Page 2
RPT091 Remote Power Transducer QUICK GUIDE The RPT091 is a compact three-phase AC Remote Power Transducer. The unit operates with a remote master (computer or PLC), and with an optional Remote Display Module (RDM091) for local display/setup. The RDM091 is stand-alone or operable with a remote master, and can be panel-mounted or hand-held.
Page 3
DO NOT attempt to open the instrument under any circumstances. 10. Although designed to operate in an electrically noisy environment, the instrument should not be placed near very high electric fields. In the event that the instrument is mounted in a harsh, noisy environment with high potential for electromagnetic impulses from heavy switch gears, motors or lightning, it is recommended to install appropriate protective devices such as...
2 Mechanical Installation Inspect the instrument for physical damage incurred in transit. If the instrument is damaged, inform your local distributor immediately. Figure 2-1 RDM Cut-out Dimensions -------------------------------------------------------------------------------------- Figure 2-2 STEP 1: Insert RDM into cut-out. RDM Panel Mounting STEP 2: Fasten washers and nut on screws...
Page 7
Figure 2-3 Retrofit: Brackets Mounting STEP 1: Insert RDM into cutout. STEP 2: Mount brackets on studs. STEP 3: Fasten brackets; do not tighten nuts. STEP 4: Mount RPT on studs. Figure 2-4 Retrofit: STEP 5: Assemble 4 screws and washers. RPT Mounting STEP 6: Fasten RPT to brackets;...
3 Electrical Installation 3.1 Power Supply The power source can be dedicated-fused, or from a monitored voltage if it is within the transducer power supply range. AC power supply: line to terminal 12; neutral to terminal 10. DC power supply: positive to terminal 12; negative to terminal 10. Figure 3-1 Locations of Terminals: Front View NOTE: Power source connection requires use of the suppression core provided with the instrument.
If copper wiring is used, its thickness should be 2.5 - 4 mm (13 - 11 AWG). 3.3 Ground Connect the chassis ground of the RPT091 to the switchgear earth ground using dedicated wire greater than 2 mm /14 AWG. 3.4 Voltage Inputs...
Page 10
1(A) LINE 2(B) LOAD LINE 3(C) Shorting Switches Currents Vo ltage s Figure 3-2 Three Wire Direct Connection Using 2 CTs (2-element) Wiring Mode = 3dir2 LINE 1(A) LINE 2(B) LOAD LINE 3(C) Shorting Switche s Currents Vo ltage s Figure 3-3 Four Wire WYE Direct Connection using 3 CTs (3-element) Wiring Mode = 4LL3 or 4Ln3...
Page 11
LINE LINE 1(A) 1(A) LINE LINE 2(B) 2(B) LOAD LOAD LINE LINE 3(C) 3(C) Shorting Shorting Switche s Switche s Currents Currents Voltages Voltages Figure 3-4 Four Wire Wye Connection Using 3 PTs,3 CTs (3-element) Wiring Mode = 4LL3 or 4Ln3 1(A) LINE 2(B)
Page 12
LINE 1(A) LINE 2(B) LOAD LINE 3(C) Shorting Switche s Currents Voltages Figure 3-6 Four Wire Wye Connection Using 2 PTs, 3 CTs (2 ½-element) Wiring Mode = 3LL3 or 3Ln3 [Note: Use this configuration only if voltages are balanced] 1(A) LINE 2(B)
LINE 1(A) 240VAC L (B) LINE 2(B) 120VAC 240VAC LOAD 240VAC 208VAC LINE 3(C) 120VAC Power Transformer Sho rting delta connection Switches Currents Voltages 120V 120V VOLTAGES DISPLAYED: 2. L ine to line voltages: 240V; 240V; 2 40V. c9 8-10008 Figure 3-8 Four Wire Delta Direct Connection Using 3 CTs (3 element) Wiring Mode = 4LL3 or 4Ln3 ____________________________________________________________...
Figure 3-10 Status Inputs Connections 3.7 Analog Output The RPT091 provides one optically isolated analog output with an internal power supply and current output options of 0-20 mA, 4-20 mA, 0-1 mA and ±1 mA. Figure 3-11 Analog Output...
ENERGY key * Only the RPT091H provides harmonic measurements. The RDM is the same for both the RPT091 and the RPT091H. In the case of the RPT091, the THD/TDD key is not used. Window 1 Window 2 Window 3...
Page 16
Table 4-1 Displayed Parameters Page Window LED 4 Parameter Digits Unit Common Measurements V1/V1-2 Voltage L1/L12 V/kV V2/V2-3 Voltage L2/L23 V/kV V3/V3-1 Voltage L3/L31 V/kV Current L1 A/kA Current L2 A/kA Current L3 A/kA Total kVA kVA/MVA Total power factor Total kW kW/MW A NEUT Neutral current...
Page 17
Page Window LED 4 Parameter Digits Unit Maximum Demands MAX. DEMAND Maximum ampere demand L1 A/kA Maximum ampere demand L2 A/kA Maximum ampere demand L3 A/kA Max. sliding window kVA demand kVA/MVA Max. sliding window kW demand kW/MW Harmonic Measurements V1/V1-2 Voltage THD L1/L12 V2/V2-3 Voltage THD L2/L23 V3/V3-1 Voltage THD L3...
5 Setup on the RDM Setup can be performed via the RDM or PComTest software. PComTest is supplied on a disk which includes setup instructions The functions of the RDM keys in the setup mode are shown below: Menu Paramete Parameter value To enter a menu/store a value To move between windows...
Analog Output * Reset enable/disable * AEPn Analog Expander * AccS Password enable/disable * * For full setup instructions for these parameters, see the complete RPT091 Installation and Operation Manual. 5.1 Basic Setup Parameters Options / Code Parameter Value Range Description...
Page 21
Options / Code Parameter Value Range Description CT Primary 1 to 50000 The primary current rating of the Current phase current transformer, in A Default = 5 Demand 1,2,5,10, The length of the demand period for Period 15,20, power demand calculations, minutes. 30,60,E E = external synchronization Default = 15 min...
8 bits, no parity = Default 8 bits, even parity * The communications protocol is selected by a short between terminals 13 and 14 on the RPT091 (see Section 6). The protocol may be modified after a cold restart of the RPT091.
Figure 6-2 Terminal Block - Non-ASCII Both the RS-422 and RS-485 standards enable connection of up to 32 instruments on one multi-drop line for a distance of up to 1200 meters. The RPT091 provides two green LED indicators TXD and RXD, which show...
7 Troubleshooting Problem Probable Cause What to do Code other than Self-diagnostic test Note the code and call ‘8’on RDM panel negative result your distributor Power LED on RPT Insufficient power Check voltage level not lit supply on power supply inputs (10,12) Display LED on Faulty cable...
Page 26
Problem Probable Cause What to do Alarm setpoints or Setup parameters that Define these setup analog output affect voltage/current/ parameters (wiring channels disabled power were changed mode, PT ratio, CT primary current) prior to setting up alarm setpoints/analog channels. Status inputs setup 1.
Page 27
Problem Probable Cause What to do PCOMTEST 1. PC COMPORT Change COMPORT program works number is not number (setup of continuously but correct PCOMTEST); TXD LED of PC Check COMPORT 2. PC COMPORT COMPORT does not card setting; setting uncorrected flash Change COMPORT 3.
Appendix: Technical Specifications Input and Output Ratings 3 Galvanically 120 V: INPUT USING PT (up to 120V+20% line-to-line Isolated Voltage voltage) Burden: <0.15 VA inputs 690 V: DIRECT INPUT (up to 690V +15% line-to-line voltage) Burden: <0.5 VA INPUT USING PT - Burden: <0.15 VA 3 Galvanically 1 A:...
Page 29
Environmental Conditions -20°C to +60°C (-4°F to +140°F) Operating temperature -25°C to +80°C (-13°F to +176°F) Storage temperature Humidity 0 to 95% non-condensing Construction Instrument body Case enclosure: Aluminum, anodized Dimension: 186x75x109 mm (7.33 x 2.95 x 4.30 “) Mounting: 35 mm DIN rail or wall mount or 4-inch panel mount Instrument weight 0.94 kg (2.1 lb.)
Page 30
Measurement Specifications Accuracy, % Range Display Resolution (%Rdg) Parameter Full Scale FS Conditions @ range Voltage × 0.25 10% to 120% FS 0 to 999,000 V 1 V @ 1V to 9,999 V 120V For Ln reading ≤0.1% @ 10,000 V to 999,000 V @ 120V and for Starting voltage 1.5% FS...
Page 31
Accuracy, % Range Display Resolution (%Rdg) Parameter Full Scale FS Conditions @ range Neutral (unbalanced) CT PRIMARY CURRENT 2% to 120% FS 0 to 60,000 A 1 A @ 1A to 9,999 A current ≤0.1% @ 10,000 A to 60,000 A Ampere demand same as for current kW demand (block &...
Page 32
Accuracy, % Range Display Resolution (%Rdg) Parameter Full Scale FS Conditions @ range Apparent energy 0 to 999,999 MVAh 1 kVAh @ 1 to 999999 kVAh according to power accuracy 10 kVAh @ 1000 to 9,999 MVAh 100 kVAh @ 10 to 99.999 GVAh 1MVAh @ 100 to 999.9 GVAh PT = external potential transformer ratio CT, CT PRIMARY CURRENT = primary current rating of external current transformer FSU = full scale voltage...