(See Figure 1.) A Universal Sensor (A3060071) is supplied with the SetPoint 150 Controller. The wire to the sensor can be extended up to 500 feet (150m) with standard 18 AWG low-voltage wire. The display indicates a sensor fault when the sensor is open or has a short circuit.
Installation Inventory Check the contents of this package. If any contents listed below are missing or damaged, please contact your Uponor Wirsbo sales representative or distributor for assistance. • One SetPoint 150 Controller (A3040150) Caution: Improper • One Universal Sensor (A3060071) installation and operation •...
Connecting the Wiring Caution: Only properly trained and experienced technicians should perform these tests using standard testing practices and procedures. A good quality multimeter, capable of reading from at least 0 to 200VAC, and at least 0 to 2,000,000 Ohms, is essential to properly test this controller.
HEAT COOL Setpoint Differential Delay Sensor Connection Caution: Never apply voltage to these terminals. Item 1. Connect the Universal Sensor to Terminals 5 and 6. NRTL/C LR 58223 Setpoint Control Sequence of Operation A3040150 No Power Made in Canada On/Off + Differential Power Relay Signal Wiring must be Guidelines for programming the On/Off + Differential are stated...
Programming Digital Display The digital display on the SetPoint 150 Controller has the following features. • Displays the actual sensor temperature. • Allows the user to view and program the various controller settings. • Displays HEAT when the relay closes to operate a heat source and displays COOL when the relay closes to operate a cooling device.
Page 9
Programming Mode Push all three buttons at the same time and PRGM appears in the display. The controller is now in the programming mode. The pointer will flash to Setpoint. Push the UP or DOWN arrow buttons to increase or decrease the setpoint temperature. (See Figure 14.) Setpoint Range: -40 to 239°F (-40 to 115°C) Note: Programming settings have a 10-year memory backup.
Troubleshooting Follow the Testing the Wiring procedure on page 4 of this manual to troubleshoot the controller. 1. If Err displays, the sensor is open, has a short circuit or the sensor temperature is outside the temperature range of the controller.
Technical Data SetPoint 150 Controller (A3040150) Literature SetPoint 150 Controller Installation Manual Control Microprocessor P control; This is not a safety (limit) control. Package Weight 1 lb. (450 g) Dimensions 4 ³⁄₄ " H x 2 ⁷⁄₈ " W x ⁷⁄₈ " D (120 x 74 x 22mm)
SetPoint 150 Controller Wired to pro Series Controls This electrical drawing shows the connections between the SetPoint 150 Controller and respective pro Series controls. Wiring Diagrams...
Page 14
SetPoint 150 Controller Wired to Zone Control Module As shown, the SetPoint 150 Controller provides input to the Zone Control Module (ZCM) and operates the associated Motorized Valve Actuators (MVAs) on the corresponding terminal connections. The sensor (S1) can be placed within a concrete slab or strapped to supply or return piping in order to operate a pump (P1) and boiler based on a drop in temperature.
Page 15
SetPoint 150 Controller Wired to Single-zone Pump Relay As shown, the SetPoint 150 Controller operates a Single-zone Pump Relay (A3010100). Place the sensor (S1) within a concrete slab or strapped to piping to operate the pump (P1) based on a drop in temperature.
Page 16
SetPoint 150 Controller Wired to a Three-zone Multi-pump Relay As shown, the SetPoint 150 Controller operates a single pump using a Three-zone Multi-pump Relay (A3080301). The sensors (S1) can be placed within a concrete slab or strapped to piping in order to operate a pump (P1) based on a drop in temperature.