FAIRFORD ELECTRONICS LIMITED DFE-30 Installation Instructions Manual

Digital soft starters

Advertisement

Quick Links

Dfe
Digital Soft Starters
230Amp to 500Amp
Installation Instructions
Montageanweisung
Notice d'installation
Istruzioni per il montaggio
Instrucciones de montaje
This device is suitable for use in industrial
environments. EN 55011/22 Class A
Das Gerät ist für den industriellen Einsatz
geeignet EN 55011/22 Klasse A.
L'appareil a été conçu pour l'emploi en milieu
industriel EN 55011/22 classe A.
L'apparecchio è adatto per uso in ambienti
industriali EN 55011/22 Classe A.
El aparato es adecuado para uso en ambiente
industrial EN 55011/22 clase A.
DFE-30
132kW @ 400V 230Amp
DFE-32
160kW @ 400V 280Amp
DFE-34
200kW @ 400V 350Amp
DFE-36
250kW @ 400V 430Amp
DFE-38
280kW @ 400V 500Amp
Further information available
l
from the Fairford website
M a n u a
www.fairford.co.uk
Soft Starters and Energy
Optimising Soft Starters
F A I R F O R D
E L E C T R O N I C S
Electric shock risk. Danger
Only skilled or instructed persons may carry
out the following operations.
Lebensgefahr durch elektrischen Strom!
Nur Elektrofachkräfte und elektrotechnisch
unterwiesene Personen dürfen die im Folgenden
beschriebenen Arbeiten ausführen.
Tension électrique dangereuse !
Seules les personnes qualifées et averties doivent
exécuter les travaux ci-après.
Tensione elettrica: Pericolo di morte!
Solo persone abilitate e qualificate possono eseguire le
operazioni di seguito riportate.
¡Corriente eléctrica! ¡Peligro de muerte!
El trabajo a continuación descrito debe ser realizado por
personas cualificadas y advertidas.
The DFE is also available in smaller
sizes from the DFE-02 at 22Amp to
the DFE-26 at 195Amp
page 1 M-7A87-F 090710

Advertisement

loading

Summary of Contents for FAIRFORD ELECTRONICS LIMITED DFE-30

  • Page 1 El trabajo a continuación descrito debe ser realizado por industriali EN 55011/22 Classe A. personas cualificadas y advertidas. El aparato es adecuado para uso en ambiente industrial EN 55011/22 clase A. DFE-30 132kW @ 400V 230Amp DFE-32 160kW @ 400V 280Amp DFE-34...
  • Page 2 Dimensions – Abmessungen – Dimensioni – Dimensiones DFE-30 to DFE-38 132kW to 280kW M10 Earth M8 clearance Unit weights DFE30 & DFE32 9.7kg DFE34 to DFE38 13.5kg All Electrical connections are M10 Unit mountings suitable for M8 fixings. 160mm x 300mm centres...
  • Page 3 Power cables/Leistungsleitungen/Conducteurs de puissance/Cavi di potenza/ Conductores de potencia 1 L 1 , 3 L 2 , 5 L 3 2 T 1 , 4 T 2 , 6 T 3 DFE-30 & DFE-32 25x 5 2x 95mm M10 - 14Nm...
  • Page 4 Standard connection – Standardanschluss – Raccordement standard – Collegamento standard – Conexión estándar Soft starter with mains contactor - Softstarter mit Netzschütz – Démarreur progressif avec contacteur réseau – Softstarter con contattore di rete – Arrancador suave con contactor red +24VDC or 110VAC + 24VDC...
  • Page 5 Semiconductor contactor – Halbleiterschütz – Contacteur à semi-conducteurs – Contattore a semiconduttori – Contactor semiconductor 1 Undervoltage release with early-make auxiliary contact - Unterspannungsauslöser mit voreilendem Hilfsschalter - Déclencheur à manque de tension avec contact auxiliaire à action avancée - Sganciatore di minima tensione con contatto ausiliario anticipato - U>...
  • Page 6 Settings - Einstellungen - Réglages - Regulazioni - Regulaciones Uini Pedestal Voltage:- 30% for standard rating 100% 100% for high breakaway loads Stop Soft Stop time:- 0 = default range 0S to 30 S Start Soft Start time:- ~12 = default range 1S to 30S Green ☺...
  • Page 7 with circuit breaker with contactor L1, L2, L3 X1, X2 23, 24 A1, A2 13, 14 ~½ second T1, T2, T3 Rated Impulse withstand Voltage (Uimp) 2.5kV Rated Insulation Voltage (Ui) 500V Pollution Degree Short Circuit Co-ordination* Type 1 Ambient Temperature 0°C to 40°C.
  • Page 8: Sizing Guide

    Sizing Guide The DFE is designed for general purpose applications and where a traditional Star / Delta is currently used, or would be considered to be appropriate. Generally the motor will start off load, and the time to accelerate to full speed will be in the region of a few seconds. The standard DFE range is suitable for the majority of cases, and conforms to Trip Class5, which means it is capable of withstanding 3 times Full Load Current for 5 second starts.
  • Page 9 3.5-12: 1188 3-23: 1177 4-19: 1181 4-29: 1171 400V 400V 460V (Standard) (3/Hr) (3/Hr) (3/Hr) (3/Hr) DFE-32 DFE-26 DFE-26 DFE-30 DFE-22 132 A 75 KW 110 HP DFE-34 DFE-30 DFE-30 DFE-32 DFE-24 160 A 90KW 130 HP DFE-36 DFE-30 DFE-32...
  • Page 10 40°C 3 start/Hr x Ie rated Model current DFE-30 230A 1035 DFE-32 280A 1120 1260 DFE-34 350A 1050 1225 1400 1575 DFE-36 430A 1075 1290 1505 1720 1935 DFE-38 500A 1000 1250 1500 1750 2000 2250 Trip Level Current (Amps) The DFE can be used at ratings other than those stated.
  • Page 11 AC53b: 3-5: 355 Internally bypassed Control Supply 24V DC approx 12VA supplied externally to terminals X1-X2. DFE-30 to DFE-38 need a power supply capable of 4 Amps for 250ms. A suitable power supply kit is available from Fairford Over Current Trip Single phase sensing, Non adjustable.
  • Page 12 Fairford Electronics Limited, Coombe Works, Derby Road, Kingsbridge, Devon TQ7 1JL, UK TEL: + 44 (0) 1548 857494 FAX: + 44 (0) 1548 853118 EMAIL: sales@fairford.co.uk WEB: www.fairford.co.uk Registered No.: 1559267 England VAT No.: GB 367 2844 24 Copyright © Fairford Electronics Ltd 2009 Document No.