Download Print this page
wattstopper FS-PP v2 Installation Instructions Manual
wattstopper FS-PP v2 Installation Instructions Manual

wattstopper FS-PP v2 Installation Instructions Manual

Fixture mount power pack

Advertisement

Quick Links

SPECIFICATIONS

Power .................................................120/277/347VAC, 60Hz
Relay Type ................. Form C with Zero Crossing on N.O. only
Output ........................ 70mA @ +24VDC with relay connected
Load Requirements
@120VAC .................................5.0A (N/O), 3.0A (N/C), 1/6hp
@277VAC .................................4.3A (N/O), 2.5A (N/C), 1/6hp
@347VAC ............................................ 3.4A (N/O), 2.0A (N/C)
Low Voltage Connections ....... RJ45 connection to FS sensors
...................................... Control in, common, +24VDC
Line and Load Connections...........12-18AWG screw terminals
Terminal Torque Rating ....4.428 inch pound-force (0.5Nm)
Operating Temperature ..................... 32° to 131°F (0° to 55°C)
Dimensions .................... 7.5" x 0.87" x 1.0" (190 x 22 x 25mm)
FS-PP v2
Fixture Mount Power Pack

Advertisement

loading

Summary of Contents for wattstopper FS-PP v2

  • Page 1: Specifications

    FS-PP v2 Fixture Mount Power Pack SPECIFICATIONS Power ..........120/277/347VAC, 60Hz Relay Type ....Form C with Zero Crossing on N.O. only Output ......70mA @ +24VDC with relay connected Load Requirements @120VAC .........5.0A (N/O), 3.0A (N/C), 1/6hp @277VAC .........4.3A (N/O), 2.5A (N/C), 1/6hp @347VAC ..........
  • Page 2: Description And Operation

    This cable carries power to the sensor and lighting control signals to the power pack. Each Watt Stopper FS-PP v2 can supply power for up to seven FS series low voltage sensors. FS-CK accessory kits are required to connect multiple sensor or multiple power pack wiring configurations.
  • Page 3 Control 120/277/347 Volts AC Green Operation RJ45 Lighting Plug Neutral Load from FS sensor Fig 2: FS-PP v2 direct wiring to lighting load 0-10VDC Ground Model: Fixture Sensor Power Pack GROUND Violet FS-PP V2 120/277/347VAC, 60Hz @120VAC 5A (N/O) Neutral...
  • Page 4 CONTROL CONFIGURATIONS Standard connection between FS sensor and FS-PP power pack Any 24VDC FS-Sensor FS-PP Fig 5: One sensor controlling one Power Pack FS-PP One FS sensor connected to two FS-PP FS-C3 (3') FS-C4 FS-C1 (10' shown) Any 24VDC FS-PP FS-Sensor Fig 6: One sensor controlling two Power Packs Two FS sensors connected to one FS-PP...
  • Page 5: Troubleshooting

    TROUBLESHOOTING Lights will not turn on: • Sensor LED does not flash: - Is green power pack LED on? If yes, check RJ45 connections at sensor and power pack. If no, check circuit breaker and wiring to power pack. - Check all wire connections. •...
  • Page 6: Ordering Information

    ORDERING INFORMATION Catalog # Description FS-PP v2 Fixture Mount Power Pack: 120/277/347VAC, 60Hz with NO/NC Relay output FS-105 Ceiling tile mount, low voltage PIR occupancy sensor with adjustable time delay and light level FS-205 Fixture mount, low voltage PIR occupancy sensor...