DEOS VAV T4 RT Specification And Installation Instructions

Zone controller for zoning system
Hide thumbs Also See for VAV T4 RT:

Advertisement

Quick Links

Models
VAV T4 RT
(4 TRIACS / pressure independent)
VAV CT 24
(
Thermostat 2x4)
Description
The DEOS Zoning System provides a simple and efficient demand-
based control of pressure independent and pressure dependent
VAV zones with roof top units (RTU) in light commercial
applications (2 to 20 tons). These products provide a local BACnet
MS/TP communication bus to ensure data exchange of all required
information between the zones and the RTUs, which permits
seamless integration with a third party BMS system.
Features
Field configured VAV algorithms, inputs and outputs
Built-in actuator, 70 lb-in
On board differential pressure sensor
Simple air balancing and commissioning via thermostat
Automatically sets operation mode to pressure dependent or
independent based on the presence of air flow
Configurable PI (Proportional-Integral) function
Independent, configurable proportional control band and dead
band per ramp
Selectable internal or external temperature sensor (10KΩ)
Changeover by contact or external temperature sensor
Freeze protection
Operational Features
Backlit LCD with simple icon and text driven menus
Select thermostat's default display
Network service port via on-board mini USB connector
Manual night set back or no occupancy override
Multi-level lockable access menu and setpoint
Selectable Fahrenheit or Celsius scale
3-wire connection to controller and 4 push buttons
Controller Specifications
Description
Torque
Power consumption
Running time through 90º
Power supply
Inputs
On-board differential pressure sensor
Outputs
Real Time Clock
BACnet
Communication connection
Electrical connection
Operating temperature
Storage temperature
Relative Humidity
Weight
The actuator performs an auto-stroke on power up. When changing the actuator adjustment screws, cycle power
to initiate the auto-stroke.
VAV T4 RT-IOM-170712-ESA.docx
VAV Zone Controller for Zoning System
70 in.lb. [8 Nm] at rated voltage
10 VA max
90 seconds
22 to 26 Vac 50/60 Hz
2 Universal inputs (Thermistor 10KΩ Type 3, digital 24Vac/dry contact, or 0-10Vdc)
2 digital inputs
0-1.0" WC
2 analog outputs (0-10 Vdc or 2-10Vdc; selectable)
Up to 4 TRIAC outputs 24 Vac, 500mA max thermal fuse in series with each TRIAC output (on/off,
pulse, or 2 floating outputs)
Real-time clock (RTC) with super capacitor backup (approximately 3 days)
®
BACnet
MS/TP @ 9600, 19200, 38400 or 76800 bps (B-ASC)
24 AWG twisted-shield cable (Belden 9841 or equivalent).
Maximum 50ft (15m) between controller and thermostat
2
0.8 mm
[18 AWG] minimum
0ºC to 50ºC [32ºF to 122ºF]
-30ºC to 50ºC [-22ºF to 122ºF]
5 to 95% non condensing
1.8 kg. [4 lb]
Specification and Installation Instructions
VAV T4 RT / VAV CT 24
Applications
Single duct, cooling only
Single duct cooling and/or heating
Up to 4 stage reheat and/or cool
Up to 4 On/Off heat and/or cool
Up to 4 time proportioned (TPM) heat or reheat
Up to 2 analog (0-10Vdc) reheat and/or cool
Up to 2 floating heat and/or cool
Pressure dependent or pressure independent
With or without auto changeover
Supply/exhaust (requires an additional VAV Controller)
Network Communication
BACnet MS/TP communication port
Select MAC address via DIP switch or via network
Automatic baud rate detection
Automatic device instance configuration
Copy & broadcast configuration via thermostat menu or
via BACnet to other controllers
BACnet scheduler
Firmware upgradeable via BACnet
VAV T4 RT
Page | 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VAV T4 RT and is the answer not in the manual?

Questions and answers

Summary of Contents for DEOS VAV T4 RT

  • Page 1 VAV CT 24 Thermostat 2x4) Description The DEOS Zoning System provides a simple and efficient demand- based control of pressure independent and pressure dependent VAV zones with roof top units (RTU) in light commercial applications (2 to 20 tons). These products provide a local BACnet...
  • Page 2: Mechanical Installation

    IP 30 (EN 60529) Weight 120 g. [0.25 lb] Dimensions A = 2.85” | 73mm B = 4.85” | 123mm C = 1.00” | 24mm D = 2.36” | 60mm E = 3.27” | 83mm www.deos-controls.com VAV T4 RT Page | 2...
  • Page 3: Mounting Instructions

    MAC Address DS.1 = 1 DS.2 = 2 DS.3 = 4 DS.4 = 8 DS.5 = 16 DS.6 = 32 DS.7 = 64 DS.8 = 128 Default Device Instance 153000 153001 153002 153003 153004 … … … … … … … … … … 153126 153127 * Slave addresses available by setting DS.8 to ON www.deos-controls.com VAV T4 RT Page | 3...
  • Page 4 Specification and Installation Instructions Wiring We strongly recommend that all DEOS products be wired to a separate grounded transformer and that transformer shall service only DEOS products. This precaution will prevent interference with, and/or possible damage to incompatible equipment. Data...
  • Page 5 AdV (Advanced) option is selected in the “List” menu Main Menu Network *** You must press the button to save any changes *** *** Pressing the button returns to the previous step without saving *** www.deos-controls.com VAV T4 RT Page | 5...
  • Page 6 “ANrA”) is selected for “Perimtr Reheat Config”. Main Menu Network *** You must press the button to save any changes *** *** Pressing the button returns to the previous step without saving *** www.deos-controls.com VAV T4 RT Page | 6...
  • Page 7 AdV (Advanced) option is selected in the “List” menu Main Menu Network *** You must press the button to save any changes *** *** Pressing the button returns to the previous step without saving *** www.deos-controls.com VAV T4 RT Page | 7...
  • Page 8 (cancel) (0-254) (0-254: max=start + 63) (confirm) Main Menu Network *** You must press the button to save any changes *** *** Pressing the button returns to the previous step without saving *** www.deos-controls.com VAV T4 RT Page | 8...
  • Page 9: Operation Menus

    Press the [*] and [] buttons simultaneously for 5 seconds. The “Enter Password” screen appears. Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the [*] and [] buttons to toggle between the digits. N:\Instructions Production\PDF-1\Actuators\DEOS Password 372 = Temperature Offset Menu...
  • Page 10: Reset To Factory Default Settings

    *** (0 to 9,995) Note: Refer to VAV-Airflow Balance Instructions on DEOS website for further information on airflow balancing function. Reset to Factory Default Settings This will erase all actual configurations and replace them with the factory default settings.
  • Page 11: Operation Mode

    VAV CT 24 thermostat. During the override period the symbol will flash. If the does not flash, the symbol override period is finished or the night set back or no occupancy override has been locked in programming mode. www.deos-controls.com VAV T4 RT Page | 11...
  • Page 12 Recycling at end of life: please return this product to your DEOS local distributor for recycling. If you need to find the nearest DEOS authorized distributor, please consult www.deos-controls.com. www.deos-controls.com...