61-1000RK-05 / 61-0140RK-05 Combustible Gas Detector Operator’s Manual Part Number: 71-0087RK Revision: F Released: 10/26/18 www.rkiinstruments.com...
Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 61-1000RK-05/61-0140RK-05 Combustible Gas Detector...
Page 3
Product Warranty RKI Instruments, Inc. warranties gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 61-1000RK-05, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 61-1000RK-05 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 61-1000RK-05 as described in this manual.
Description This section describes the components of the 61-0140RK-05 and 61-1000RK-05 detectors. The 61-1000RK-05 includes the 61-0140RK-05 combustible gas detector and a junction box. A four point terminal strip is provided inside the junction box for detector connections. The 61-0140RK-05 does not include a junction box.
61-1000RK-05 detector. 10. If using shielded cable, connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically have a ground stud that is a convenient grounding location. 8 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector...
Page 9
Cable S hield Controller W hite Detector Green Terminals Black J-Box Terminal Strip Black Green Detector W ires W hite Combustible Detector Figure 3: Wiring the Combustible Gas Detector to a Controller 61-1000RK-05/61-0140RK-05 Combustible Gas Detector • 9...
If the display reading is 0% LEL, start up is complete. The combustible detector is in normal operation. If the display reading is not 0% LEL, continue with step 3. Perform a zeroing operation at the controller. See the controller operator’s manual for directions. 10 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector...
4. If the calibration/response difficulties detector requires continue, contact RKI for further calibration once every instruction. three months. Some applications may require a more frequent calibration schedule. 61-1000RK-05/61-0140RK-05 Combustible Gas Detector • 11...
(see Figure 3). See the controller operator’s manual and the controller’s detector head specification sheet for the 61-1000RK-05 detector to verify the connections to the controller are correct.
Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 3 to 6 months is adequate for most combustible gas detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months.
NOTE: If you do not allow the gas reading to decrease below the alarm points, then unwanted alarms may occur. Verify that the controller display reading decreases and stabilizes at 0 %LEL. Store the components of the calibration kit in a safe and convenient place. 14 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector...
Parts List Table 3 lists replacement parts and accessories for the 61-1000RK-05 combustible gas detector. Table 3: Parts List Part Number Description 18-0400RK-01 Junction box with spacers 61-0140RK-05 Replacement combustible gas detector 71-0087RK 61-1000RK-05 Combustible Gas Detector Operator’s Manual (this document)