Foreign Device support to connect to multiple networks and password protected browser based setup screens. The B6060 has a built in web server that allows users to log in using a web browser. Once a user is logged in, configuration is easy and very self explanatory.
Page 4
B6060 User Manual Cimetrics, Inc Meters Configuration (if any} Sett;ngs for serial line devices Parameter Va lue Description 9600 Baud rate The baud rate serial port (Oefaul =9600) Serial Mode Default mode: (8 data bits, pairity, 1 stop bit) Common...
Page 5
B6060 User Manual Cimetrics, Inc Note: You can integrate a second meter and it is an advanced configuration. For correct wiring, please, refer to Spirax Sarco FP-93 flow processor documentation.
When you click on "Activate Configuration" and “confirm” then the configuration process is completed. Please Note: A user will be able to access the B6060 using the above mentioned IP address at ALL TIMES (even if you have changed the IP address under BACnet/IP settings)
The Home Page displays five important Objects of each meter that has been configured. The example below shows that this B6060 is connected to one Emco meter and shows five important objects from this meter. This is not user configurable as it is only a snapshot of the meters configured.
Page 8
B6060 User Manual Cimetrics, Inc 100014 Download configuration: Clicking on this button will initiate a download of the existing configuration. This will be downloaded as a text file. This file can be saved for uploading (without any edits) in the future to restore a previous configuration.
BACnet Device. Default ID is generated from the MAC address of B6060. 6. BBMD IP Address – If you want B6060 to be a foreign device then here you specify IP address of target BBMD. It will enable Foreign Device mode.
B6060 User Manual Cimetrics, Inc Meters Configuration On this screen, a user can configure an FP-93 that will be integrated into the BACnet/IP network. The user will need to choose the appropriate baud rate and the serial mode. Please note that if...
B6060 User Manual Cimetrics, Inc BACnet Object Status On this screen, a user can view the BACnet Objects of each of the configured Meters. The following parameters of each BACnet Object are viewable Name Object Value Units Status Description The information on the page gives the user a snapshot of the entire configuration...
B6060 User Manual Cimetrics, Inc Reset Configuration Clicking on Restore default will reset the entire device's configuration to factory defaults. Clicking on Discard changes will discard all changes and revert to active configuration.
B6060 User Manual Cimetrics, Inc Activate Configuration Once changes are made to any configuration on the B6060, the changes get saved only after clicking on the "Confirm" button in the Activate Configuration screen. Clicking on this will initiate a reboot of the device and will save the changes that have been made.
Need help?
Do you have a question about the B6060 and is the answer not in the manual?
Questions and answers