEN: Generator voltage Generator output current KVA: Generator power output The measure selected is Generator frequency showed by led Vdc:...
EAS 15 - 806 REV.1-07/11 2.13- Function description BOARD IN RESET If it is pressed, it switches on the RESET led and switches off eventual MAN, AUT or TEST leds. If the generator is in running, the load is disconnected and the stop phase begins (without cooling) No function of the generator can be executed.
Page 16
EAS 15 - 806 REV.1-07/11 Then it opens the EV (solenoid valve) output or, if enabled, it closes the P6.02 output for a P3.01 time (electromagnet) Remote start (input on terminal 8.2) It is only active in automatic mode When the start input is closed and the remote stop is open, the start phase begins. When it is reopened, the stop phase starts.
EAS 15 - 806 REV.1-07/11 E01 Remote stop During the generator operation, in AUT mode, if the stop input is closed for a longer time than 0,5sec, the alarm as per table is executed. The display visualizes E01 E02 Emergency stop During the generator operation, if the emergency input is closed for a longer time than 0,3sec, the alarm as per table is executed.
EAS 15 - 806 REV.1-07/11 3.4 - Setting the MAINS voltage - Set the board to - keep on pressing for about 8” the STOP button until the TEST LED switches on - Press the button to increase voltage. – Press the button to decrease voltage - When this setting procedure is over, press button for about 1”...
Page 19
EAS 15 - 806 REV.1-07/11 Group 4 Protections P4.01 Minimum frequency (fixed delay 5sec) 80 – 100 % Maximum frequency (over-speed) 100 – 120% 110% Maximum frequency alarm tripping delay 0-15s. Minimum voltage battery 7-12V Maximum voltage battery 13 – 17V Load maximum current 10 –...