Pqa - Real Time Measurement Of Network Parameters; Measurement Of Network Parameters In Single Phase Systems - T.I.S. INSTRUMENTS MFT-PRO Quick Reference Manual

Table of Contents

Advertisement

4.9.
PQA – REAL TIME MEASUREMENT OF NETWORK PARAMETERS
 The instrument can be used for measurements on installations with overvoltage category CAT III 240V
to earth and CAT III 415V between inputs. Category CAT III is suitable for measurements carried out on
installations inside buildings with low voltage (examples are distribution boards, wirings, switches, fixed
installation sockets, electric motors, industrial equipment)
 We recommend holding the alligator clip and the leads respecting the safety area created by the hand
protection (see § 2.4)
 The maximum voltage allowed between inputs B1 and B4 is equal to 460V. Exceeding such a limit
may cause electrical shock to the user or damage the instrument.
Access the general menu by pressing the HOME key
shows the following screen:
4.9.1.

Measurement of network parameters in Single phase systems

1. Select the "
" measurement and the desired full scale of the optional clamp by pushing the F3 key
or touch the
icon
2. Connect the optional clamp to the In1 input and the test leads for the voltage measurement as shown in
the below picture:
3.
4. The measurement is in real time and the results are shown at display
5. Push the F2 key or tuch the
of voltage and current by touching the icons at display for selection of the pages relative to the harmonics
of higher order (up to the 25
6. Press the SAVE key or touch the relevant icon
display. Confirm saving by pressing the SAVE key again, or the relevant icon.
For any details and for the measurement on Three phase balanced systems please refer to the user manual
of the instrument
CAUTION
icon for the visualization of harmonic analysis parameter (Hxx, THDx)
th
)
EN – 14
and select function
to save the result of measurement shown on the
MFT-PRO
Quick reference guide
. The instrument

Advertisement

Table of Contents
loading

Table of Contents