Veris HAWKEYE 5002 Installation Instructions Manual

Remote status current sensing 2-point remote status panel

Advertisement

Quick Links

INSTALLATION
!CAUTION !
• This product is not intended for life or safety
applications
• Installing sensors in an energized motor control
center or on any energized conductor can be hazard-
ous.
Severe injury or death can result from electrical shock during
contact with high voltage conductors or related equipment.
Disconnect and lock-out all power sources during installation.
Applications shown are suggested means of installing sensors,
but it is the responsibility of the installer to ensure that the
installation is in compliance with all national and local codes.
Installation should be attempted only by individuals familiar
with codes, standards, and proper safety procedures for high-
voltage installations.

SENSOR INSTALLATION (5800/5900)

The 5004 Remote Status panel accepts any combination of
5800 mini-sensors or 5900 split-core sensors. Sensors may be
located up to 1000 feet away from remote status panel.
Ensure power conductor to be monitored is disconnected and
locked out from the power source!
For model 5800, slide conductor to be monitored through the
sensor hole, and re-connect the conductor.
For model 5900 split-core, simply clamp sensor over the
monitored conductor.
NOTE: 5800/5900 sensors are polarity sensitive. Wire accord-
ing to diagram. Unlike ordinary CTs, these sensors may be left
unshorted, however, they will generate up to 24VDC. Be sure
to label wiring to observe polarity for easy connection to
processor.
Note: Monitoring amperages above or below sensor ratings
require special installation:
a. Low amperage (<1 amp FLA for 5800 mini-sensor &
<2A FLA for 5900 split-core sensor) - to provide adequate
current, wrap conductor through the center hole and
around the sensor body to produce multiple turns and
increase flow. Measured current = Actual Current x
Number of turns.
b. High amperage (>100A FLA for 5800 mini-sensor &
>200A FLA for 5900 split-core sensor) - current flows in
excess of sensor rating require the use of an appropriately
sized external current trans former. Install the external CT
on the conductor and run the CT secondary wire through
the sensor. CAUTION: CTs can contain hazardous volt-
ages. Install CTs in accordance to manufacturers' specifica-
tions and instructions.
SEE REVERSE SIDE FOR REMOTE PANEL

INSTALLATION INFORMATION

Installation Instructions

HAWKEYE 5002
Remote Status Current Sensing
2-point Remote Status Panel
VERIS INDUSTRIES, INC.
10831 S.W. CASCADE BLVD.
PORTLAND, OREGON 97223
(503) 598-4564 FAX (503) 598-4664
http://www.veris.com

SENSOR SPECIFICATIONS

5800 Mini-sensor
Amperage Ratings........................................ 1to 100A continous
Dimensions..........................................2.29"L x 1.85"W x 0.875"H
Sensor Hole Size............................................................ 0.70" Dia.
Sensor wiring........................Up to 1000' from remote, two wire
5900 Split-core Sensor
Amperage Ratings......................................2 to 200A continuous
Dimensions............................................3.63"L x 2.75"W x 0.88"H
Sensor Hole Size........................................................... 1.00" Dia.
Sensor wiring........................Up to 1000' from remote, two wire

REMOTE PANEL SPECIFICATIONS

SENSOR SPECIFICATIONS
Model 5002
Number of points accepted......................................1 to 2 sensors
Supply voltage...............................................................24 VAC/DC
Supply current.............................................................25 mA max.
Trip set-points................................Adjustable to +/- 1% of range
Dimensions ................................. 3.250"L x 2.375"W x 1.080"H
Sealing............................................................................N.E.M.A. 1
Temperature range.......................................................-15 to 85 C
Humidity range.........................................0-95% non-condensing
Output type ....................................Dry Contact, reed relay, N.O.
Output rating..............................................200 mA @ 30 VAC/DC
All Outputs and Adjustments are per point
P/N Z101170
For larger jobs, use model 5004 four point remote
status panel
1-800-354-8556
®
email:sales@veris.com
22 AWG twisted pair
22 AWG twisted pair
50 mA @ 120 VAC

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HAWKEYE 5002 and is the answer not in the manual?

Questions and answers