Ac voltage signal conditioner

Advertisement

5
3. Determine the appropriate input signal range, i.e. 400 mV,
4 Volt, 40 Volt or 400 Volt. Also ensure that the frequency of
AC source is within the specified limits.
4. Ensure that if the selected range is different from the default
then change the internal range by using the Setup Software
and select the appropriate range.
5. Connect the signal input to screw terminal, and ensure that
the screws are tight. Failure to do so may cause electrical
shock should the wires become loose and come out of the
screw terminal.
6. To verify that the set up is correct, you may connect a DVM
to the analog output. Once connected, power the signal
conditioner and apply a known voltage from an AC source to
input. Measure and compare with expected values. To
custom scale the analog output proceed to the next step.
7. To view/change the scaling that relates the analog output to
signal input: connect the RS232 output of the signal conditioner to
an available serial port of a computer. The cable and the DB9 or
DB25 connectors are available as an option.
8. Turn on the computer, start Windows 3.0 or higher and run
the Signal Conditioner Configuration Setup Program.
9. Start the configuration program, you need to indicate which
serial port is to be used for serial communication by checking
the appropriate check box on the opening menu.
Note: It is not necessary to know the serial communication
protocol. i.e. baud rate, parity, 7/8 data bit and stop bit; the
program will determine this information automatically.
However, it is good practice to mark the protocols used on the
signal conditioner label if different from default.
10. Once the program starts it will automatically detect the
signal conditioner configuration and will display a window of
available options. To view the signal input click on the
display on/off.
11. To change analog output scaling choose analog output
scaling and enter the desired values.
12. Once the custom scaling is finished, ensure that Send
Configuration is clicked, otherwise the changes will not take effect.
13. The input/output scaling may be fine tuned, while both
communication and analog output are active. In fact you may
make a change to the analog output in the configuration
program, and watch the DVM connected to analog output of
the signal conditioner follow the new settings.
14. You may save or print a particular configuration by
selecting the file menu. It's always a good practice to both
print and save the scaling of each signal conditioner.
6
15. If the program is not able to establish communication then
an error message is displayed. This happens either when the
wrong serial port is specified or when the cable is
disconnected.
16. The procedure to disable Continuous Mode and change
the iDRN to Command Mode is as follows:
Using HyperTerminal, or any serial communication program,
type: Ctrl + S
To change the device to Command Mode, type: ^AE
To change the Bus Format Register, type: *W0814
To reset the device,type: *Z01
Cycle power to the unit.
Modbus Register Definition
Reg. # Read Function
Write Function
1
Input Range
Input Range
2
Input/Output Config.
Input/Output Conf.
3
Decimal Point
Decimal Point
4
Filter Time Constant
Filter Time Constant
5
Reading/Output Scale
Not supported
6
Reading/Output Offset Not supported
7
Comm. Parameters
Comm. Parameters
8
Comm. Bus Format
Comm. Bus Format
9
Comm. Data Format
Comm. Data Format
A
Comm. Device Addr.
Comm. Device Addr.
B
Comm. Recog. Char.
Comm. Recog. Addr.
C
Unit of measure
Not supported
D
Gate Time
Gate Time
E
Debounce Time
Debounce Time
F
Transmit Time
Transmit Time
10
Main Value
Hard Reset
11
Peak Value
Reset Peak
12
Valley Value
Reset Valley
13
Not Supported
L.S. bytes Output Scale
14
Not Supported
M.S. byte Output Scale
15
Not Supported
M.S. bytes Output Offset
16
Not Supported
L.S. byte Output Offset
Note:
1) Main, Peak, Valley value: 4 bytes will send from the unit
a. Highest byte always 00h.
b. 2nd Highest byte: (MSB is sign (1=negative, 0=positive),
next 3 bits are number of decimal points).
c. Low nibble of second byte, and lowest 2 bytes are the
value.
d. The decimal point register has to set to: 1, 2, 3, or 4.
2) Bus Format: Bit 5 1/0 = Modbus/Newport
3) Output Scale/Offset Write:
Due to write single only, two write operation is needed to
write scale/offset, and to make it effective it needs to
follow with Hard Reset command.
4) To configure to Newport protocol, set bit 5 of Bus Format
to low and follow with Hard Reset command.
WARNING: These products are not designed for use in, and should not be used
for, patient-connected applications.
This device is marked with the international caution symbol. It is important to
read the Setup Guide before installing or commissioning this device, as the
guide contains important information relating to safety and EMC.
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its products to
the European New Approach Directives. OMEGA will add the mark to every
appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA
Engineering, Inc. accepts no liability for any errors it contains, and reserves the right
to alter specifications without notice.
PATENT NOTICE: This product is covered by one or more of the following
patents: U.S. Pat. No. Des. 336,895, 5,274,577/ Canada 2052599, 2052600/ Italy
1249456, 1250938/ France Brevet No. 91 12756/ Spain 2039150, 2048066/ UK
Patent No. GB2 249 837, GB2 248 954/ Germany DE 41 34398 C2.
TRADEMARK NOTICE:
®
omega.com
®
,
are trademarks of OMEGA Engineering, Inc.
# of byte
1
WARRANTY/DISCLAIMER
1
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and
1
workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an
additional one (1) month grace period to the normal one (1) year product warranty to cover
1
handling and shipping time. This ensures that OMEGA's customers receive maximum
coverage on each product.
3
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA's
3
Customer Service Department will issue an Authorized Return (AR) number immediately upon
phone or written request. Upon examination by OMEGA, if the unit is found to be defective it will
1
be repaired or replaced at no charge. OMEGA'S WARRANTY does not apply to defects
resulting from any action of the purchaser, including but not limited to mishandling, improper
1
interfacing, operation outside of design limits, improper repair, or unauthorized modification. This
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows
1
evidence of being damaged as a result of excessive corrosion; or current, heat, moisture or
vibration; improper specification; misapplication; misuse or other operating conditions outside of
1
OMEGA's control. Components which wear are not warranted, including but not limited to
contact points, fuses, and triacs.
1
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA
3
neither assumes responsibility for any omissions or errors nor assumes liability for any damages
that result from the use if its products in accordance with information provided by OMEGA, either
1
verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and
free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY
1
KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED
WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A
2
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The
remedies of purchaser set forth herein are exclusive and the total liability of OMEGA with respect
3
to this order, whether based on contract, warranty, negligence, indemnification, strict liability or
otherwise, shall not exceed the purchase price of the component upon which liability is based. In
1
no event shall OMEGA be liable for consequential, incidental or special damages.
1
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a
"Basic Component" under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2)
2
in medical applications or used on humans. Should any Product(s) be used in or with any nuclear
installation or activity, medical application, used on humans, or misused in any way, OMEGA
1
assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and
additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or
2
damage whatsoever arising out of the use of the Product(s) in such a manner.
1
RETURN REQUEST/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department.
BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM OMEGA'S CUSTOMER SERVICE
DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number
should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging
to prevent breakage in transit.
FOR WARRANTY RETURNS, please have
FOR NON-WARRANTY REPAIRS, consult
the following information available BEFORE
OMEGA for current repair charges. Have
contacting OMEGA:
the following information available BEFORE
contacting OMEGA:
1. P.O. number under which the product
was PURCHASED,
1. P.O. number to cover the COST of the
2. Model and serial number of the product
repair,
under warranty, and
2. Model and serial number of product, and
3. Repair instructions and/or specific
3. Repair instructions and/or specific
problems relative to the product.
problems relative to the product.
OMEGA's policy is to make running changes, not model changes, whenever an improvement
is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2004 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or reduced to any
electronic medium or machine-readable form, in whole or in part, without prior written
consent of OMEGA ENGINEERING, INC.
iDRN-ACV
AC Voltage Signal Conditioner
OMEGAnet
®
On-Line Service
www.omega.com
Servicing North America:
USA:
One Omega Drive, P.O. Box 4047
ISO 9001 Certified
Stamford CT 06907-0047
TEL: (203) 359-1660
e-mail: info@omega.com
Canada:
976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928
e-mail: info@omega.ca
For immediate technical or application assistance:
USA and Canada:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
Customer Service: 1-800-622-2378 / 1-800-622-BEST
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
Mexico and
TEL: (001)800-TC-OMEGA
Latin American:
En Espa ñ ol: (001) 203-359-7803
e-mail: espanol@omega.com
Servicing Europe:
Benelux:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
TEL: +31 20 3472121
Toll Free in Benelux: 0800 0993344
e-mail: sales@omegaeng.nl
Czech Republic:
Frystatska 184, 733 01 Karviná
TEL: +420 59 6311899
e-mail: info@omegashop.cz
France:
11, rue Jacques Cartier, 78280 Guyancourt
TEL: +33 1 61 37 29 00 FAX: +33 1 30 57 54 27
Toll Free in France: 0800 466 342
e-mail: sales@omega.fr
Germany/Austria:
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 7056 9398-0
Toll Free in Germany: 0800 639 7678
e-mail: info@omega.de
United Kingdom:
One Omega Drive
ISO 9002 Certified
River Bend Technology Centre
Northbank, Irlam Manchester M44 5BD United Kingdom
TEL: +44 161 777 6611 FAX: +44 161 777 6622
Toll Free in England: 0800 488 488
e-mail: sales@omega.co.uk
M2533/0304
®
®
Internet e-mail
info@omega.com
FAX: (203) 359-7700
FAX: (514) 856-6886
®
®
®
®
FAX: (001) 203-359-7807
FAX: +31 20 6434643
FAX: +420 59 6311114
FAX: +49 7056 9398-29

Advertisement

loading