61-1000RK / 61-0140RK
Combustible Gas Detector
Operator's Manual
Part Number: 71-0067RK
Revision: E
Released: 10/26/18
www.rkiinstruments.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 61-1000RK and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for RKI Instruments 61-1000RK

  • Page 1 61-1000RK / 61-0140RK Combustible Gas Detector Operator’s Manual Part Number: 71-0067RK Revision: E Released: 10/26/18 www.rkiinstruments.com...
  • Page 2 Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 61-1000RK/61-0140RK Combustible Gas Detector...
  • Page 3 Product Warranty RKI Instruments, Inc. warranties gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
  • Page 4: Table Of Contents

    Parts List ..............15 61-1000RK/61-0140RK Combustible Gas Detector...
  • Page 5: Overview

    ± 5% of reading or ± 2% LEL (whichever is greater) WARNING: When using the 61-1000RK, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 61-1000RK and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1000RK as described in this manual.
  • Page 6: Description

    Description This section describes the components of the 61-0140RK and 61-1000RK detectors. The 61-1000RK includes the 61-0140RK combustible gas detector and a junction box. A four point terminal strip is provided inside the junction box for detector connections. The 61-0140RK does not include a junction box.
  • Page 7: Installation

    2.70 0.38 3/4 NPT Female 3.65 J-Box 7.50 m ax Spacer, 3X 3/4 x 1/2 NPT Reducing Bushing Combustible Detector Figure 2: Mounting the Combustible Gas Detector 61-1000RK/61-0140RK Combustible Gas Detector • 7...
  • Page 8: Wiring The Combustible Gas Detector

    61-1000RK detector. 10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 8 • 61-1000RK/61-0140RK Combustible Gas Detector...
  • Page 9 Cable Shield Controller White Detector Green Terminals Black J-Box Terminal Strip Black Green Detector W ires White Combustible Detector Figure 3: Wiring the Combustible Gas Detector to a Controller 61-1000RK/61-0140RK Combustible Gas Detector • 9...
  • Page 10: Startup

    If the display reading is 0% LEL, start up is complete. The combustible detector is in normal operation. If the display reading is not 0% LEL, continue with step 3. Perform a zeroing operation at the controller. See the controller operator’s manual for directions. 10 • 61-1000RK/61-0140RK Combustible Gas Detector...
  • Page 11: Maintenance

    4. If the calibration/response difficulties detector requires continue, contact RKI for further calibration once every instruction. three months. Some applications may require a more frequent calibration schedule. 61-1000RK/61-0140RK Combustible Gas Detector • 11...
  • Page 12: Replacing The Combustible Detector

    (see Figure 3). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1000RK detector to verify the connections to the controller are correct.
  • Page 13: Calibration Frequency

    Place the controller into its calibration program or disable external alarms. NOTE: Calibrating the combustible detector may cause alarms. Be sure to put the controller into its calibration program or disable external alarms before continuing. 61-1000RK/61-0140RK Combustible Gas Detector • 13...
  • Page 14: Setting The Zero Reading

    NOTE: If you do not allow the gas reading to decrease below the alarm points, then unwanted alarms may occur. Verify that the controller display reading decreases and stabilizes at 0 %LEL. Store the components of the calibration kit in a safe and convenient place. 14 • 61-1000RK/61-0140RK Combustible Gas Detector...
  • Page 15: Parts List

    Parts List Table 3 lists replacement parts and accessories for the 61-1000RK combustible gas detector. Table 3: Parts List Part Number Description 18-0400RK-01 Junction box with spacers 61-0140RK Replacement combustible gas detector 71-0067RK 61-1000RK Combustible Gas Detector Operator’s Manual (this document)