5. After plumbing has been completed, tum on the Hot and
Cold water and check for leaks.
6. Now you can plug in the control panel into a GFI outlet.
The switch on the 6 x 6 gray box will turn the unit on.
The Controller will light up to let you know power is
present. Use the arrow buttons to set Controller to the
desired 73°F temperature. The word "OUT" will appear,
this is normal. (SV = set value) Make adjustments to
maintain temperature inside the room. Example: the set
temperature may need to be set at 69°F to maintain 73°F
inside the room. After each change, allow 24 hours for
the room to stabilize.
NOTE: The by-pass ball valve (extreme left on panel)
is normally closed. lf a power failure occurs, or the
electrical solenoid valve fails, the by-pass valve can be
opened for manual operation to flow water to the spray
heads. Also during a power failure, the Actuator can
be used in a manual mode. Turn power off then insert
a 3/16" Allen key into the top of the Actuator. Turn the
Allen key to the desired position, valve position toward
up is hotter, (counter clock wise) and valve position
going down is toward a cooler setting (clock wise).
The Temperature Controller, located at the far upper
right of the panel is an approximate indication of the
temperature. Adjust Controller up or down using a
thermometer or temperature recorder from inside the
room for precise measurements.
NOTE: ***Interior of room must be waterproofed***
NOTE: DO NOT DISCARD INSTRUCTIONS!
• Remember, this panel must be mounted on the outside of
a moisture room and indoors protected from water. Water
splashed on electrical components will void any warranty.
The Temperature Sensor is the only component designed
to be inside the moisture room.
• Any modifications or design changes without prior consent
or approval from the designer voids the warranty.
• Hot and Cold water supply must be available at or near
the panel.
• Minimum 40gal dedicated hot water tank.
• Must have a floor drain in room.
• 120V/60Hz/15A GFCI electrical outlet within 4 ft.of panel.
• Minimum Water pressure of 40psi.
• Tubing must be ½" copper or CPVC installed as a continuous
loop.
• 1.5gph Spray Heads at perimeter should be mounted at a
45° angle to the floor.
• System Runs 24hrs/day, 7days/week.