MOUNTING INSTRUCTION
ZIP Economizer
Installation
Each ZIP Economizer module is designed with a unique form fi t which allows it
to fi t only in one location on the ECON-ZIP-BASE.
Insert the ECON-ZIP-EM module in the center designated slot of the ZIP
Economizer base unit. Illustration located below for location.
Press fi rmly to lock the module in place – you will hear a snap.
Energy Module
Removal of ECON-ZIP-EM
Insert a fl at head screw driver into the latch of the module. Apply light
pressure on the latch away from the base unit. Lift up to remove.
ECON-ZIP-EM
Technical Data
Type
Name
Description
CO2 sensor
Input
CO2 +/-
input
Indoor fan
Output
IF
low speed
enable
Exhaust fan
Output
EF
enable
Auxiliary input
Input
AUX1 ±
Purge contact
input
Auxiliary input
Remote
Input
AUX2 ±
Potentiometer
Input
Electrical Specifi cation
0-10 VDC
Sensor auto-detection
100'000 cycles @ inrush current
of 3A, normal current 1.5A
Impedance for Auto detection
@24 V:
<600 Ω @ 60Hz
<800 Ω @ 50Hz
100'000 cycles @ inrush current
of 3A, normal current 1.5A
Impedance for Auto detection
@ 24 V:
<600 Ω @ 60Hz
<800 Ω @ 50Hz
On/Off, 24 VAC, 50/60 Hz
Current load min. 10mA
2-10 VDC
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZIP Economizer and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Belimo ZIP Economizer

  • Page 1 Installation Removal of ECON-ZIP-EM Each ZIP Economizer module is designed with a unique form fi t which allows it to fi t only in one location on the ECON-ZIP-BASE. Insert the ECON-ZIP-EM module in the center designated slot of the ZIP Economizer base unit.
  • Page 2 Power 2-10Vdc Signal Power Source should be same as ECON-ZIP-BASE Not Supplied by Belimo Remote Potentiometer Sold Separately by Belimo If the RTU has a 2 speed fan (IF wired), then W1 on the ECON-ZIP-BASE needs to be wired as well, since...