Product features:
• Operating modes for visualization of input 1, input 2 or combinations of inputs (IN1+IN2, IN2-IN2,
IN1xIN2, IN1:IN2)
• Two universal 16 bit analog inputs for -10 ... +10 V / 0 ... 10 V / 0 ... 20 mA / 4 ... 20 mA
• High accuracy reference output 10 V for potentiometers > 1 kOhm
• Bright and high-contrast display with event-dependent color variations
• Emulation of a 7-segment display inclusively icons and units
• Intuitive and easy parameterization by plain text and touchscreen
• 24 V auxiliary output for encoder supply
• Totalization for each input
• Linearization with 24 control points for each input
• Numerous features, e. g. tara, averaging filter, sampling time for each input
• 3.78 x 1.89 inch norm panel housing and IP65 protection
Available Options:
• WAY-AX-S:
• Option AC:
• Option AO:
• Option CO:
• Option RL:
All options can be combined
Legal notices:
All contents included in this manual are protected by the terms of use and copyrights of WayCon GmbH. Any
reproduction, modification, usage or publication in other electronic and printed media as well as in the
internet requires prior written authorization by WayCon GmbH.
Display WAY-AX
Basic unit with 2 analog inputs (16 Bit), 3 control inputs
Power supply 115...230 VAC
16 bit analog output, 4 control outputs, serial RS232 interface
4 control outputs, serial RS232 interface
2 relay outputs

Advertisement

Table of Contents
loading

Summary of Contents for Waycon WAY-AX

  • Page 1 All options can be combined Legal notices: All contents included in this manual are protected by the terms of use and copyrights of WayCon GmbH. Any reproduction, modification, usage or publication in other electronic and printed media as well as in the...
  • Page 2: Table Of Contents

    Table of Contents Safety Instructions and Responsibility ................... 3 1.1. General Safety Instructions ....................3 1.2. Use according to the intended purpose ................. 3 1.3. Installation ..........................4 1.4. Cleaning, Maintenance and Service Notes ................4 Introduction ............................5 2.1. Operation mode ........................
  • Page 3: Safety Instructions And Responsibility

    Safety Instructions and Responsibility General Safety Instructions This operation manual is a significant component of the unit and includes important rules and hints about the installation, function and usage. Non-observance can result in damage and/or impairment of the functions to the unit or the machine or even in injury to persons using the equipment! Please read the following instructions carefully before operating the device and observe all safety and warning instructions! Keep the manual for later use.
  • Page 4: Installation

    1.3. Installation The device is only allowed to be installed and operated within the permissible temperature range. Please ensure an adequate ventilation and avoid all direct contact between the device and hot or aggressive gases and liquids. Before installation or maintenance, the unit must be disconnected from all voltage-sources. Further it must be ensured that no danger can arise by touching the disconnected voltage-sources.
  • Page 5: Introduction

    Introduction This series of display unit is suitable for analog signals (-10 … 10V or 0/4 … 20 mA). It is very versatile in use, due to the intuitive handling and the extensive range of functions and options. 2.1. Operation mode All functions are can be configured in the parameter menu.
  • Page 6: Electrical Connections

    3. Electrical Connections The terminal screws should be tightened with a slotted screwdriver (blade width 2mm). 3.1. DC Power Supply The unit accepts DC supply from 18 to 30 V at the terminals 1 and 2. The power consumption depends on the level of the supply voltage with aprox.
  • Page 7: Analog Input

    3.3. Analog Input The reference potential (AGND) for the analog inputs is connected at terminal 5. The unit provides two 16 bit analog inputs at terminal 6 and 7. The characteristics of the analog inputs (voltage input or current input ) can be set in the Menu IN 1/IN 2 PROPERTIES. Important: Before connecting the sensor the configuration (voltage or current input) must be set!
  • Page 8: Control Inputs

    3.5. Control Inputs The three control inputs at terminal 10, 11 and 12 have HTL PNP characteristics. In the COMMAND MENU the programmable functions for the control inputs can be assigned. Available functions are: reset the display value, display switching, locking the touch screen or release the lock function of the control or relay outputs.
  • Page 9: Serial Interface (Option Ao / Co)

    3.7. Serial interface (Option AO / CO) A serial interface (RS232) is available at terminal 16, 17 und 18. This interface can be configured in the SERIAL MENU. The serial interface RS232 can be used: • for easy setup and commissioning of the units •...
  • Page 10: Ac Power Supply (Option Ac)

    3.9. AC Power supply (Option AC) The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25. The power consumption depends on the level of the supply voltage and the additional current required at the auxiliary voltage output and is about 3 VA.
  • Page 11: Display And Touch Screen

    Display and touch screen 4.1. Screen structure for parametrization The parameter menus and the parameters are described in chapter 5. Start setup procedure: To edit the parameters, press the touchscreen for 3 seconds. Menu selection: Select the parameter menu via arrow buttons and confirm with “OK”.
  • Page 12: Screen Structure In Operation

    4.2. Screen structure in operation The following screens are available during operation. Depending on the device version and the selected operation mode, not all displays will be shown. The source (IN1, IN2, …) for the single channel display and the two channel display are defined in the DISPLAY MENU.
  • Page 13 Display with actual / minimum / maximum values of input 1 and input 2 To switch to the next display, type on the touch screen. Seite 13 / 48...
  • Page 14: Parameter / Overview-Menu Structure

    Parameter / Overview-Menu Structure This section provides an overview of the menus and their parameters. The menu names are printed bold and the associated parameters are listed under the menu name. Depending on the device version and the selected operation mode, only the necessary menus / parameters are shown. Menu / Parameter Menu / Parameter GENERAL MENU...
  • Page 15 Menu / Parameter Menu / Parameter PRESELECTION 1 MENU SERIAL MENU SOURCE 1 UNIT NUMBER MODE 1 SERIAL BAUD RATE HYSTERESIS 1 SERIAL FORMAT PULSE TIME 1 SERIAL INIT OUTPUT TARGET 1 SERIAL PROTOCOL OUTPUT POLARITY 1 SERIAL TIMER OUTPUT LOCK 1 SERIAL VALUE START UP DELAY 1 ANALOG OUT MENU...
  • Page 16: General Menu

    5.1. General Menu OPERATIONAL MODE This parameter specifies the selected measuring function. SINGLE Single channel mode, only input 1 DUAL Dual channel mode, input 1 and input 2 separated IN1 + IN 2 Dual channel mode, sum of input 1 and input 2 IN1 –...
  • Page 17: In 1 Properties

    5.2. IN 1 Properties This menu defines the parameter for input 1. CONFIGURATION This parameter defines the configuration of input 1. -10 … 10 V -10 … 10 V 0 … 20 mA 0 … 20 MA 4 … 20 mA 4 …...
  • Page 18 Continuation „IN 1 Properties“: SCALE UNITS This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number of decimal places must be defined with the parameter DECIMAL POINT. Default km/h feet/min inch/min inch feet...
  • Page 19 Continuation„IN 1 Properties“: SAMPLING TIME (S) The configured value corresponds to the sampling interval. This time interval in seconds defines the time between the single samples of the analog signals. This parameter directly affects the response time of the unit. 0,001 Shortest sampling time 0,01...
  • Page 20: In 1 Linearization

    5.3. IN 1 Linearization The linearization points of input 1 are defined in this menu. This menu is shown only, if the linearization is selected in 1 PROPERTIES. Linearization description and examples are shown in the appendix. P1(X) … P24(X) X-coordinate of the linearization point.
  • Page 21: In 1 Totalization

    5.4. IN 1 Totalization The totalization function is defined in this menu. This menu will only be showed, if the totalization is active in Menu IN 1 PROPERTIES. The totalizator depends on the operation mode. See in the following list. Totalisation Operation mode INPUT 1 TOTAL...
  • Page 22 Continuation„IN 1 Totalization“: SCALE UNITS This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number of decimal places must be defined with the parameter DECIMAL POINT. Default km/h feet/min inch/min inch feet 1/sec...
  • Page 23: In 2 Properties

    IN 2 Properties This menu defines the parameter for input 2. CONFIGURATION Configuration of input 2, see IN 1 Properties START VALUE Display value of input 2 at 0 V or 0/4 mA, see IN 1 Properties END VALUE Display value of input 2 at +10 V or 20 mA, see IN 1 Properties DECIMAL POINT Position of the decimal point, see IN 1 Properties SCALE UNITS...
  • Page 24: In 2 Linearization

    IN 2 Linearization The linearization points of input 2 are defined in this menu. P1(X) … P24(X) X-coordinate of the linearization point, see IN 1Linearization. P1(Y) … P24(Y) Y-coordinate of the linearization point, see IN 1Linearization. IN 2 Totalization The totalization function is defined in this menu. TIME BASE The time base of the totalization, see IN 1 Totalization DIVIDER...
  • Page 25: Linkage Properties

    Linkage Properties In this menu the parameters for the linked operation mode are defined. This menu is shown only, if in GENERAL MENU an operation mode (z.B. IN1 – IN2) with link was selected. The parameters in Menu IN 1 PROPERTIES and IN 2 PROPERTIES have to be set, before using a linked operation mode.
  • Page 26 Continuation „Linkage Properties Menu“: SCALE UNITS This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number of decimal places must be defined with the parameter DECIMAL POINT. Default km/h feet/min inch/min inch feet...
  • Page 27: Preselection Values

    Preselection Values This menu is used to set the preselection values or the switching points. The preselection values / switching points are always referred to the display value. This menu is only available for devices with option CO, A0 or RL. PRESELECTION 1 Preselection / switching point 1 -99999999...
  • Page 28: Preselection 1 Menu

    5.10 Preselection 1 Menu Switching conditions for preselection 1. Output/ relay/ display switches under the following conditions. This function is only available for devices with option CO, AO or RL. SOURCE 1 This parameter defines the reference source for PRESELECTION 1 the reference source is input 1 INPUT 1 the reference source is input 2...
  • Page 29 Continuation „Preselection 1 Menu“: MODE 1 Switching conditions for preselection 1. Output/ relay/ display switches under the following conditions: Absolute value of the display value is greater or equal absolute value of PRESELECTION 1 0 |RESULT|>=|PRES| With HYSTERESIS 1 not equal 0 the following switching condition is applied: Display value >= PRESELECTION 1 ...
  • Page 30 Continuation „Preselection 1 Menu“: HYSTERESIS 1 This parameter defines the switching hysteresis of the switch-off point for preselection 1 No switching hysteresis … 99999 Switching hysteresis of 99999 PULSE TIME 1 (S) Duration of output pulse for the switching condition of preselection 1 0,000 No output pulse (static signal) …...
  • Page 31 Continuation „Preselection 1 Menu“: START UP DELAY 1 (S) Start-up suppression for the switching condition of preselection 1. This adjustment is only valid for the switching condition |RESULT|<=|PRES| or RESULT<=PRES (Start Up Delay 3 and 4 have an automatic start up suppression). 0.000 No start-up suppression …...
  • Page 32: Preselection 2 Menu

    5.11 Preselection 2 Menu SOURCE 2 The reference source for PRESELECTION 2, see PRESELECTION 1 MENU MODE 2 Switching conditions for preselection 2, see PRESELECTION 1 MENU (expect trailing preselection) See chapter PRESELECTION 1 MENU Trailing preselection 2: RES>=PRES- Display value is greater or equal to PRESELECTION 1 – PRESELECTION 2 TRAIL PRESELECTION 2 is the trailing preselection from PRESELECTION 1.
  • Page 33: Preselection 3 Menu

    5.12 Preselection 3 Menu SOURCE 3 The reference source for PRESELECTION 3, see PRESELECTION 1 MENU MODE 3 Switching conditions for preselection 3, see PRESELECTION 1 MENU (expect trailing preselection) See chapter PRESELECTION 1 MENU Trailing preselection 3: RES>=PRES- Display value is greater or equal to PRESELECTION 4 – PRESELECTION 3 TRAIL PRESELECTION 3 is the trailing preselection from PRESELECTION 4.
  • Page 34: Preselection 4 Menu

    5.13. Preselection 4 Menu SOURCE 4 The reference source for PRESELECTION 4, see PRESELECTION 1 MENU MODE 4 Switching conditions for preselection 4, see PRESELECTION 1 MENU (expect trailing preselection) See chapter PRESELECTION 1 MENU Trailing preselection 4: RES>=PRES- Display value is greater or equal to PRESELECTION 3 – PRESELECTION 4 TRAIL PRESELECTION 4 is the trailing preselection from PRESELECTION 3.
  • Page 35: Serial Menu

    5.14. Serial Menu This menu defines the basic settings of serial interface. This function is only available for devices with option CO or A0 UNIT NUMMER This parameter defines serial device addresses. The addresses between 11 and 99 can be assigned to the devices.
  • Page 36 Continuation „Serial Menu”: SERIAL PROTOCOL Determines the sequence of characters send, when using the serial output for cyclic data transmission under time control (xxxxxxx = value SERIAL VALUE). Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle. Transmission report = Unit Nr., +/-, data, LF, CR Transmission report = +/-, data, LF, CR SERIAL TIMER (S)
  • Page 37: Analog Out Menu

    5.15. Analog Out Menu This menu defines the basic settings of the analog output. This function is only available for devices with option A0. SOURCE 1 This parameter defines the reference source for PRESELECTION 1 the reference source is input 1 INPUT 1 the reference source is input 1 INPUT 2...
  • Page 38 Continuation „Analog Out Menu“: ANALOG GAIN (%) This parameter specifies the maximum conversion of the analog output in %. e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is reached. e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is reached.. 0,00 Smallest gain 100,00...
  • Page 39: Command Menu

    5.16. Command Menu INPUT 1 ACTION This parameter defines the function of the input “Ctrl. In 1”. No function TARA INPUT 1 Value of input 1 is stored as an OFFSET of input 1 TARA INPUT 2 Value of input 2 is stored as an OFFSET of input 2 Value of input 1 is stored as an OFFSET of input 1 TARA INPUT 1+2 Value of input 1 is stored as an OFFSET of input 1...
  • Page 40 Continuation „Command Menu:“ INPUT 1 CONFIG This parameter defines the switching characteristics of the input “Ctrl. In 1”. ACTIVE LOW Active at „LOW“ (static) ACTIVE HIGH Active at „HIGH“ (static) RISING EDGE Activate at rising edge (dynamic) FALLING EDGE Activate at falling edge (dynamic) INPUT 2 ACTION This parameter defines the function of the input “Ctrl.
  • Page 41: Display Menu

    5.17. Display Menu Parameter changes become active only after closing the menu selection. START DISPLAY This parameter defines the start display after switching on the device. Single-channel display Single The source must be defined in SOURCE SINGLE Dual The sources must be defined in SOURCE DUAL TOP / DOWN. SOURCE SINGLE the reference source is input 1 INPUT 1...
  • Page 42 Continuation „ Display Menu“: COLOR This parameter defines the display color. Event-depending change of the display color by a switching condition is possible (see PRESELECTION 1…4 MENU) Event-depending changes are only available for devices with option CO350, A0350 or RL350. Red display GREEN Green display...
  • Page 43: Appendix

    Appendix 6.1. Data readout via serial interface All codes shown in the parameter SERIAL VALUE are available for serial readout by PC or PLC. For communication the monitors use the Drivecom Protocol according to ISO 1745. To request for a data transmission you must send the following request string to the converter: EOT = control character (Hex 04) AD1 = unit address, High Byte AD2 = unit address, Low Byte...
  • Page 44: Linearization

    6.2. Linearization The linearization function of this unit allows converting a linear input signal into a non-linear developing (or vice versa). There are 24 programmable x/y coordinates available for input 1 and input 2, which can be set in any desired distance over the full conversion range. Between two coordinates, the unit uses linear interpolation.
  • Page 45 Application Example: We like to display the filling quantity (volume) of a tank as shown below, with use of a pressure sensor mounted to the bottom of the tank. With this application the analogue pressure signal is proportional to the filling level, but not to the filling quantity.
  • Page 46: Dimensions

    6.3. Dimensions Dimension in mm [inch] Seite 46 / 48...
  • Page 47: Technical Specifications

    6.4. Technical specifications Seite 47 / 48...
  • Page 48 Technical Specifications: Connections: Connector type: screw terminal, 1.5 mm² / AWG 16 Power supply (DC): Input voltage: 18 … 30 VDC Protection circuit: reverse polarity protection Consumption: approx. 100 mA (unloaded) Fuse protection: extern: T 0,5A Power supply (AC): Input voltage: 115…230 VAC, 50…60 Hz) (Option AC) Power consumption:...