Download Print this page

Honeywell RP418B Installation Instructions page 2

Electric/pneumatic relays

Advertisement

Available languages

Available languages

RP418A, B, C AND RP818A, B ELECTRIC/PNEUMATIC RELAYS
MP516A
RP418 OR RP818
Fig. 2. RP418 or RP818 relays mounted directly to an
MP516A operator using the 14003638-001 adaptor kit.
RP418 OR RP818
Fig. 3. RP418 or RP818 relays mounted directly to a
VP512C valve using the 14003638-001 adaptor kit.
Wiring and Piping
All pneumatic piping connections on the RP418 and RP818
are sized for 1/4-in. (6mm) OD polyethylene tubing. The con-
nections are sharp, barb-type connections. See Fig. 6 and 7.
Wiring connections on the RP418A and RP818A are made via
splices inside the splice box. Knockouts are provided on the
box. For ambient temperatures between 100 to 120°F (38 to
49°C) either use 75°C rated wire or attach a close-coupled
4 x 4 electrical box to the RP418A or RP818A splice box.
Make the wire splices within the electrical box.
Wire leads provide a means of connection on the RP418B
and RP818B. Use standard wire nut connectors, obtained
locally, when making these connections.
NOTE: A cord and plug are provided for wiring connections
on the RP418C.
The RP418 and RP818 relays require no adjustment or
calibration.
Automation and Control Solutions
Honeywell
Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
35 Dynamic Drive
Golden Valley, MN 55422
Scarborough, Ontario
M1V 4Z9
95-6046EF
J.H. Rev. 1-02
BRACKET
M18372
VP519C
BRACKET
M18373
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
PP910B
RP418 OR RP818
Fig. 4. RP418 or RP818 relays mounted directly to a
PP901B pressure regulator using the 14003638-001
adaptor kit.
RP418 OR RP818
Fig. 5. RP418 or RP818 relays mounted directly to a PP902
pressure regulator using the 14003638-001 adaptor kit.
RP418 OR
RP818
SUPPLY
1
AIR
3
Fig. 6. RP418 and RP818 typical wiring and piping.
2
1
3
DEENERGIZED:
PORTS 2 AND
3 CONNECTED,
PORT 1 BLOCKED.
Fig. 7. Pneumatic schematic.
BRACKET
M18375
PP920B
BRACKET
M18374
VOLTAGE
SUPPLY
FAN
SWITCH
2
EXHAUST
FAN MOTOR
DAMPER
DAMPER
OPERATOR
M18298
1
2
3
ENERGIZED:
PORTS 1 AND
3 CONNECTED,
PORT 2 BLOCKED.
M18299
customer.honeywell.com

Advertisement

loading

This manual is also suitable for:

Rp418cRp418aRp818bRp818a