Littelfuse PGR-6100 Manual

Ground-fault & insulation monitor

Advertisement

Quick Links

Tel: +1-800-832-3873
E-mail: techline@littelfuse.com
www.littelfuse.com/PGR-6100
PGR-6100 MANUAL
GROUND-FAULT & INSULATION MONITOR
Revision 2-C-050818
Copyright © 2018 Littelfuse
All rights reserved.
Document Number: PM-1100-EN

Advertisement

Table of Contents
loading

Summary of Contents for Littelfuse PGR-6100

  • Page 1 Tel: +1-800-832-3873 E-mail: techline@littelfuse.com www.littelfuse.com/PGR-6100 PGR-6100 MANUAL GROUND-FAULT & INSULATION MONITOR Revision 2-C-050818 Copyright © 2018 Littelfuse All rights reserved. Document Number: PM-1100-EN...
  • Page 2 Page i PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 This page intentionally left blank.
  • Page 3: Table Of Contents

    DISCLAIMER 2.4.2 >∆I ............2 Specifications are subject to change without notice. 2.4.3 CT ............2 Littelfuse, Inc. is not liable for contingent or consequential damages or for expenses sustained as result of incorrect 2.4.4 Active ............2 application, incorrect adjustment, or malfunction.
  • Page 4 Page iii PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 This page intentionally left blank.
  • Page 5: General

    < 50 ms to 1.0 s. Coordination requires the same trip level for all ground-fault devices in a system and the trip The PGR-6100 can be directly connected to a supply up to time to progressively increase upstream. The amount of 1.3 kV.
  • Page 6: Test

    6000 High Tension Coupler connection, as shown in Fig. 2. The green LED labeled ACTIVE indicates that the Offline A PGR-6100 can be surface- or DIN-rail mounted. See Fig. 1. monitoring function is active. The insulation monitoring or lockout function is active when terminals 27 and 28 are Use terminal 6 (L1) as the line terminal for a 120 or 240 connected.
  • Page 7: Pgr-6100 Outline And Mounting Details

    <R 250 kΩ 2.0 MΩ 110.0 (4.33) FRONT SIDE 99.80 (3.93) 85.0 (3.35) (0.29) ANALOG AUTO FAIL AUTO FAIL OUT I OUT R INSULATION RESET SAFE RESET SAFE >1.3 KV BOTTOM MOUNTING DETAIL FIGURE 1. PGR-6100 Outline and Mounting Details.
  • Page 8: Pgh-5000 And

    PGH-5000/PGH-6000 terminal E monitored circuit with a PGH-5000 and PGH-6000 respectively. (PGR-6100 terminal 2 is not used). Connect terminal A to one See Fig. 4 for PGH-5000 outline and mounting details. See phase on the load side of the motor starter. See Fig. 2. The Fig.
  • Page 9: Pgc-5000-Series Current Sensors

    Page 5 PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 FIGURE 3. PGC-5000-Series Current Sensors.
  • Page 10: Pgh-5000 Outline And Mounting Details

    Page 6 PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 95.2 (3.75) 44.5 (1.75) (0.38) NOTE 2 POWR-GARD E E M PGH-5000 Æ 5kV HIGHTENSION COUPLER PGH-5000 5 KV HIGH TENSION COUPLER Æ 5,000 Vac Max. Coupling Voltage: PGH-5000 Current to Ground: 2.5 mA Max.
  • Page 11: Pgh-6000 Outline And Mounting Details

    Page 7 PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 145.0 (5.71) 98.5 120.0 12.50 (3.88) (4.72) (0.49) POWR-GARD POWR-GARD E E M PGH-6000 Æ 6kV HIGHTENSION COUPLER 6kV HIGHTENSION COUPLER PGH-6000 PGH-6000 6 KV HIGH TENSION COUPLER Æ Coupling Voltage: 6,000 Vac Max.
  • Page 12: Technical Specifications

    Page 8 PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 Altitude ..........2,000 m (6,562 ft) 4. TECHNICAL SPECIFICATIONS maximum 4.1 PGR-6100 Overvoltage Category ....II Supply: Pollution Degree ......2 120 Option ........5 VA, 120/24 Vac, (+10, -15%) 50/60 Hz Certification ..........UL Listed 240 Option...
  • Page 13: Pgh High Tension Couplers

    Page 9 PGR-6100 Ground-Fault & Insulation Monitor REV. 2-C-050818 5. ORDERING INFORMATION 4.2 PGH High Tension Couplers Maximum Line Voltage: PGR-6100- PGH-5000 ........5,000 Vac PGH-6000 ........6,000 Vac Supply: 120 – 120- or 24-Vac Supply Current to Ground......2.5 mA maximum 240 –...
  • Page 14: Tests

    10% of the SE-400 setting. Set the test current to 120% of the PGR-6100 1. Evaluate the interconnected system in accordance setting. Inject the test current through the CT window for with the overall equipment manufacturer’s detailed...
  • Page 15: Insulation Test

    Select a phase that is not connected to PGR-6100 terminal 2 (or the PGH-5000 or PGH-6000). The PGR-6100, operating in Offline mode (as indicated by the green ACTIVE LED), will alarm, operating the K1 low insulation output relay and lighting the red <R LED.
  • Page 16: Appendix A Pgr-6100 Revision History

    SECTION 5 Ordering information updated. APPENDIX A Revision history updated. REVISION 2-A-013014 SECTION 1 Product name changed to PGR-6100 Ground-Fault & Insulation Monitor. SECTION 3 Fig. 3 updated. SECTION 4 UL Certification and contact rating specifications added. REVISION 1 Initial release.