  • Page 1 Manual PCD2.F2xxx serial interface modules Document 27-649 │ Version ENG02 │ 2018-08-15...
  • Page 2: Table Of Contents

    1.3.4 Restrictions ..................... 1-7 Module variants ....................1-8 1.4.1 RS-422/485 on module - PCD2.F2100 port x.0 ..........1-8 1.4.2 RS-232 on module - PCD2.F2210 Port x.0 (for modem) ........ 1-10 1.4.3 Belimo MP-Bus on module - PCD2.F2810 port x.0 ........1-11 PCD7.F1xxS serial interface modules for port x.1 ..........
  • Page 3: Document Versions

    Saia-Burgess Controls AG Contents Dokumenthistorie Document versions Version Date Updated Comments ENG01 2018-02-08 2018-02-08 Translated from the german version ENG02 2018-08-15 Revised, overview improved, Chapter 2 Brand names and trademarks Saia PCD and Saia PG5 ® ® are registered trademarks of Saia-Burgess Controls AG. Technical changes based on the current technical state of the art Saia-Burgess Controls AG, 2017.
  • Page 4: Pcd2.F2Xxx Serial Interface Modules

    PCD2.F2xxx serial interface modules Modules overview PCD2.F2xxx serial interface modules I/O-Slot Modules overview Serial communications modules with two serial interface ports PCD2.F2100 Port x.0: RS-422 / RS-485 Port x.1: slot for PCD7.F1xxS module PCD2.F2210 Port x.0: RS-232 Port x.1: slot for PCD7.F1xxS module PCD2.F2810...
  • Page 5: Block Diagram

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules General info on the PCD2.F2xxx 1.1.2 Block diagram PCD2.F2xxx I/O Bus Power supply Interface 3.3 V I/O Bus Port x.0 (CPLD) serial line driver/receiver RS-232 or I/O Port RS-422/485 equipped Microcontroller ARM7 UART 1 UART 1 Port x.1 SPI (Slave)
  • Page 6: General Info On The Pcd2.F2Xxx

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules PCD2 slots are available on... General info on the PCD2.F2xxx System properties of the PCD2.F2xxx modules One plug-in socket (orange) for each interface. The first port named Port # 0 is factory-fitted with a fixed serial port depending on your choice. The second interface with the designation Port # 1 allows free loading with a PCD7.F1xxS module of your choice or as a reserve for later assembly.
  • Page 7: Module Description

    Each module has two serial ports, a fixed interface and a second which can be equipped with one of the PCD7.F1xxS modules if required. Serial communications modules with two serial interface ports: PCD2.F2100 Port x.0: RS-422 / RS-485 (equipped) Port x.1: slot for PCD7.F1xxS module PCD2.F2210 Port x.0: RS-232 (equipped)
  • Page 8: Connection Terminals

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules PCD2 slots are available on... 1.3.1 Connection terminals RS-232 RS-422 RS-485 0 PGND 0 PGND PGND Rx-Tx 1 2 /Rx-/Tx PGND 5 PGND 5 PGND 5 /RTS /CTS (SGD) Terminal to port Terminal to port TTY (CL) Belimo MP-Bus 10 pin (2x5)
  • Page 9: Technical Data

    Baud rates supported (bit/s): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Current consumption +5 V-Bus Basis module Port x.1 config. [I in mA] [I in mA] none PCD7.F110S PCD7.F121S PCD2.F2100 PCD7.F130 PCD7.F150S PCD7.F180S none PCD7.F110S PCD7.F121S PCD2.F2210 PCD7.F130 PCD7.F150S PCD7.F180S none PCD7.F110S...
  • Page 10: Restrictions

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module description 1.3.4 Restrictions The PCD2.F2xxx modules for the PCD2 systems enable users to create up to 8 additional serial interfaces. Note: every additional interface uses CPU capacity. The use of these 8 ports depends on the type of communication, the baud rate required and the volume of the data transfer.
  • Page 11: Module Variants

    1.4.1 RS-422/485 on module - PCD2.F2100 port x.0 The PCD2.F2100 module contains two different interface types on port x.0, RS- 422 with RTS/CTS and RS-485 (electrically connected). The line terminator is integrated into the module and can be connected to the module via a switch.
  • Page 12 Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module description RS 485 connection Port x.0 RS-485 PGND Rx-Tx 1 2 /Rx-/Tx 10 pin spring-loaded terminal block PGND 5 (SGD) (Electrically connected RS-485 interface) Peripherie- Terminal RS-485 device PGND x0 PGND RS-485 RX - TX x1 RX - TX RS-485...
  • Page 13: Rs-232 On Module - Pcd2.F2210 Port X.0 (For Modem)

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module description 1.4.2 RS-232 on module - PCD2.F2210 Port x.0 (for modem) The PCD2.F2210 module has a full RS-232 interface on port x.0 an. This port is designed in particular for all modem connections, including the RTS/CTS, DTR/ DSR and DCD.
  • Page 14: Belimo Mp-Bus On Module - Pcd2.F2810 Port X.0

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants 1.4.3 Belimo MP-Bus on module - PCD2.F2810 port x.0 The PCD2.F2810 module has a full Belimo MP-Bus interface on port x.0 an. An MP-Bus with up to 8 drives and sensors can therefore be connected to port x.0. Belimo connection Port x.0 Belimo MP-Bus...
  • Page 15: Pcd7.F1Xxs Serial Interface Modules For Port X.1

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants PCD7.F1xxS serial interface modules for port x.1 1.5.1 PCD7.F1xxS modules overview PCD7.F1xxS serial interface modules will be used, among others, for the insertion of port x.1 of the PCD2.F2xxx modules. A second interface can be mounted on each CD2.F2xxx module depending on the purpose of the application.
  • Page 16: Rs-485/Rs-422 - Pcd7.F110S Serial Interface Module

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants 1.5.2 RS-485/RS-422 - PCD7.F110S serial interface module The terminating connectors can be linked using slide switches (CLOSED) or isolated (OPEN). PCD7.F110S RS-485 terminator Slider Open not terminated (factory setting) Closed terminated Slider RS-422 connection Port x.1...
  • Page 17: Rs-232 Up To 115 Kbit/S, Suitable For Modem Connection Pcd7.F121S Serial Interface Module

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants Peripherie- Terminal RS-485 device PGND x0 PGND RS-485 RX - TX x1 RX - TX RS-485 /RX - /TX x2 /RX - /TX More details are available in the manual 26-740 “Installation components for RS- 485 networks”.
  • Page 18: Rs-485 Galv. Isolation - Pcd7.F150S Serial Interface Module

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants 1.5.4 RS-485 galv. isolation - PCD7.F150S serial interface module Electrical isolation is achieved using three optical couplers and a DC/DC converter. The data signals are protected against excess voltages by a suppressor diode (10 V).
  • Page 19: Belimo Mp-Bus Pcd7.F180S - Serial Interface Module

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants When using this module, the permitted ambient temperature for the control unit is reduced by 5°C. More details are available in the manual 26-740 “Installation components for RS-485 networks”. 1.5.5 Belimo MP-Bus PCD7.F180S - serial interface module Up to a maximum of 8 actuating drives and sensors can be connected.
  • Page 20: Pcd7.Fxxx - Overview Of Older Interface Modules (No Longer Available)

    Saia-Burgess Controls AG PCD2.F2xxx serial interface modules Module variants 1.5.6 PCD7.Fxxx - Overview of older interface modules (no longer available) The older serial interface modules PCD7.F1xx (without «S» at the end) are no longer available. Except PCD7.F130 current loop 20 mA For completeness they are still listed here.
  • Page 21: Pcd2 Slots Are Available On

    Saia-Burgess Controls AG PCD2 slots are available on... PCD1.M22xx-C15 PCD2 slots are available on... This chapter indicates which PCD controllers can be used with which PCD2.F2xxx modules. PCD1.M22xx-C15 A maximum of two PCD2.F2xxx modules can be used on the two slots. The slots can be accessed with the following port addresses via communication FBoxes: Slot 0 with the PCD2.F2xxx module...
  • Page 22: Pcd1.M21Xx

    Saia-Burgess Controls AG PCD2 slots are available on... PCD1.M21xx PCD1.M21xx Slots IO0 and IO1 on the PCD1.M2_ can also be equipped with the PCD2.F2xxx interface modules. The slots can be accessed with the following port addresses via communication FBoxes (or AWL commands): PCD1.M2120 /PCD1.M2160 PCD1.M2110-Room Module...
  • Page 23: Pcd2.M4Xxx

    P C D 2 . F 2 1 0 0 P C D 2 . F 2 1 0 0 P C D 2 . F 2 1 0 0 P C D 2 . F 2 1 0 0 PCD2.F2100 PCD2.F2100 PCD7.F1xxS PCD7.F1xxS...
  • Page 24: Pcd2.M5Xxx

    Saia-Burgess Controls AG PCD2 slots are available on... PCD2.M5xxx PCD2.M5xxx The PCD2.F2xxx modules are intended for inclusion in the I/O slot 0...3 on a PCD2.Mxxxx. As shown in the diagram, the I/O slots are labelled as follows: Module port Module terminal Module slot address block...
  • Page 25 Saia-Burgess Controls AG Appendix Icons Appendix Icons This symbol indicates that additional information on this topic exists in this manual, a different manual or technical documentation. There are no direct links to these documents. This symbol indicates instructions that require strict compliance. Manual PCD2.F2xxx serial interface modules ...
  • Page 26 Saia-Burgess Controls AG Appendix Contact details Contact details Saia-Burgess Controls AG Bahnhofstrasse 18 3280 Murten, Switzerland Head office telephone .... +41 26 580 30 00 SBC Support telephone ..+41 26 580 31 00 Fax .......... +41 26 580 34 99 Email support: ......

Table of Contents