P.I. 08925720156 -Tel. +39 0331 577479 - Fax +39 0331 579479 E-mail: info@cdautomation.com - Web: www.cdautomation.com Declare that the product / Dichiara che il prodotto: Revo S 1PH 30-40A PRODUCT DESCRIPTION: Electric power control SCOPE OF APPLICATION: Thermal control process DESCRIZIONE DEL PRODOTTO: Unità...
User’s manual REVO S 1PH from 30A to 40A Important warnings for safety This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
Page 5
User’s manual REVO S 1PH from 30A to 40A WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse or other user serviceable component replacement must be performed only by properly qualified personnel. Service personnel must read this manual before proceeding with work. While service is being performed un-qualified personnel should not work on the unit or be allowed in the immediate vicinity.
Page 6
User’s manual REVO S 1PH from 30A to 40A AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés. WARNING! Verify the voltage and current ratings of the power controller are correct for the application. AVERTISSEMENT! Vérifier que les valeurs de tension et de courant du régulateur de puissance sont correctes pour l’application.
User’s manual REVO S 1PH from 30A to 40A Maintenance In order to have a corrected cooling, the user must clean the heat-sink and the protective grill of the fans. The frequency of this servicing depends on environmental pollution. Also check periodically if the screw for the power cables and safety earth are tightened correctly (See Connection Diagram) Warranty condition Producer gives a 12 months warranty to its products.
User’s manual REVO S 1PH from 30A to 40A Basic Connections Single phase wiring with resistive load I= P V V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load Open Delta wiring with resistive load I= P V = Nominal voltage of the load...
User’s manual REVO S 1PH from 30A to 40A tions General features Cover and Socket material: PolymericV2 Mounting: DIN bar (thickness type 1mm Max) Utilization Category: AC-51 AC-55b IP Code: Method of Connecting: Single Phase load Delay switch ON/OFF time: 1/2 Period Max Input features Logic input SSR:...
User’s manual REVO S 1PH from 30A to 40A Environmental installation conditions Ambient temperature 0-40 °C (32-104 °F) at nominal current. Over 40°C use the derating curve. Storage temperature -25°C to 70°C, -13°F to 158°F Installation place Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
User’s manual REVO S 1PH from 30A to 40A Installation Before to install, make sure that the Thyristor unit have not damages. ≥5 cm If the product has a fault, please contact the dealer from which you purchased the product. Verify that the product is the same thing as ordered.
User’s manual REVO S 1PH from 30A to 40A Wiring instructions The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions: •...
User’s manual REVO S 1PH from 30A to 40A Connection Diagram for Single-phase L2/N L2/N LOAD Input: INPUT Note: 1 A suitable device must ensure that the unit can be electrically isolated from the supply, this allows the qualified people to work in safety. 2 The thyristor unit must be protected by extrarapid fuses (optional).
User’s manual REVO S 1PH from 30A to 40A Firing type Zero Crossing ZC firing mode is used with Logic Output from temperature controllers and the Thyristor operates like a contactor. The Cycle time is performed by temperature controller. ZC minimizes interferences because the Thyristor unit switches ON-OFF at zero voltage.
User’s manual REVO S 1PH from 30A to 40A External Fuse (not included) The thyristor unit without IFH option (Internal Fuse + Fuse-Holder), must be protected by fuses against short circuit. The Fuses must have I²t 20% less than thyristor’s I²t. The warranty of thyristor is null if no proper fuses are used. Fuse + Fuse-Holder Fuse Code Current...
User’s manual REVO S 1PH from 30A to 40A Trouble shooting Small problems sometimes can be solved locally with the help of the below tab of trouble shooting. If you don’t succeed, contact us or your nearest distributor. Possible reasons Symptom Indication on front unit Actions...