Page 1
www.eurovent-certification.com Cert. n° 0545 CRC-ECM Carisma CRT-ECM CRS-ECM Fan Coil Units The Fan Coil Unit with EC Brushless Electronic Motor and Inverter Board T E C H N I C A L G U I D E...
Page 60 The air flow rate can be varied in continuous by means CRC–ECM/CRT–ECM/CRS–ECM • version of a 1-10 V signal generated by Sabiana controls or by • Accessories Page 62 • CRYSTALL electrostatic filter Page 83 independent control systems. The continuous air flow •...
Page 3
Carisma CRC–ECM version with centrifugal fan Range includes 5 air flow rates (from 115 to 1395 m /h) and 5 models (for wall and ceiling installation, with casing and concealed), each equipped with 3 or 4 row coil and with the possibility to add a 1 or 2 row coil for 4 pipe systems.
CRC–ECM Carisma CRC–ECM version Construction Outer casing Made of strong synthetic lateral corners and from galvanized and prepainted front steel panel. The plastic top grid has fixed louvres and is reversible in order to distribute the air in two different directions. Standard colours: •...
CRC–ECM Carisma CRC–ECM version Models Vertical Casing – Wall Installation Vertical Casing – Ceiling Installation NOTE: the MV model can also be installed horizontally leaving behind a 100 mm gap for air intake. MO-MVB MO-MVB Vertical Casing – Floor Installation Horizontal Casing IV-IO IV-IO...
CRC–ECM Carisma CRC–ECM version EUROVENT Certification www.eurovent-certification.com CRC−eCM units with Row Coil 2 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T.
Page 11
CRC–ECM Carisma CRC–ECM version EUROVENT Certification www.eurovent-certification.com CRC−eCM units with Row Coil 2 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 45°C E.W.T.
Page 12
CRC–ECM Carisma CRC–ECM version EUROVENT Certification www.eurovent-certification.com CRC−eCM units with Row additional Coil 4 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 65°C E.W.T.
Highest water inlet temperature....... + 85 °C Lowest water inlet temperature........ + 5 °C for entering water temperatures below + 5°C, contact “SABIANA” technical department Highest working pressure........1000 kPa (10 bars) Note: For MO model the maximum installation height is 2,8 m.
CRC–ECM Carisma CRC–ECM version Cooling emission of 3 row coil Entering air temperature: 27°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,72 1,27 1,53 1,19 1,12...
Page 15
CRC–ECM Carisma CRC–ECM version Cooling emission of 3 row coil Entering air temperature: 26°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,52 1,19 1,33 1,12 0,99...
Page 16
CRC–ECM Carisma CRC–ECM version Cooling emission of 3 row coil Entering air temperature: 25°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,33 1,12 1,13 1,04 0,90...
Page 17
CRC–ECM Carisma CRC–ECM version Cooling emission of 4 row coil Entering air temperature: 27°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 2,00 1,42 16,9 1,79 1,33...
Page 18
CRC–ECM Carisma CRC–ECM version Cooling emission of 4 row coil Entering air temperature: 26°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,78 1,33 13,8 1,57 1,25...
Page 19
CRC–ECM Carisma CRC–ECM version Cooling emission of 4 row coil Entering air temperature: 25°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,57 1,25 11,0 1,35 1,16...
Page 20
CRC–ECM Carisma CRC–ECM version Heating emission of 3 row coil Entering air temperature: 20°C WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 3,64 2,78 1,92 2,22 1,80 3,09 2,36 1,63...
Page 21
CRC–ECM Carisma CRC–ECM version Heating emission of 4 row coil Entering air temperature: 20°C WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 4,01 12,9 3,07 2,14 2,45 19,4 1,98 13,6...
Page 22
CRC–ECM Carisma CRC–ECM version Heating emission of 1 row additional coil Entering air temperature: 20°C WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 2,04 1,84 1,018...
Page 23
CRC–ECM Carisma CRC–ECM version Heating emission of 2 row additional coil Entering air temperature: 20°C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C WT: 50/40 °C WT: 45/40 °C WT: 45/35 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 2,48 16,7 21,6...
CRC–ECM Carisma CRC–ECM version Water pressure drop 3 row coil 4 row coil Dp - kPa Dp - kPa Water Water flow (l/h) flow (l/h) 1000 1500 1000 1500 The water pressure drop figures °C refer to a mean water temperature of 10°C; for different temperatures, multiply 0,94 0,90...
CRT–ECM Carisma CRT–ECM version Construction Outer casing Made of strong synthetic lateral corners and from galvanized and prepainted front steel panel. The plastic top grid has fixed louvres and is reversible in order to distribute the air in two different directions. Standard colours: •...
CRT–ECM Carisma CRT–ECM version Models Vertical Casing – Wall Installation Vertical Casing – Ceiling Installation NOTE: the MV model can also be installed horizontally leaving behind a 100 mm gap for air intake. MO-MVB MO-MVB Vertical Casing – Floor Installation Horizontal Casing IV-IO IV-IO...
CRT–ECM Carisma CRT–ECM version EUROVENT Certification www.eurovent-certification.com CRt−eCM units with Row Coil 2 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T.
Page 33
CRT–ECM Carisma CRT–ECM version EUROVENT Certification www.eurovent-certification.com CRt−eCM units with Row additional Coil 4 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T.
Highest water inlet temperature....... + 85 °C Lowest water inlet temperature........ + 5 °C for entering water temperatures below + 5°C, contact “SABIANA” technical department Highest working pressure........1000 kPa (10 bars) Note: For MO model the maximum installation height is 2,8 m.
CRT–ECM Carisma CRT–ECM version Cooling emission of 3 row coil Entering air temperature: 27°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,08 0,85 0,95 0,80 0,71...
Page 36
CRT–ECM Carisma CRT–ECM version Cooling emission of 3 row coil Entering air temperature: 26°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 0,94 0,80 0,81 0,75 0,65...
Page 37
CRT–ECM Carisma CRT–ECM version Cooling emission of 3 row coil Entering air temperature: 25°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 0,82 0,75 0,71 0,71 0,60...
Page 38
CRT–ECM Carisma CRT–ECM version Cooling emission of 3+1 row coil Entering air temperature: 27°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 1,03 0,81 0,91 0,76 0,68...
Page 39
CRT–ECM Carisma CRT–ECM version Cooling emission of 3+1 row coil Entering air temperature: 26°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 0,90 0,76 0,78 0,71 0,62...
Page 40
CRT–ECM Carisma CRT–ECM version Cooling emission of 3+1 row coil Entering air temperature: 25°C – R.H.: 50% WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 0,78 0,71 0,67 0,67 0,57...
Page 41
CRT–ECM Carisma CRT–ECM version Heating emission of 3 row coil Entering air temperature: 20°C WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 2,63 1,99 1,35 1,61 1,29 1,95 1,48 1,01...
Page 42
CRT–ECM Carisma CRT–ECM version Heating emission of 3+1 row coil Entering air temperature: 20°C WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 1,38 1,24 1,09 0,95...
CRT–ECM Carisma CRT–ECM version Water pressure drop 3 row coil Dp - kPa The water pressure drop figures refer to a mean water temperature of 10°C; for different temperatures, multiply the pressure drop figures by the correction factors K. °C Water 0,94 0,90...
CRS–ECM Carisma CRS–ECM version Construction features Casing Made from 1 mm galvanized steel insulated with 3 mm polyolefin (PO) foam (class M1). Filter Polypropylene cellular fabric regenerating filter. The filter frame of galvanized steel is inserted into special plastic sliding guides fastened to the internal structure for easy insertion and removal of the filter.
CRS–ECM Carisma CRS–ECM version Dimension, Weight, Water content Vertical Installation Coil connections on the left Ø 15 ext. Supply frame dimension = E 119 mm Auxiliary condensate tray (optional) Horizontal Installation Ø 15 ext. Supply frame dimension = E 119 mm COIL CONNECTIONS 3 or 4 row coils Heating additional coil (1 or 2 rows)
CRS–ECM Carisma CRS–ECM version EUROVENT Certification www.eurovent-certification.com CRs−eCM units with Row Coil 2 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T.
Page 49
CRS–ECM Carisma CRS–ECM version EUROVENT Certification www.eurovent-certification.com CRs−eCM units with Row additional Coil 4 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T.
CRS–ECM Carisma CRS–ECM version Main performance and technical characteristics 2 pipe units. The following standard rating conditions are used: COOLING HEATING Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C Water temperature + 7°C E.W.T. + 12°C L.W.T. Water temperature + 45°C E.W.T.
Highest water inlet temperature....... + 85 °C Lowest water inlet temperature........ + 5 °C for entering water temperatures below + 5°C, contact “SABIANA” technical department Highest working pressure........1000 kPa (10 bars) Water flow limits for 3 row coil (l/h) CRS−ECM 13...
CRS–ECM Carisma CRS–ECM version Cooling emission of 3 row coil Entering air temperature: 27°C – R.H.: 50% – Available pressure: 0Pa WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 3,84 2,86...
Page 53
CRS–ECM Carisma CRS–ECM version Cooling emission of 3 row coil Entering air temperature: 25°C – R.H.: 50% – Available pressure: 0Pa WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 3,01 2,55...
Page 54
CRS–ECM Carisma CRS–ECM version Cooling emission of 4 row coil Entering air temperature: 27°C – R.H.: 50% – Available pressure: 0Pa WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 4,47 3,26...
Page 55
CRS–ECM Carisma CRS–ECM version Cooling emission of 4 row coil Entering air temperature: 25°C – R.H.: 50% – Available pressure: 0Pa WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C Qw Dp(c) Qw Dp(c) Qw Dp(c) Qw Dp(c) odel 3,50 2,88...
Page 56
CRS–ECM Carisma CRS–ECM version Heating emission of 3 row coil Entering air temperature: 20°C – Available pressure: 0Pa WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) odel 8,03 36,9 6,15 23,8...
Page 57
CRS–ECM Carisma CRS–ECM version Heating emission of 1 row additional coil Entering air temperature: 20°C – Available pressure: 0Pa WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C Dp(c) Dp(c) Dp(c) Dp(c) Dp(c) Dp(c)
CRS–ECM Carisma CRS–ECM version Air flow and emission correction factors with different available pressure mission correction factors 10 V for high speed figures at signaL Qv (m Ap ( Ap ( Ap ( odel 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 1,00 0,97 0,92...
Page 59
CRS–ECM Carisma CRS–ECM version Air flow table, correction factors for emission and Watts absorbed by the motor with different available pressures Qv (m Qv % Ap ( Ap ( Ap ( odel 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 1,00 0,95 0,89...
CRS–ECM Carisma CRS–ECM version Water pressure drop 3 row coil 4 row coil Dp - kPa Dp - kPa Water Water flow (l/h) flow (l/h) 1000 1500 1000 1500 The water pressure drop figures °C refer to a mean water temperature of 10°C; for different temperatures, multiply 0,94 0,90...
Page 61
Carisma CCessoRies and ontRols foR CRC–ECM version with centrifugal fan CRT–ECM version with tangential fan CRS–ECM version with high pressure centrifugal fan...
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version main coil 3 way valve Control valve kit: 3 way valve, ON-OFF, with electric motor and mounting kit with micrometric lockshield valve. CRC–eCM / CRt–eCM eRsion CRs–eCM MV –...
Page 63
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version simplified kit for 3 way valve (concealed model only) 3 way valve, (ON-OFF) with electric motor and mounting kit. Valve with flat connection without micrometric lockshield valve. CRC–eCM / CRt–eCM eRsion CRs–eCM...
Page 64
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version 3 way double valve kit for 4 tube installation and single coil The kit consists of: • 2 special 3 way valves; • 2 230 Volt ON-OFF actuators with internal safety micro switch; •...
Page 65
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version Balancing valves independent from the system pressure • The balancing valve and a combined 2 way valve allow the regulation of the water flow value autonomously, regardless of the system pressure, and the control of the flow by using an ON/OFF electro-thermal actuator.
Page 66
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version The valve upstream-downstream minimum differential pressure (“p1” – “p3”), which depends on the valve calibration value, must be exceeded to access the constant flow rate field. DN 10 Model DN 15 Model DN 20 Model...
Page 67
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version Balancing valves for main coil 2 way valve for main coil and assembly kit. The valve is supplied equipped with 230 Volt electro-thermal actuator for the ON/OFF control. CRC–eCM / CRt–eCM eRsion CRs–eCM...
Page 68
BREEZE frame kit for wall concealed installation The Carisma Breeze frame kit is available in 3 sizes and allows the installation of recessed Carisma CRC-ECM fan coils. The kit includes a top closing panel that prevents the access to technical spaces and coil ensuring the safety of the end user.
Page 69
CRC–ECM Carisma Accessories for CRC–ECM version Technical characteristics of the main components: The aesthetic frame includes: • the closing frame; • air supply louvre; • front panel; • air intake grid. Perimeter frame, front panel and intake grid are made of steel painted with epoxy polyester coat, dried in a furnace at 180°, colour RAL 9003.
Page 70
CRC–ECM Carisma Accessories for CRC–ECM version Aesthetic frame dimensions CRC–eCM eRsion odel aCkaged esthetiC RaMe eight CBR A 9076452 10,5 CBR B 1052 9076453 12,5 CBR C 1267 9076455 14,5...
Page 77
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version FRD straight inlet flange Can be used together with GRAG air inlet grid. Made of galvanized steel. CRC–eCM / CRt–eCM eRsion CRs–eCM iV – io odel CRC/CRt –...
Page 78
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version GRAG air inlet grid To be used with FRD straight inlet flange. Made of anodized aluminium. CRC–eCM / CRt–eCM eRsion CRs–eCM iV – io odel CRC/CRt CRs esCRiption –...
Page 79
Accessories for CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version FM 90 90° outlet flange Made of galvanized steel insulated with polyethylene lining. CRC–eCM eRsion CRs–eCM iV – io odel – FM90 - 2 9066382 FM90 - 3/4 38,5 9066383 –...
Page 80
CRC–ECM Carisma Accessories for CRC–ECM version PMC spigot diffuser Made of galvanized steel insulated with polyethylene lining. CRC–eCM eRsion All the plenums CRs–eCM iV – io are supplied with spigots odel for the connection of flexible ducts. pigots – PMC - 2 N°...
Page 81
CHK Hotel fan kit Hotel box for concealed installation for Carisma CRC-ECM, IO model (frontal return and supply). The new CHK kit is the best solution for all installations requiring a built-in fan coil where there is no other possibility of accessing the unit except from the air outlet side.
Page 82
Accessories for CRC–ECM / CRS–ECM Carisma CRC–ECM / CRS–ECM version BXS silencers plenum Sound attenuator module Made of galvanised steel metal sheet, lined internally with a reinforced glass wool mat on both sides with a black glass coating; the 50 mm and 30 kg/m density lining ensures high noise reduction with very low pressure drops.
Crystall (CRC–ECM only) Introduction The CRYSTALL SABIANA electrostatic filter matches the need for better air conditioning with the concepts of space and design. With this filter the various stages of air treatment are combined in one appliance. Thanks to this new patented filter (efficiency compliant with new Standard UNI 11254), air pollutants such as cigarette smoke, dust (PM10, PM2.5), pollen and most...
CRC–ECM / CRT–ECM / CRS–ECM Carisma CRC–ECM / CRT–ECM / CRS–ECM version CRC–ECM / CRT–ECM / CRS–ECM configuration For this fan coil configuration, the 1-10 Vdc signal, which controls the inverter, must be supplied by a controller with the following signal specifications: Fan coil control signal 0 Vdc = Fan OFF...
The most evolved CB-T-ECM version allows the manual and the automatic speed switch or the continious variation of the fan speed. For the Carisma CRC-ECM units, supplied with Crystal filter or with electric heater, the CB-T-ECM-IAQ control is available.
CRC–ECM / CRT–ECM / CRS–ECM version Controls and units MB version All the Carisma CRC-ECM / CRT-ECM / CRS-ECM units can be supplied in MB version. This version includes a wide range of controls, including the infra-red remote control, which allows managing one single unit or several units by using the Modbus RTU - RS 485 communication protocol.
KNX laboratories. KNX devices The Sabiana WM-KNX room thermostat controls and adjusts the temperature of a room or area in a building. In combination with one or several UP-KNX power units, the thermostat is able to control the operation of terminal units such as fan coils.
Page 88
Follow us on Sabiana app SABIANA SpA Società a socio unico Via Piave 53 - 20011 Corbetta (MI) Italy T. +39 02 97203 1 r.a. • F. +39 02 9777282 info@sabiana.it www.sabiana.it...