Rtd temperature sensor for temperature-measurement up to 900 f (482 c) in division 1 locations

Advertisement

Wiring inforMAtion
The length of RTD extension wires is determined by the wire
gauge used.
To reduce the likelihood that electrical noise will affect
temperature measurement, keep RTD extension wires as short as
possible.
Use shielded instrument cable such as Raychem MONI-RTD-WIRE
(22AWG, PVC insulation, –30°F to 140°F, –20°C to 60°C) or Belden
83553 (22 AWG, FEP insulation, –95°F to 395°F, –70°C to 200°C).
rtD Direct connection
c1D1 instAllAtion With heAting cAble
electrical Wiring notes:
Most electrical codes (such as NEC 725–15) permit Class 1 circuits
to occupy the same cable, enclosure, or raceway without regard
to whether the individual circuits are alternating current or direct
current, providing all conductors are insulated for the maximum
voltage of any conductors in the cable, enclosure or r aceway.
Additional Materials required
• Approved junction box (supplied by others)
• HAK-C-100
• Pipe strap
rtD7Al Wiring
Connect the wires as shown.
1 note: Ground RTD extension wire shield at one
end only, preferably at Raychem electronics end.
2 note: RTD housing must be properly grounded
using the screw provided.
NORTH AMERICA
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
thermal.info@pentair.com
Pentair is owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change
specifications without prior notice.
© 2001-2015 Pentair.
INDUSTRIAL HEAT TRACING SOLUTIONS
Electrical schematic of RTD
White
Red
Red
EuROpE, MIddlE EAsT, AfRICA
Tel: +32.16.213.511
Fax: +32.16.213.603
thermal.info@pentair.com
EN-RaychemRTD7AL-IM-H56916      11/15
Maximum rtD extension wire length
AWg
feet
16
4500
18
2800
20
1800
22
1100
Place strap under heating cable
Pipe strap
Field Wiring
White (Common return)
Red (Source)
Red (Compensate)
AsIA pACIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
cn.thermal.info@pentair.com
(meters)
(1400)
(880)
(550)
(340)
Conduit
drain
Agency approved
Div 1 junction box
(supplied by others)
HAK-C-100
Place pipe strap under heating cable
WWW.PENTAIRTHERMAL.COM
lATIN AMERICA
Tel: +1.713.868.4800
Fax: +1.713.868.2333
thermal.info@pentair.com
PN 229056-000
Pipe strap
Div 2
Div 1