Important Notes Usage for the intended purpose Use level electrode NRG 6-42 only in conjunction with level switch NRS -42. Safety note The equipment must only be installed and commissioned by qualified and adequately trained personnel. Maintenance and retrofitting must only by performed by entrusted personnel who – through adequate training –...
Explanatory Notes Scope of supply NRG 16-42 Level electrode type NRG 6-42 Joint ring (of stainless steel .430) D 33 x 39 to DIN 7603, bright annealed Terminating resistor 20 Ω Installation manual Description The level electrode NRG 6-42 works according to the conductivity measurement principle. With the NRG 6-42 a maximum of 4 levels can be signalled in conductive liquids: ■...
Technical data NRG 16-42 Type Approval Nº TÜV · WR · 04-399 Max. service pressure 32 bar g at 238°C Connections Screwed " BSP, DIN ISO 228- Flanged DN 50, PN 40, DIN 2635 Materials Case: Die cast aluminium 3.26 (G AlSi8Cu3) Stem: S. S. .457 (X6CrNiMoTi7-2-2) Measuring electrodes: S.
(bending and alternating stress). The dimensional allowances for corrosion reflect the latest state of technology. Name plate / marking Betriebsanleitung beachten See installation instructions Voir instructions de montage Designation of NRG 16-42 the equipment PN 40 1.4571 IP 65 32 bar ( 464 psi) Pmax Tmax 238 °C...
Functional Elements NRG 16-42 MAX 70 °C MAX 70°C GESTRA Steam Systems MAX 95 % MAX 95% GESTRA IP 65 NRG 16-42 F G F Fig. 5 Fig. 6...
Page 11
Design / Functional Elements continued Thermal insulation, provided on site, d = 20 mm (outside of thermal insulation of the steam boiler) Seating surface Joint ring (of stainless steel .430) D 33 x 39 to DIN 7603, bright annealed Electrode thread " BSP, EN ISO 228- Housing screws M4 M 2 sensor connector, 5 poles, A-coded M 2 sensor jack, 5 poles, A-coded...
Installation NRG 16-42 . Determine required measuring lengths of electrode rods and enter data in table “Functions”. accordingly, Fig. 3 2. Cut electrode rods 3. Deburr faces of electrode tips. 4. Strip off 50 mm of PTFE insulation from the ends of electrode tips. 5.
Installation continued Flange PN 40, DN 50 (2"), DIN 2527 Flange PN 40, DN 00 (4"), DIN 2527 For the approval of the boiler standpipe with connecting flange the relevant regulations must be considered. Vent hole Provide vent hole as close as possible to the boiler wall. High water (HW) Electrode rod d = 5 mm Protection tube DN 80...
Wiring NRG 16-42 Note that screened multi-core twisted-pair control cable is required, e. g. UNITRONIC ® BUS CAN 2 x 2 x ... mm or RE-2YCYV-fl 2 x 2 x ... mm Prefabricated control cables (with connector and coupler) of various lengths for connecting the equipment are available as accessories.
Wiring continued Wiring diagram Code switch Electrode rod Electrode rod NRG 16-42 Electrode rod Electrode rod 24V DC e.g. UNITRONIC BUS CAN 2 x 2 x... ® CAN - Bus e.g. UNITRONIC BUS CAN 2 x 2 x... ® Terminating resistor 20 Ω, paired cable.
Wiring continued Attention Wire equipment in series. Star-type wiring is not permitted! ■ Interlink screens of control cables such that electrical continuity is ensured and ■ connect them once to central earthing point (CEP). In a CAN bus network the first and the last equipment must be provided with a ■...
Basic Settings CAN bus All level and conductivity controllers and associated electrodes are interconnected by means of a CAN bus adopting the CANopen protocol. Every item of equipment features an electronic address (Node ID). The four-core bus cable serves as power supply and data highway for high-speed data exchange. The CAN address (Node ID) can be set between 1 and 123.
Basic Settings continued Code switch settings for node ID / baud rate Node ID Node ID Fig. 13 (Factory setting) Fig. 14 (Example) Length of cable Baud rate 250 kBit/s 25 m 25 kBit/s 250 m 00 kBit/s 335 m 50 kBit/s 500 m 20 kBit/s 000 m 0 kBit/s 000 m Fig. 15 (Factory setting 250 kBit/s)
Commissioning Check wiring Check whether the level electrode NRG 6-42 and the associated level switch NRS -42 have been wired according to the wiring diagram. Fig. 11 Apply mains voltage Turn on the power for level switch NRS -42. Operation Level electrode with CAN bus During operation the level switch detects the level electrode via CAN bus. The communication via CAN bus is faultless –...
Page 22
Malfunctions continued Fault finding list for troubleshooting continued The equipment fails to work – no function Fault: LED “Power” does not light up. Remedy: Apply mains voltage. Wire equipment according to the wiring diagram. Fault: The thermal fuse has been triggered. Remedy: The ambient temperature must not exceed 70°C. The LED I does not light up. No data exchange. Fault: Remedy: Check level switch NRS -42.
Decommissioning Danger Risk of severe burns and scalds to the whole body! Before removing the level electrode make sure that the vessel and the measuring pot are depressurised (O bar) and cooled down to room temperature (20 °C). Disposal Remove the level electrode and separate the waste materials, using the material specifications as a reference.