Mueller Super Centurion 350 Operating Instructions Manual
Mueller Super Centurion 350 Operating Instructions Manual

Mueller Super Centurion 350 Operating Instructions Manual

Fire hydrant
Hide thumbs Also See for Super Centurion 350:

Advertisement

Quick Links

o p E R at i n g i n s t R U c t i o n s M a n U a L
MUELLER
Super
Centurion
350 Fire
Hydrant
!
WARNING:
Before working on, or disassembling the Hydrant (including removing any bolts(s) holding the Hydrant together), shut off gate valve to isolate
Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant - bleed off any pressure, then
remove nozzle cap completely. Open Hydrant main valve completely. A continuous flow of water, no matter how slight, indicates Hydrant is not properly isolated from
the main water supply, and that problem must be corrected before any Hydrant disassembly can proceed. Disassembly of Hydrant with pressurized water acting
against the main valve could result in unexpected ejection of Hydrant parts, debris or high-pressure water stream, which could cause serious bodily injury.
®
®

taBLe of ContentS

www.muellercompany.com
moreinfo@muellercompany.com
PaGe
5-6
7-8
9-10
11
12
13-14
15
16
Reliable Connections
Customer Service Center
Decatur, Illinois
800.423.1323
2
3
4
TM

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Super Centurion 350 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mueller Super Centurion 350

  • Page 1: Table Of Contents

    E R at i n g i n s t R U c t i o n s M a n U a L MUELLER ® Super taBLe of ContentS PaGe Inspection and Maintenance Filling Oil Reservoir Centurion Facing the Hydrant ®...
  • Page 2: Inspection And Maintenance

    MUELLER Super Centurion 350 Fire Hydrant ® Inspection and Maintenance GenerAl This manual applies to all Mueller Remove all Nozzle Caps. Clean and For additional information on Super Centurion 350 Fire Hydrants. lubricate threads. Hydrant anchorage, blocking, and drainage, see AWWA Standard Examine inside of Barrel to make Inspection C600 and Manual M17. certain Drain Valves have completely To ensure their readiness for drained water from Barrel.
  • Page 3: Filling Oil Reservoir

    MUELLER Super Centurion 350 Fire Hydrant ® Filling Oil Reservoir CAUTION: Always fill the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is filled with lubricant under any other circumstances, excess lubricate can overfill the Bonnet and create a pressure lock.
  • Page 4: Facing The Hydrant

    MUELLER Super Centurion 350 Fire Hydrant ® Facing the Hydrant EqUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: A-311 operating wrench and proper bolt/nut wrenches. Loosen Nuts on Traffic Flange Bolts. Turn Operating Nut slightly in the Rotate Upper Barrel section as desired. opening direction to relieve compression between Barrel sections. Tighten Operating Nut, turning in Turn Operating Nut in closing direction Tighten Traffic Flange Bolts to 60 ft-lbs.
  • Page 5: Restoring Service After Traffic Knockover

    MUELLER Super Centurion 350 Fire Hydrant ® Restoring Service after Traffic Knockover WARNING: Before removing any bolt(s) holding the Hydrant together, shut off gate valve to isolate Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant –...
  • Page 6 MUELLER Super Centurion 350 Fire Hydrant ® Restoring Service after Traffic Knockover CAUTION: Always fill the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is filled with lubricant under any other circumstances, excess lubricate can overfill the Bonnet and create a pressure lock.
  • Page 7: Main Valve Replacement: Bonnet Flange

    MUELLER Super Centurion 350 Fire Hydrant ® Main Valve Replacement: Bonnet Flange WARNING: Before removing any bolt(s) holding the Hydrant together, shut off gate valve to isolate Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant –...
  • Page 8 MUELLER Super Centurion 350 Fire Hydrant ® Main Valve Replacement: Bonnet Flange CAUTION: Always fill the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is filled with lubricant under any other circumstances, excess lubricate can overfill the Bonnet and create a pressure lock.
  • Page 9: Main Valve Replacement: Lower Barrel Flange

    MUELLER Super Centurion 350 Fire Hydrant ® Main Valve Replacement: Lower Barrel Flange WARNING: Before removing any bolt(s) holding the Hydrant together, shut off gate valve to isolate Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant –...
  • Page 10 MUELLER Super Centurion 350 Fire Hydrant ® Main Valve Replacement: Lower Bonnet Flange CAUTION: Always fill the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is filled with lubricant under any other circumstances, excess lubricate can overfill the Bonnet and create a pressure lock.
  • Page 11: Replacing Damaged Nozzles

    MUELLER Super Centurion 350 Fire Hydrant ® Replacing Damaged Nozzles EqUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench, A-317 Nozzle Lock Installation Tool, brass hammer. Remove Nozzle Cap. Remove stainless steel Nozzle Lock Place A-316 Nozzle Wrench on Nozzle by driving it out with a pointed tool and with Wrench Forks facing toward hammer. Hydrant Barrel and locked onto Nozzle Drive Lugs. Replace Nozzle Cap and tighten until Cap rests loosely against backside of Wrench. Remove Nozzle...
  • Page 12: Changing The Shoe

    MUELLER Super Centurion 350 Fire Hydrant ® Changing the Shoe EqUIPMENT & TOOLS NEEDED – PPE: Hard hat, safety shoes, safety vest, safety glasses, work gloves. Tools: Wrench, A-316 nozzle wrench. Remove all 6 Shoe Bolt Nuts. Tighten Operating Nut to be sure Main Slip off Hydrant Shoe. Valve is in the fully closed position. Replace Shoe Bolts and Nuts and...
  • Page 13: Adding An Extension

    MUELLER Super Centurion 350 Fire Hydrant ® Adding an Extension WARNING: Before removing any bolt(s) holding the Hydrant together, shut off gate valve to isolate Hydrant from main water source. Loosen (do not remove) one nozzle cap two turns and check for water under pressure inside Hydrant –...
  • Page 14 MUELLER Super Centurion 350 Fire Hydrant ® Adding an Extension CAUTION: Always fill the oil reservoir with the Bonnet installed, the Hydrant in its normal upright position, and the main valve fully closed. If the Hydrant is filled with lubricant under any other circumstances, excess lubricate can overfill the Bonnet and create a pressure lock.
  • Page 15: Parts

    MUELLER Super Centurion 350 Fire Hydrant ® Super Centurion 350 Parts ® a-1 operating nut a-85 Weather Seal a-3 Hold-Down nut o-ring a-84 Hold Down nut a-5 Bonnet o-ring a-6 thrust Bearing a-7 oil filler Plug a-8 Bonnet a-9 Bonnet Bolt & nut...
  • Page 16: Repainting The Hydrant

    International 1.800.423.1323 1.705.719.9965 1.423.490.9555 www.muellercompany.com www.muellercanada.com www.mueller-international.com Reliable Connections moreinfo@muellercompany.com more-info@muellercanada.com international@muellercompany.com Copyright © 2017 Mueller Co., LLC. All Rights Reserved. The trademarks, logos and service marks displayed in this document herein are the property of Mueller Co., LLC, its affiliates or other third parties. Products marked with a section symbol ( § ) are subject to patents or patent applications. For details, visit www.mwppat.com. These products are Form 12860 - Rev 06/17 intended for use in potable water applications. Please contact your Mueller Sales or Customer Service Representative concerning any other application(s).

Table of Contents