Speci cations:
Input Voltage:
Input Frequency:
Relays:
Max Switched Current:
Radio Frequency:
RF Transmission Output Power (Average):
Dimensions:
Voltage measurement:
Current measurement:
Operating Environment:
Memory:
Wires:
Mounting:
Ordering Information:
Catalog Number
LC - 1R
LC - 2R
LC - 1RD
XA
To comply with RF exposure compliance requirements, for mobile con gurations, a separation distance of at least 20 cm must be
maintained between the antenna of this device and all persons. This device must not be co-located or operating in conjunction with
any other antenna or transmitter.
Class A Digital Devices
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable protection against harmful Interference when the equipment
is operated in a commercial environment. The equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful interference to radio communica-
tions. Operation of the equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his/her own expense.
WARRANTY INFORMATION
Adura Technologies™ warranties its products to be free of defects for a period of ve years. Adura Technologies will, at its option,
repair or replace any product that is defective in materials or manufacture that is returned to ADURA within the warranty period.
This warranty is void if this product has been installed improperly or in an improper environment, overloaded, misused, or altered
in any manner, or not installed in accordance with any labels or instructions. Adura Technologies is not liable for incidental, indirect,
special, or consequential damages, including without limitation, damage to, or loss of use of property, revenue or pro t. This
warranty does not cover the cost of installation, removal or reinstallation.
w w w . a d u r a t e c h . c o m
100 – 277 VAC
60 Hz
Normally open, SPST, zero crossing control
5A Ballast/5A Tungsten (LC-2R = 5A x 2 relays)
2.4 GHz
+12 dBm
7" 5/8 L x 1" 3/16 W x 1" H
2% accuracy full scale
2% accuracy full scale
40 to 140 deg F
Con guration programming
stored in non-volatile memory
24" 600 VAC Rated, 18 AWG solid conductors
Magnets or screws inside of a UL-rated xture
or enclosure rated for the application
Description
Single relay
Two relay
Single relay with 0-10 VDC dimming
Optional external antenna
ADURA TECHNOLOGIES™
TM
San Francisco, CA 94105
Tel: 415.227.0868 • Toll Free 1-888-828-8281
LC Instructions 06.09
INSTALLATION
INSTRUCTION MANUAL
The Light Controller is to be used to control lighting in commercial and industrial buildings.
It provides control of lights (on/o or dimming) by means of commands transmitted and
received via radio frequency.
The Light Controller is intended to be used in a network of devices which communicate
wirelessly, such as wall switches, occupancy sensors, gateways and software management
tools.
The Light Controller is to be mounted inside the enclosure of a light xture or in a separate
UL-rated enclosure. In the case of uorescent lights, the Light Controller is to be installed
inside the ballast cavity of a standard uorescent luminaire.
The Light Controller is intended to be used to control uorescent ballasts, incandescent
lights, LED drivers and HID ballasts.
There are 3 models of the Light Controller:
• LC-1R has one relay and is intended to control one light xture or group of light xtures.
• LC-2R has two relays and is intended to control two levels of light within one xture or
two xtures or two groups of light xtures.
• LC-1RD has one relay and a low voltage dimming output (Class 1 rated) intended to
control standard 0-10 VDC dimming ballasts. Each LC-1RD can provide dimming control to
a maximum of 5 standard 0-10 VDC dimming ballasts.
Installation Materials (Not Supplied)
Wiring connectors. All existing wiring connectors must be replaced with new UL listed
wiring connectors, either wire nuts or captive-type connectors. All wiring connectors must
be correctly sized for the application, the number and the size of the electrical conductors.
Sheet metal screws. As an option, the Light Controller can be secured with 2 #8 sheet metal
screws.
• Disconnect all incoming power before installation or service.
• All installation and maintenance work must be performed by qualified personnel.
• The Light Controllers must be installed in accordance with state, local and national
electrical codes and requirements.
• The Light Controller must be installed within a UL-rated fixture or enclosure rated for
this application.
CAUTION
ADURA TECHNOLOGIES™
TM
San Francisco, CA 94105
Tel: 415.227.0868 • Toll Free 1-888-828-8281
Need help?
Do you have a question about the LC-1R and is the answer not in the manual?
Questions and answers