Download Print this page

wattstopper LMIO-301 Installation Manual

Digital lighting management photocell input module

Advertisement

Quick Links

Warranty Information
WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are
no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use
or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal,
installation or reinstallation.
2800 De La Cruz Blvd.
Santa Clara, CA 95050
1/2011
Please
Phone: 800.879.8585
Recycle
www.wattstopper.com
13132r3
For full operational details and more features
of the Digital Lighting Management (DLM
System), see the DLM System Installation Guide
www.wattstopper.com
available at
INSTALLATION SHALL BE IN
For Class 2 Device Wiring Only –
ACCORDANCE WITH ALL
Do Not Reclassify and Install as
APPLICABLE REGULATIONS,
Class 1, or Power and Lighting
LOCAL AND NEC CODES.
Wiring.
For Class 2 DLM devices - To be
Wire connections shall be rated
connected to a Class 2 power source
suitable for the wire size (lead
only.
and building wiring) employed.
UNIT DESCRIPTION
The LMIO-301 photocell input module is an accessory for a
networked Digital Lighting Management (DLM) installation
that allows an LMSM segment manager to read ambient
light levels for use in controlling exterior lighting or interior
lighting installed in brightly day-lit spaces such as atriums.
The LMIO-301 works in conjunction with either the LMPO-
200 exterior or LMPS-6000 skylight low voltage photocell
heads.
OPERATION
The LMIO-301 operates on Class 2 power supplied to a DLM
local network by one or more room controllers or an LILM
panel. It transmits light levels over the segment network
as read from one of the remote analog LMPO or LMPS
photocell sensors. The LMIO-301 converts the analog signal
from the photocell sensor to a digital signal that is shared
across the network. The segment manager controls the
lighting based on user-defined setpoints and time delay
settings.
APPLICATION
The LMIO-301 photocell input module is an ideal solution
for any application where exterior lighting needs to be
controlled based on actual ambient exterior light levels
such as parking, site and landscape lighting. Applications
with large expanses of skylight, clearstory or atrium glazing
can also benefit from controlling lighting based on ambient
light entering the building through the glazing.
When controlling outdoor lighting, the LMPO-200 photocell
head mounts on the roof of the building facing North. The
LMPO-200 photocell head is waterproof and has a built in
hood to shield the lens from direct sunlight.
The LMPS-6000 photocell head is designed for indoor
applications with direct exposure to extremely high light
levels as would be present adjacent to the glass in an
atrium, skylight or clearstory.
LMIO-301
Digital Lighting Management
Photocell Input Module
Specifications
Voltage ................................................................................................ 24VDC
Current Consumption ........................................................................... 20mA
Power Supply ............................................... WattStopper Room Controllers
Connection to DLM Local Network ...........................................2 RJ-45 ports
Analog Input Voltage Range
Input 1 (terminal 9) ....................................................................... 0-5VDC
Input 2 (terminal 10) ................................................................... 1-10VDC
Supply Output @24VDC +/- 15% .............................................................. 5mA
Environment ...................................................................For Indoor Use Only
Operating Temperature .................................... 32° to 104°F (0° to 40°C)
Storage Temperature ......................................23° to 176°F (-5° to 80°C)
Relative Humidity ........................................... 5 to 95% (non condensing)
Other:
RoHS compliant
UL2043 Plenum rated
5-year warranty
LMPO-200 Outdoor Application
North
Sensor Hood
Watertight J Box
LMPO-200
Sensor
LMIO-301
#20 AWG up to 250 feet
#18 AWG up to 1000 feet
Class 2 wiring
To DLM Local Network
LMPS-6000 Skylight Application
Skylight
Well
Vertical
Orientation
Option
LMPS-6000
Sensor
#20 AWG up to 250 feet
LMIO-301
Class 2 wiring
To DLM Local Network

Advertisement

loading

Summary of Contents for wattstopper LMIO-301

  • Page 1 Sensor WattStopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of WattStopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.
  • Page 2 LMRC-3xx 24V Overload: Blinks (1x/sec) when terminal 5 (24VDC) Wiring LMRJ Cables 0-10 Volt Room Controller All connections to the LMIO-301 are Class 2 low voltage. Terminals output exceeds 5mA and the LMIO-301 shuts off the Ballast w/ Network J-Box Bridge output.
  • Page 3 MARCOM Email: dawn.revel@wattstopper.com Title: LMIO-301 Installation ENGINEERING Instructions All information in this drawing is the property of WattStopper and cannot be copied or used without the written approval of WattStopper. Orig. Drawing Date: 9 JUN 10 Drawing #: REV. #:...